Application

The Robertshaw 9550 is a single-stage auto changeover thermostat designed to control 24 VAC gas or electric heating and cooling systems or a single-stage heat pumps. The 9550 requires the use of a common wire.

Features

  • Auto changeover [deadband adjustable from 2°F to 8°F (1.0°C – 4.5°C)]
  • Large backlit display
  • Adjustable temperature differential
  • Compressor short-cycle protection
  • Adjustable fan delay on cooling
  • LED indication of system status
  • Zone system compatible as a master thermostat
  • Battery-free EEPROM memory retention
  • Optional temperature-limiting settings
  • Fahrenheit/Celsius display option
  • Gas/electric operation
  • Adjustable from 45°F to 90°F (7°C – 32°C)
  • Quick wire terminal block

IMPORTANT SAFETY INFORMATION WARNING:

  • Always turn off power at the main power source by unscrewing the fuse or switching the circuit breaker to the off position before installing, removing, cleaning, or servicing the thermostat.
  • Read all the information in this manual before installing or programming this thermostat.
  • This is a 24 VAC low-voltage thermostat. Do not install on voltages higher than 30 VAC.
  • All wiring must conform to local and national building and electrical codes and ordinances.
  •  Do not short (jumper) across terminals on the gas valve or at the system control to test installation. This will damage the thermostat and void the warranty.

Step 1: Replacing the Existing Thermostat

  1. Turn off the power to the heating and cooling system.
  2. Remove the cover from the old thermostat to expose the wires (Figure 1).Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-1
  3. Disconnect wires one at a time from existing terminals. Use enclosed labels to mark existing wires. Refer to cross-references in Table 1 if existing wiring does not directly match the labels.NOTE: THIS THERMOSTAT REQUIRES A 24V COMMON WIRE FOR PROPER OPERATION
  4. If you have any questions about cross-referencing the old terminal to the new label, reference your equipment installation manual, a licensed contractor, or call Robertshaw Technical Support at (800) 445-8299.
  5. Remove the existing thermostat base from the wall.
Old Terminal New Label Description
R, V-VR or VR-R R 24 VAC, Return
Y, Y1 or M Y Cooling Control
Oor R O Cool Active Reversing Valve
B B Heat Active Reversing Valve
For G G Fan Control Relay
C, X or B C 24 VAC, Transformer Common Side
W1 or W W Heating Control

Recycling Thermostat
If this thermostat is replacing a thermostat that contains mercury in a sealed tube, do not place your old thermostat in the garbage. Contact your local waste management authority for instructions regarding the proper disposal of the thermostat. If you have any questions, call Robertshaw technical support at 1-800-445-8299.

Step 2: Installing Model 9550 Thermostat

NOTE: FOR NEW INSTALLATIONS, MOUNT THERMOSTAT ON INSIDE THE WALL, FIVE FEET ABOVE THE FLOOR. DO NOT INSTALL BEHIND A DOOR, IN A CORNER, NEAR AIR VENTS, IN DIRECT SUNLIGHT, OR NEAR ANY HEAT OR STEAM-GENERATING FIXTURES. INSTALLATION AT THESE LOCATIONS WILL AFFECT THERMOSTAT OPERATION.

  1. Turn the power off to the heating and cooling systems.
  2. Place AUTO-HEAT-OFF-COOL in the OFF position (Figure 2).
  3. Place -ON-AUTO switches into the AUTO position (Figure 2).Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-2
  4. Remove the cover using a coin or screwdriver (Figure 3). Set aside.Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-3
  5. Place the thermostat against the wall at the desired location. Make sure wires will feed through the opening (Figure 4) on the base of the thermostat.
  6. Mark placement of mounting holes (Figure 4). Set base aside.Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-4
  7. If mounting on drywall, tap plastic anchors into the wall.
    NOTE: ENCLOSED PLASTIC ANCHORS DO NOT REQUIRE A DRILLED HOLE FOR DRYWALL.
  8. Drill the marked holes using a 3/16″ drill bit if mounting on a surface other than drywall.
  9. Align the base with plastic anchors and feed wires through the opening.
  10.  Secure base to wall with supplied screws.
    NOTE: THE THERMOSTAT WILL MOUNT HORIZONTALLY ON A SINGLE GANG JUNCTION BOX.
  11.  Strip the end of wires 5/16” if needed.
  12. Terminal screws are already loose and ready for wire insertion. Insert wires into the terminal strip (Figure 5) matching the label to the corresponding terminal (see Wiring Diagrams below). Tighten screws.
  13.  Make sure wire connections are secure.
  14. Push the access wire back through the opening.Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-5

Wiring Diagrams for 9550

Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-6

TERMINALLEGEND 9550
TERM EQUIPMENT TOCONNECT REQ? TERMINAL FUNCTION
C 24VAC common connection Yes For input of 24VAC common side of the transformer
R 24VAC hot connection Yes For input of 24VAC hot side of the transformer
W First-stage heat convection Yes* Energizes on a call for heat
Y Second-stage heat convection No Energizes on a call for cooling
G Indoor fan connection Yes** Energizes with W (ELECTRIC mode only) and Yor with FAN option switched to the ON position
O Cool active reversing valve connection No*** Energizes when in the COOL mode
B Heat active reversing valve connection No*** Energizes when in the HEAT or EM modes

This thermostat can be used as a heat-only or cool-only thermostat therefore it is not always necessary to use both W and Y. A heat-only gas system typically will not require the G terminal connection unless a separate indoor blower is installed. Most heat pump systems will have a cool active OR a heat active reversing valve. Use the appropriate terminal. If using a single-stage heat pump system, set the switch to HP.

Set the GAS/ELEC switch to either GAS for a gas/oil heating system or ELEC for an electric heating system.

Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-7

A temperature-limiting jumper has been included in this thermo-stat. Cutting this jumper (J3) limits the heating setpoint to no greater than 72°F and the cooling setpoint to no lower than 78°F (Figure 7).

Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-8

Replace the thermostat cover by snapping it into place. Turn on the power to the system. Test the thermostat as described in the following section.

Step 3: Testing the Thermostat

WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS VALVE OR SYSTEM CONTROL TO TEST OPERATION. THIS WILL DAMAGE THE THERMOSTAT AND VOID YOUR WARRANTY.

CAUTION: DO NOT SWITCH THE SYSTEM TO COOL IF THE TEMPERATURE IS BELOW 50°F (10°C). THIS CAN DAMAGE THE AIR CONDITIONING SYSTEM AND CAUSE PERSONAL INJURY.

Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-9

  1. Place the AUTO-HEAT-OFF-COOL switch into the COOL position.
  2. Press the Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-10button until the temperature setting is at least 3 degrees below the room temperature. The air conditioning system should turn on within a few seconds.NOTE: ONCE THE THERMOSTAT TURNS OFF WHEN IN THE COOL MODE, ABUILT IN 5-MINUTE DELAY PREVENTS THE SYSTEM FROM TURNING ON AGAIN. THIS PROTECTS THE COMPRESSOR. NO ADDITIONAL TIME DELAY RELAY IS REQUIRED. TO OVERRIDE THE 5-MINUTE DELAY FOR INSTALLATION, PRESS THE RESET BUTTON.
  3. Put the AUTO-HEAT-OFF-COOL switch into the OFF position. The air conditioning system should turn off.Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-11
  4. Put the AUTO-HEAT-OFF-COOL switch into the HEAT position.
  5. Press the Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-12button until the temperature setting is at least 3 degrees above room temperature. The heating system should turn on. The fan may not turn on immediately, depending on the fan delay built into the furnace.Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-13
  6. Put the AUTO-HEAT-OFF-COOL switch into the OFF position. The heating system should turn off. The fan may continue to run for a short period of time.
  7. Put theRobertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-14 -ON-AUTO switches into the ON position. The blower fan should turn on.
  8. Put theRobertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-14 -ON-AUTO switches into the AUTO position. The blower fan should turn off.

Step 4: Customizing the Thermostat

Settings System

  • Cool: The thermostat controls the cooling.
  • Off: The heating and cooling systems are off.
  • Heat: The thermostat controls the heat.
  • AUTO: The thermostat automatically selects heat or cool depending on the temperature.

Fan
Auto: Equipment controls the fan.
On: The fan operates continuously.

Temperature
The default setpoint temperature for heating is 70°F (21°C), for cool-ing is 78°F (25°C), and for auto is 72°F (22.0°C). After putting the system switch in heat, cool, or auto, press either the Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-10or Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-12‚ button to adjust the temperature setting up or down. The display will return to the current room temperature five seconds after the last input and the new setpoint will be saved.

Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-15

Temperature Differential and Deadband

The temperature differential is factory set at 1°F (0.5°C). This means that whenever the room temperature changes by one degree Fahrenheit from the temperature setting, the system will turn on. If the system turns on too often, increase the temperature differential. Although programmed at the same time as the temperature differentials, the deadband is used only during the AUTO mode. In the AUTO mode, the thermostat will automatically cycle either the heating or cooling system to maintain optimal comfort. The deadband is the minimum allowable temperature which must occur to switch to the opposite mode. For example, if the deadband is set at 3°F (1.5°C)and the setpoint is set at 70°F, the thermostat will switch to cooling mode when the temperature reaches 73°F.
NOTE: IF THE TEMPERATURE LIMITING JUMPER J3 IS CUT (FIGURE 7), THE DEADBAND IS NOT ADJUSTABLE AND IS AUTOMATICALLY SET TO 6°F (3°C).

Changing Fahrenheit (F) to Celsius (C), Temperature Differential, Deadband, and Residual Cool
The temperature differential is factory set at 1°F (0.5°C). The deadband for auto changeover is set at 3°F (1.5°C). To change settings:

  1. 1. The thermostat is preset to display the temperature in degrees Fahrenheit (US models) or degrees Celsius (Canadian models). The temperature display can be changed.
    2. Press and hold both Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-10the Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-12 and  buttons for three seconds.
  2. The display will read F or C. Release the buttons. Press the  Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-10or  Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-12but-ton to switch the display.
    3. After three seconds the display will switch to the differential setting. The display will read DIFFERENTIAL 1st.
    4. The temperature differential is factory set at 1°F (0.5°C). Press the Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-10 or Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-12 to adjust the differential up or down.
  3. Either wait three seconds or press theRobertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-16 button. The display will indicate: AUTOCHANGE DEADBAND.
  4. Press either the Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-10 or Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-12button to adjust the deadband between 2.0°F – 8.0°F (1.0°C – 4.5°C).
  5. Either wait five seconds or Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-16press the button. The fan icon and ON will be displayed.
  6. Press either the Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-10 or Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-12button to adjust the residual cool fan delay between 0, 30, 60, or 90 seconds.
  7. The display will return to the original room temperature display after a few seconds.

LED Indicators
The Robertshaw 9550 uses three LED indicators (in addition to icons on the LCD display) to indicate the functionality of the thermostat. When illuminated, the right orange LED indicates that the thermostat is calling for heat. The left green LED indicates a call for cool. The middle amber LED indicates the fan is running

Backlit Display
This thermostat is equipped with a backlight to make nighttime temperature adjustments quick and easy. Press theRobertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-16 button to activate the backlight. The backlight will turn off after about 15 seconds of inactivity.

Reset
To reset the thermostat to factory preprogrammed conditions, press the RESET button located beneath the lower left corner of the display.

Robertshaw-9550-NON-PROGRAMMABLE-THERMOSTAT-FIG-17

Step 5: Troubleshooting

Symptom Remedy
The thermostat does not turn on the system. Check to wire (see Installation

section).

Thermostat turns system on and off too frequently. Increase temperature differential (see Changing the Temperature Differential section).
System fan does not operate properly. Move fan option switch to either gas or electric, to match system (see Installation section).
Thermostat does not display proper room temperature. Check F/C (Fahrenheit/Celsius) settings (see Changing Fahrenheit

(F) to Celsius (C) section).

If problems with thermostat cannot be resolved, call: Technical Support: (800) 445-8299
Monday-Friday 7:30 AM – 5:30 PM CST

Two-Year Limited Warranty

Climate Controls Americas warrants to the original contractor installer, or to the original consumer user, each new Robertshaw thermo-stat to be free from defects in materials and workmanship under normal use and service for a period of two (2) years from date of purchase. This warranty and our liability does not apply to batteries or merchandise that has been damaged by misuse, neglect, mishandling, alterations, improper installation, or use in a way other than in accordance with Climate Controls Americas recommendations and instructions.
Climate Controls Americas agrees to repair or replace at its option any thermostat under warranty provided it is returned within the warranty period, postage prepaid, with proof of the date of purchase. Cost of thermostat removal or reinstallation is not the responsibility of Climate Controls Americas. Repair or replacement as provided under this warranty is the exclusive remedy of the consumer. Climate Controls Americas shall not be liable for any incidental or consequential damages for breach of any express or implied warranty on this product, or under any other theory of liability. Except to the extent prohibited by applicable law, any implied warranty of merchantability or fitness for a particular purpose on this product is limited to the duration of this warranty.

Some states do not allow the exclusion or limitation of incidental or consequential damages, or allow limitations on how long an implied warranty lasts, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. For warranty returns, send thermostat, shipping prepaid to: Invensys Climate Controls Americas
Warranty Claims Department
515 S. Promenade Corona, CA 91719 Climate Controls Americas 191 E.
North Avenue Carol Stream Illinois 60188 United States of America ©2003 Climate Controls Americas

Reference:

Download Manual:

Robertshaw 9550 NON-PROGRAMMABLE THERMOSTAT User Manual

Robertshaw logo

Robertshaw 9550 NON-PROGRAMMABLE THERMOSTAT User Manual


Posted

in

by

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *