peco-logo

PECO T168 Proportional THERMOSTAT 

PECO-T168-Proportional-THERMOSTAT-PRODUCT

INSTALLATION

  1. Install the T168 with the two furnished mounting screws to a standard 4 1/16” x 2 1/8” square device box with a 2” x 4” adapter ring.
  2. For wall installations, mount the thermostat on an inside wall approximately 5 feet above the floor. The locations should provide circulation at an average room temperature. Avoid direct sunlight or sources of hot or cold air in the room.
  3. Remove the cover. Mount the thermostat base assembly to the outlet box using the screws provided. Tighten the screws evenly but do not overtighten. Connect wires per the wiring diagram.
  4. To use a remote sensor on units with local sensing capability, remove jumper JP-1 to disable local sensing. Failure to remove JP-1 will cause improper operation of the thermostat.
  5. Connecting a jumper between terminals 16 and 17 will disable the secondary output and change the main output to heat mode.
  6. The connection of a 24 VAC setback signal will force the control into an unoccupied mode (see diagram). Pressing an arrow key or the mode buttons on the thermostat cover will disable the setback input for one hour.
  7. Remove the LCD plastic protective film to complete the installation. Reinstall the cover assembly. Install the cover locking screw provided.
  8. Checkout: After wiring and installation are complete, energize the system and check the operation. Adjust the thermostat as necessary to complete at least one cycle. Be sure the thermostat and all other equipment are functioning correctly.

CAUTION

MOUNTING

PECO-T168-Proportional-THERMOSTAT-FIG.1

WARNING

WIRING DIAGRAM

PECO-T168-Proportional-THERMOSTAT-FIG.2

ELECTRICAL RATING

ELECTRICAL RATINGS
Fan Switch (Terminals 1-4) Line Voltage Connections
Voltage Inductive  

Resistive

 

Pilot

Thermostatic Switching/ Low Voltage
FLA LRA
24 VAC N.A. N.A. N.A. 24 VA 10 VA
120 5.8 34.8 6.0 125 VA N.A.
240 2.9 17.4 5.0 125 VA N.A.
277 2.4 14.4 4.2 125 VA N.A.

APPLICATION NOTES

  1. When no changeover pipe sensor is used, the main output controls cooling and the secondary output controls heating.
  2. The fan output, terminal 12, is energized whenever there is a demand for heating or cooling. This output can be connected to a relay that can be used to provide fan cycling to terminal 1.
  3. The changeover pipe sensor should be mounted on the main coil input for water system operation and in the main duct system for forced air operation.
  4. The set point and operating mode will be retained on a loss of power.
  5. When using either a remote probe or pipe sensor, run the wiring away from any electrical motors or power wiring.
  6. The auxiliary heat output supplies a 24 VAC signal with a call for heat. This output is shipped configured for staged heat.
  7. The thermostat is shipped with all dip switches in the “ON” (closed) position.
  8. The damper output is ON when the mode is AUTO, HEAT or COOL, the damper is OFF in set back.

THERMOSTAT OPERATION

These thermostats are designed to control 0-10 VDC/4-0 mA valves. These units may include a fan switch with one or more fan speed selections.

MODE BUTTON OPERATION

CONFIGURATION

CIRCUIT BOARD JUMPER CONFIGURATION
Jumper

Designation

Closed

ON*

Open OFF
JP1 Local Sensing Remote Sensing
 

JP2

 

2 Pipe System

 

4 Pipe System

 

JP3

 

Factory Use Only

JP4 0-10 VOC

Main Output

4-20 mA

Main Output

JP5 0-10 VOC

Secondary Output

4-20 mA

Secondary Output

DIP SWITCH CONFIGURATION
Switch

Designation

Closed On* Open

Off

 

1

Not Used  

Not Used

 

2

Staged Heat 3°F Diff. (Term. 13) Aux. Heat No Diff. (Term. 13)
3 F Display C Display
 

4

Main & Sec. Outputs

0-10 VOC (Term. 10 & 11)

requires JP4 & JP5

Main & Sec. Outputs 4-20 mA (Term. 10 & 11)

Remove JP4 & JP5

 

5

Operating Position Not Used
6 Setback= 90°F & 50°F Setback = 85°F & 60°F

PECO-T168-Proportional-THERMOSTAT-FIG.3

Service Menu:

Item # Function Range Default
1 Zone Temp Offset -5.1F to 5.1F 0F
2 Valve Stroke Time 30 sec. To 5 min. 120 sec.
3 Fan Delay to OFF 2 to 10 Minutes 120 Sec.
4 Compressor Minimum Off Time 30 Sec. To 10 min. 120 Sec.
5 Purge Cycle 0 = Time-Based

1 = Temperature Based

1

REFERENCE:

DOWNLOAD MANUALS:

PECO T168 Proportional THERMOSTAT Installation Guide

OTHER MANUALS:

PECO T168 Proportional Thermostats Product Specifications Guide

peco-logo

PECO T168 Proportional THERMOSTAT Installation Guide

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)