Panasonic V1.00 KNX Room Thermostat
Functional characteristics
Room temperature controller sense the current room temperature and controls the heating and/or cooling. It is also controls Fan coil units. Device has 2 different weekly switching programs which can be programed separately by user. The display is backlighted for easier reading. The Room temperature controller is fitted with push-switches and an LCD to show the current operating modes and values. A separate bus coupling unit is not required. The room temperature controller does not require an auxiliary power supply. The Engineering Software Tool (from ETS3-f) is used to assign the physical address and set the parameters.
Technical data
General | |
Power supply | Bus voltage. |
Permitted operating temperature | -5 °C… + 45°C |
Current draw from bus voltage | Max 10 mA |
Bus connection | Bus terminal |
Type of protection | IP 20 to EN 60529 |
Application programs
Selection in the product database
Manufacturer | Panasonic |
Product group | Heating, ventilation, air condition |
Product type | Thermostat |
Program names | Room Thermostat MD, Room Thermostat STD |
Program version | 1.0 1.0 |
Number of communication objects: | 25 |
Number of group addresses: | 128 |
Number of assignments: | 128 |
Communication objects
Table 1: Object Overview
Obj. No | Object name | Function | Size | Datapoint type | Flags | ||||
C | R | W | T | U | |||||
0 | Actual temperature value | Transmit actual value | 2 Bytes | 9.001 – DPT_Value_Temp | ü | ü | ü | ||
1 | Current operation mode | Indicate operation mode | 1 Byte | 20.102 – DPT_HVACMode | ü | ü | ü | ü | |
2 | Presence Input | Input for presence signal | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | ||
3 | Window State | Input for window contact | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | ||
4 | Heating base setpoint | Define set point value | 2 Bytes | 9.001 – DPT_Value_Temp | ü | ü | ü | ||
5 | Cooling base setpoint | Define set point value | 2 Bytes | 9.001 – DPT_Value_Temp | ü | ü | ü | ||
6 | Current Setpoint | Indicate/adjust set point | 2 Bytes | 9.001 – DPT_Value_Temp | ü | ü | ü | ü | |
7 |
Heating Switching Control Value | Transmit actuating value | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | ||
Heating Continuous Control
Value |
Transmit actuating value | 1 Byte | 5.001 – DPT_Scaling | ü | ü | ü | |||
8 |
Cooling Switching Control Value | Transmit actuating value | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | ||
Cooling Continuous
Control Value |
Transmit actuating value | 1 Byte | 5.001 – DPT_Scaling | ü | ü | ü | |||
9 |
Switchover between
heating and cooling |
heating=0, cooling=1 | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | ü | |
Report heating or cooling mode | heating=0, cooling=1 | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | |||
10 | Reset manual operations | Reset=1 | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | ||
11 | Fan mode (manual/auto) | 1=manual, 0=auto | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | ü | |
12 |
Fan level | send/receive fan level
0-100 % |
1 Byte | 5.001 – DPT_Scaling | ü | ü | ü | ü | ü |
Fan level | send/receive fan level
0-3 |
1 Byte | 5.010 – DPT_Value_1_Ucount | ü | ü | ü | ü | ü | |
13 | LCD backlight | on/off backlight | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | ||
14 | Time | Receive time | 2 Bytes | 10.001 – DPT_TimeOfDay | ü | ü | ü | ||
15 | Time query | Request for time | 1 Bit | 1.002 – DPT_Bool | ü | ü | ü | ||
16 | Date | Receive date | 3 Bytes | 11.1 – DPT_Date | ü | ü | ü | ||
17 | Date query | Request for date | 1 Bit | 1.002 – DPT_Bool | ü | ü | ü | ||
18 | Switching program lock | Lock=1 | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | ||
19 | Heating PWM Control Value | Transmit actuating value | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | ||
20 | Cooling PWM Control Value | Transmit actuating value | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | ||
21 | Fan level | send/receive fan level 1 | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | ü | ü |
22 | Fan level | send/receive fan level 2 | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | ü | ü |
23 | Fan level | send/receive fan level 3 | 1 Bit | 1.001 – DPT_Switch | ü | ü | ü | ü | ü |
24 | Fan unit | Send on/off | 1 Bit | 1.001 – DPT_Switch | ü | ü |
Explanation of the flags
Flag | Flag name | Description |
C | Communication | Object has a connection with bus. |
R | Read | Object can be read from bus. |
W | Write | Value can be written to object from bus. |
T | Transmit | Object can send data to bus. |
U | Update | Object updated with any response telegram. |
Description of objects
Obj. No | Object name | Function | Description |
0 |
Actual temperature value |
Transmit actual value |
This object sends the temperature currently being measured by the sensor. |
1 |
Current operation mode |
Indicate operation mode |
Transmits the current operation mode as a 1 byte value (see below: Coding of operation modes).
Coding of HVAC operation modes: |
2 |
Presence Input |
Input for presence signal |
The status of a presence indicator (e.g. sensor, movement detector) can be received via this object. 1 on this object activates the comfort operation mode. |
3 |
Window State |
Input for window contact |
The status of a window contact can be received via this object.
1 on this object activates the frost / heat protection operation mode. |
No | |||
4 |
Heating base setpoint |
Define set point value |
The Heating base setpoint value is first specified via the application (ETS) at start-up and stored in the “Heating base setpoint value” object.
This object can be changed any time via bus (limited by minimum or maximum valid setpoint value). If this object value is changed via bus that value is written as Heating comfort setpoint value. Also standby and night setpoints are updated as parameterized in ETS. |
5 |
Cooling base setpoint |
Define set point value |
The Cooling base setpoint value is first specified via the application (ETS) at start-up and stored in the “Cooling base setpoint value” object.
This object can be changed any time via bus (limited by minimum or maximum valid setpoint value). If this object value is changed via bus that value is written as Cooling comfort setpoint value. Also standby and night setpoints are updated as parameterized in ETS. |
6 |
Current Setpoint |
Indicate/adjust set point |
This object sends the current setpoint temperature to bus. Current setpoint value can be changed via this object from bus. |
7 |
Heating Switching
Control Value |
Transmit actuating value | Sends the current heating actuating value (0-1) |
Heating Continuous
Control Value |
Transmit actuating value | Sends the current heating actuating value (0…100%) | |
8 |
Cooling Switching Control Value | Transmit actuating value | Sends the current cooling actuating value (0-1) |
Cooling Continuous
Control Value |
Transmit actuating value | Sends the current cooling actuating value (0…100%) | |
9 |
Switchover between heating and cooling |
heating=1, cooling=0 |
The function of the object depends on the “Control Function” parameter on the “Controller General” parameter page.
Automatic: Reports whether the room thermostat is currently operating in heating or cooling mode.
Via object: Receives the switching command for switching between heating and cooling mode. |
Report heating or cooling mode |
|||
10 | Reset manual operations | Reset=1 | |
11 | Fan mode (manual/auto) | 0=manual, 1=auto | Sends fan mode to bus. |
12 |
Fan level |
send/receive fan level 0-100 % |
If a manual fan mode is selected on the device, this object sends a percentage value that corresponds to the configured threshold value. |
Fan level | send/receive fan level
0-3 |
This object sents counter value from 0 to 3 as fan level. |
No | |||
13 |
LCD backlight |
on/off backlight |
Enables switching on and off of LCD backlighting via the bus.
This means, for example, that all displays can be turned off simultaneously. |
14 |
Time |
Receive time |
Receives time (with weekday) from the bus in KNX DPT 10.001 format in order to set the internal clock. |
15 |
Time query |
Request for time |
Sends automatically a time query to the time transmitter after restoration of the bus, reset and/or download.
If the time cannot be received, then sends a new time query every 5 minutes. |
16 |
Date |
Receive date |
Receives date from the bus in KNX DPT_Date (11.001) format in order to set the internal date. |
17 |
Date query |
Request for date |
Sends automatically a date query to the time transmitter after restoration of the bus, reset and/or download.
If the date cannot be received, then sends a new date query every 5 minutes. |
18 | Switching program lock | Lock=1 | Makes the time program inoperative. |
19 |
Heating PWM Control Value |
Transmit actuating value |
The actuating value in object 7 is emitted as a PWM signal (ON/OFF). |
20 |
Cooling PWM Control Value |
Transmit actuating value |
The actuating value in object 8 is emitted as a PWM signal (ON/OFF). |
21 | Fan level | send/receive fan level 1 | Activates related fan level |
22 | Fan level | send/receive fan level 2 | Activates related fan level |
23 | Fan level | send/receive fan level 3 | Activates related fan level |
24 |
Fan unit |
Send on/off |
If fan level Off is selected this object sends OFF telegram. If fan level auto, 1, 2 or 3 is selected this object sends ON telegram. |
Parameters
The General parameter page
Designation | Values | Description |
Settings menu on device |
Disable
Enable |
Selection of setting menu on device: press and hold menu key for 3 seconds.
Operation not possible Operation possible |
Operation mode after reset |
Comfort
Standby Night Frost/Heat Protection |
Operation mode after start-up or reprogramming. |
Fan Control | Disable
Enable |
Fan control option is inactive
Fan control is active. “Fan Control” page and “Fan Objects” appears. |
Transmit operation mode and fan step | not cyclically, only at change
every 2 min. every 3 min. every 5 min. every 10 min. every 15 min. every 20 min. every 30 min. every 45 min. every 60 min. |
How often should the current operation mode and current fan level be sent?
Fan level is sent only if “Fan Mode” is not in auto mode. |
The Controller General parameters page
Designation | Values | Description |
Switching program after reset |
No program User defined program 1 User defined program 2 Default program 1 Default program 2
Unchange |
Device has 2 switching program PRG1 and PRG2.
After start-up or reprogramming, the device: runs without any switching program
Runs with PRG1.(If adjusted keeps user defined switching program settings)
Runs with PRG2.(If adjusted keeps user defined switching program settings)
Runs with PRG1. (Reset PRG1 to default settings)
Runs with PRG2.(Reset PRG2 to default settings)
Don’t change current switching program. *Before select this setting Date-Time should be set from bus or manually. |
Language after download |
Deutsch English Español Français Polski Русский Türkçe |
Select user interface language. |
Select date-time object | Time object only
Time + Date object |
Only time of day object is active. Time and day of week could be adjusted from bus.
Time of day and date objects are active. Date and time can be changed from bus. |
The Temperature Measurement parameter page
Designation | Values | Description |
Offset for temperature sensor 0.1K Steps
(-50..50) |
Value from -50 to 50
Default value = 0 |
Positive or negative adjustment of measured temperature in 1/10 increments.
Examples: a) -This thermostat sends 20.3°C. – The room temperature of 21.0°C is measured using a calibrated thermometer. 21.0 – 20.3 = 0.7K must be added to thermostat for correction. 0.7 / 0.1 = 7 must be entered as offset.
b) -This thermostat sends 21.5°C. -The room temperature of 20.1°C is measured using a calibrated thermometer. 20.1 – 21.5 = -1.4K must be added to thermostat for correction. -1.4/ 0.1 = -14 must be entered as offset. |
Transmit actual temperature at change | Inactive
0.2 K 0.3 K 0.5K 0.8K 1K 1.5K 2.0K |
Don’t send actual temperature value on value change event.
Send actual value on specified change value. |
Transmit actual temperature cyclically | Not cyclically, only at change
every 2 min. every 3 min. every 5 min. every 10 min. every 15 min. every 20 min. every 30 min. every 45 min. every 60 min. |
Sending period of actual temperature value to bus. |
The Setpoints parameter page
Designation | Values | Description |
Heating setpoint base |
15°C, 16°C ……31°C, 32°C |
Base setpoint which is assigned to heating comfort setpoint value after ETS download. |
Heating reduction standby | 1K, 2K ….9K,10K | Reduction value to optain standby setpoint value from base setpoint.
Ex: Heating base setpoint is 21°C,heating reduction value is 2K than standby setpoint value is; 21-2=19°C |
Heating reduction night | 1K, 2K ….9K,10K | Reduction value to optain night setpoint value from base setpoint. |
Heating setpoint frost
protection |
1°C, 2°C ….14°C,15°C | Setpoint value to start frost protection |
Cooling setpoint base | 15°C, 16°C ……31°C, 32°C | Base setpoint which is assigned to cooling comfort setpoint value after ETS download. |
Cooling increase standby | 1K, 2K ….9K,10K | Increase value to optain standby setpoint value from base setpoint. |
Cooling increase night | 1K, 2K ….9K,10K | Increase value to optain night setpoint value from base setpoint. |
Cooling setpoint heat
protection |
30°C, 31°C ….39°C,40°C | Setpoint value to start heat protection |
Maximum allowed manual setpoint offset | Manual offset not allowed
+/- 1K +/- 2K . . +/- 6K +/- 7K |
Manually maximum shift the setpoint values by user. |
Transmit current setpoint cyclically | Not cyclically, only at change
every 2 min. every 3 min. every 5 min. every 10 min. every 15 min. every 20 min. every 30 min. every 45 min. every 60 min. |
Sending period of current setpoint value to bus. |
The Heating Control parameter page
Designation | Values | Description |
Heating controller type | 2 Step
Continuous |
This function allows you to specify the mode of control.
You can select “2-step control” or “Continuous control” |
2 Step Parameters | ||
Heating hysteresis | 0.2K | Set a hysteresis value to ensure that the valve |
0.4K | does not constantly switch with each minor | |
0.6K | under and overshoot when using 2-step | |
0.8K | control of the actuator. | |
1.0K | The hysteresis value lies around the setpoint. | |
1.2K | For example, if the setpoint is 21 °C and the | |
1.4K | hysteresis is 1 K, the room thermostat only | |
1.6K | sends an “on” signal at 21.5 °C and an “off” | |
1.8K | signal at 20.5 °C. This parameter is only | |
2.0K | available if “2-step ” is set as the control type. | |
Heating invert control value | no
yes |
This parameter is used to adjust the direction of control action of the control value to “de- energised open” or “de-energised closed” valves. |
Continuous Parameters | ||
Heating PI parameter type | Via type of system
User defined |
Standard applications
Professional applications. Adjust PI controller parameters. |
Heating type of the system | PI control with: | |
Warm water heating | Integrated time = 100 minutes Bandwidth = 1.5K | |
Electric heating | Integrated time = 50 minutes Bandwidth = 1.5K | |
Floar heating | Integrated time =200 minutes Bandwidth = 4.0K | |
Split unit | Integrated time = minutes Bandwidth = k |
Designation | Values | Description |
Heating proportional band | 0.5K, 1.0K, 1.5K, 2.0K, 2.5K,
3.0K,3.5K, 4.0K, 4.5K, 5.0K, 5.5K, 6.0K, 6.5K, 7.0K, 7.5K, 8.0K, 8.5K, 9.0K, 9.5K, 10K |
Professional setting for adapting control response to the room.
Small values cause large changes in control variables, larger values cause finer control variable adjustment. |
Heating integral reset time | Value from 0 to 250 | Professional setting:
See appendix: Response of the PI controller This time can be adapted to suit particular circumstances. If the heating system is over- dimensioned and therefore too fast, shorter values should be used. Conversely, under-dimensioned heating (slow) benefits from longer integrated times. |
Heating PWM cyclic time(Min.) | Value from 1 to 60 | An actuation cycle consists of a switch-on and a switch-off
process and forms a PWM period.
Example: Actuating value= 20%, PWM time = 10 min: In an actuating cycle of 10 min, 2min switched on and 8 min switched off (i.e. 20% on/ 80% off). |
Transmit control value at change of | %1
%2 %3 %4 %5 … %12 %13 %14 %15 |
After how much % change* in the control variable is the new value to be sent. Small values increase control accuracy but also the bus load.
*Change since last transmission |
Heating transmit control value cyclically | Not cyclically, only at change
every 2 min. every 3 min. every 5 min. every 10 min. every 15 min. every 20 min. every 30 min. every 45 min. every 60 min. |
How often is the current heating actuating value to be sent (regardless of changes)? |
The Cooling Control parameter page
Designation | Values | Description |
Cooling controller type | 2 Step
Continuous |
See heating description. |
2 Step Parameters | ||
Cooling hysteresis | 0.2K
0.4K 0.6K 0.8K 1.0K 1.2K 1.4K 1.6K 1.8K 2.0K |
See heating description. |
Cooling invert control value | no
yes |
See heating description. |
Continuous Parameters | ||
Cooling PI parameter type | Via type of system
User defined |
See heating description. |
Cooling type of the system |
Cool ceiling
Split unit |
PI control with:
Integrated time = 225 minutes Bandwidth = 5K
Integrated time = 90 minutes Bandwidth = 4K |
Cooling proportional band | 0.5K, 1.0K, 1.5K, 2.0K, 2.5K,
3.0K,3.5K, 4.0K, 4.5K, 5.0K, 5.5K, 6.0K, 6.5K, 7.0K, 7.5K, 8.0K, 8.5K, 9.0K, 9.5K, 10K |
See heating description. |
Cooling integral reset time | Value from 0 to 250 | See heating description. |
Cooling PWM cyclic time(Min.) | Value from 1 to 60 | See heating description. |
Transmit control value at change of | %1
%2 %3 %4 %5 … %12 %13 %14 %15 |
See heating description. |
Designation | Values | Description |
Cooling transmit control value cyclically | Not cyclically, only at change
every 2 min. every 3 min. every 5 min. every 10 min. every 15 min. every 20 min. every 30 min. every 45 min. every 60 min . |
See heating description. |
System type | 2 pipe system
4 pipe system |
Heating control value object and cooling control value object must have same group address.
Heating control value object and cooling control value object must be used in different group objects. |
The Fan Control parameter page
Designation | Values | Description |
Fan level object type | 1-Byte object, percentage value 0-100
1-Byte object, counting value 0-3
1-Bit objects |
The selected fan stage can be sent via a
1-byte object with the continuous value from 0 to 100 %.
The selected fan stage can be sent via a 1-byte object as a counter value from 0 to 3.
When 1-bit values are selected, a 1-bit communication object is available for every fan stage. |
Value for fan level 1 | Percentage from %0 to %100
10 |
Available if “1-Byte object, percentage value 0-100” is selected.
Threshold value for the specific stage. |
Value for fan level 2 | Percentage from %0 to %100
60 |
Available if “1-Byte object, percentage value 0-100” is selected.
Threshold value for the specific stage. |
Value for fan level 3 | Percentage from %0 to %100
100 |
Available if “1-Byte object, percentage value 0-100” is selected.
Threshold value for the specific stage. |
Switchover fan auto and manual mode |
Via object ”Fan mode auto/manual”, auto is 0
Via object ”Fan mode auto/manual”, auto is 1 |
Effect of fan mode object to adapt to the used fan coil actuator. |
User Interface
Keys and Screen
Change operation mode
Change current setpoint value
- Press MENU (two times) to select current setpoint value.
- Press
to set the desired setpoint value.
- Press OK to confirm.
- You can instantly change the setpoint value via buttons
Change fan level
- Press MENU (there times) to select fan level.
- Press
to set the desired fan level.
- Press OK to confirm.
- You can easy select fan level via OK button.
- Press MENU for 3 seconds to enter settings menu
- Press
to select desired line.
- Press OK to enter.
- Press MENU to go back.
Summer / Winter
This line is available only if “Via object ” is selected for parameter “Switchover between heating and cooling”.
Temperature
- Adjust setpoint values for different operation modes and different control functions.
- Press OK to move betweet setpoints.
- Each value can be set separately. Maximum and minimum limits are applied automatically
Switching Program
- Select program 1 or program 2 for configuration.
- All Days This settings will effect all day. Every day same switching program will be executed.
- Weekdays This settings will effect only weekdays.
- Weekend This settings will effect only Saturday and Sanday.
- Days Every day from Monday to Sunday can be set individually.
- Reset Clear this program to preset values. See appendix for preset program values
- Set user defined switching program.
- There are 4 time periods.
- Start and end times of all periads can be set.
- Operation modes for those time period can be set.
- Ex: Lets see settingd on the left side picture
Program 1 / Program 2
- Select active switcing program.
- PRG 1 Program 1 is active
- PRG 2 Program 2 is active
- NO PRG Swithing programsa re disabled.
Language
- Select user language.
- Press to select desired language.
- Press OK to select
Date, Time
- Adjust date and time.
- If some field are “- -“ it means date is not set by user . Please set date.
- Date and time can be set manually from thermostat or can be received from the bus.
- Thermostat keeps date and time up to 10 hours when power off. After this time period date and time will be reset. Please check setting after long power off periods.
Display
- Adjust brightness level of the display and light on/off option.
- Light : On Light is always on
- Off Light is always on
- Key Light is on when one of key is pressed.
Startup Behaviour
Object number | Object name | Description |
6 | Current Setpoint | Depending to current operation mode sends set point value. |
7 | Heating Switching Control Value |
If ETS parameter “Control function” is selected as “Heating and Cooling” both heating and cooling objects will be available. Otherwise only heating or |
Heating Continuous Control Value |
Object
number |
Object name | Description |
8 |
Cooling Switching Control Value | cooling objects will be available.
These objects send value different from At start up thermostat runs controller functions ; n If controller decided to heat the room then cooling objects are set to 0. n If controller decided to cool the room then heating objects are set to 0 n If no heating or cooling is required then both heating and cooling objects are set to 0. |
Cooling Continuous Control Value | ||
19 | Heating PWM Control Value | |
20 | Cooling PWM Control Value | |
9 | Report heating or cooling mode | This object reports if thermostat is in heating mode or cooling mode. This is not related with controller outputs. |
11 | Fan mode (manual/auto) | Sends fan auto mode data to bus. |
15 | Time query | Sends 1 bus. |
17 | Date query | Sends 1 bus. |
REFERENCE:
DOWNLOAD MANUALS:
Panasonic V1.00 KNX Room Thermostat User Manual
Leave a Reply