Panasonic -V1.00- KNX- Room- Thermostat FEA

Panasonic V1.00 KNX Room Thermostat User Manual

panasonic logo

Panasonic V1.00 KNX Room Thermostat  

Panasonic -V1.00- KNX- Room- Thermostat PRO

Functional characteristics

Room temperature controller sense the current room temperature and controls the heating and/or cooling. It is also controls Fan coil units. Device has 2 different weekly switching programs which can be programed separately by user. The display is backlighted for easier reading. The Room temperature controller is fitted with push-switches and an LCD to show the current operating modes and values. A separate bus coupling unit is not required. The room temperature controller does not require an auxiliary power supply. The Engineering Software Tool (from ETS3-f) is used to assign the physical address and set the parameters.

Technical data

General
Power supply Bus voltage.
Permitted operating temperature -5 °C… + 45°C
Current draw from bus voltage Max 10 mA
Bus connection Bus terminal
Type of protection IP 20 to EN 60529

Application programs

Selection in the product database

Manufacturer Panasonic
Product group Heating, ventilation, air condition
Product type Thermostat
Program names Room Thermostat MD, Room Thermostat STD
Program version 1.0                                  1.0
Number of communication objects: 25
Number of group addresses: 128
Number of assignments: 128

Communication objects

Table 1: Object Overview

Obj. No Object name Function Size Datapoint type Flags
C R W T U
0 Actual temperature value Transmit actual value 2 Bytes 9.001 – DPT_Value_Temp ü ü ü
1 Current operation mode Indicate operation mode 1 Byte 20.102 – DPT_HVACMode ü ü ü ü
2 Presence Input Input for presence signal 1 Bit 1.001 – DPT_Switch ü ü ü
3 Window State Input for window contact 1 Bit 1.001 – DPT_Switch ü ü ü
4 Heating base setpoint Define set point value 2 Bytes 9.001 – DPT_Value_Temp ü ü ü
5 Cooling base setpoint Define set point value 2 Bytes 9.001 – DPT_Value_Temp ü ü ü
6 Current Setpoint Indicate/adjust set point 2 Bytes 9.001 – DPT_Value_Temp ü ü ü ü
 

7

Heating Switching Control Value Transmit actuating value 1 Bit 1.001 – DPT_Switch ü ü ü
Heating Continuous Control

Value

Transmit actuating value 1 Byte 5.001 – DPT_Scaling ü ü ü
 

8

Cooling Switching Control Value Transmit actuating value 1 Bit 1.001 – DPT_Switch ü ü ü
Cooling Continuous

Control Value

Transmit actuating value 1 Byte 5.001 – DPT_Scaling ü ü ü
 

9

Switchover between

heating and cooling

heating=0, cooling=1 1 Bit 1.001 – DPT_Switch ü ü ü ü
Report heating or cooling mode heating=0, cooling=1 1 Bit 1.001 – DPT_Switch ü ü ü
10 Reset manual operations Reset=1 1 Bit 1.001 – DPT_Switch ü ü ü
11 Fan mode (manual/auto) 1=manual, 0=auto 1 Bit 1.001 – DPT_Switch ü ü ü ü
 

12

Fan level send/receive fan level

0-100 %

1 Byte 5.001 – DPT_Scaling ü ü ü ü ü
Fan level send/receive fan level

0-3

1 Byte 5.010 – DPT_Value_1_Ucount ü ü ü ü ü
13 LCD backlight on/off backlight 1 Bit 1.001 – DPT_Switch ü ü ü
14 Time Receive time 2 Bytes 10.001 – DPT_TimeOfDay ü ü ü
15 Time query Request for time 1 Bit 1.002 – DPT_Bool ü ü ü
16 Date Receive date 3 Bytes 11.1 – DPT_Date ü ü ü
17 Date query Request for date 1 Bit 1.002 – DPT_Bool ü ü ü
18 Switching program lock Lock=1 1 Bit 1.001 – DPT_Switch ü ü ü
19 Heating PWM Control Value Transmit actuating value 1 Bit 1.001 – DPT_Switch ü ü ü
20 Cooling PWM Control Value Transmit actuating value 1 Bit 1.001 – DPT_Switch ü ü ü
21 Fan level send/receive fan level 1 1 Bit 1.001 – DPT_Switch ü ü ü ü ü
22 Fan level send/receive fan level 2 1 Bit 1.001 – DPT_Switch ü ü ü ü ü
23 Fan level send/receive fan level 3 1 Bit 1.001 – DPT_Switch ü ü ü ü ü
24 Fan unit Send on/off 1 Bit 1.001 – DPT_Switch ü ü

Explanation of the flags

Flag Flag name Description
C Communication Object has a connection with bus.
R Read Object can be read from bus.
W Write Value can be written to object from bus.
T Transmit Object can send data to bus.
U Update Object updated with any response telegram.

Description of objects

Obj. No Object name Function Description
 

0

 

Actual temperature value

 

Transmit actual value

This object sends the temperature currently being measured by the sensor.
 

 

 

 

 

 

1

 

 

 

 

 

 

Current operation mode

 

 

 

 

 

 

Indicate operation mode

Transmits the current operation mode as a 1 byte value (see below: Coding of operation modes).

 

Coding of HVAC operation modes:

 

 

2

 

 

Presence Input

 

 

Input for presence signal

The status of a presence indicator (e.g. sensor, movement detector) can be received via this object. 1 on this object activates the comfort operation mode.
 

 

3

 

 

Window State

 

 

Input for window contact

The status of a window contact can be received via this object.

1 on this object activates the frost / heat protection operation mode.

No
 

 

 

4

 

 

 

Heating base setpoint

 

 

 

Define set point value

The Heating base setpoint value is first specified via the application (ETS) at start-up and stored in the “Heating base setpoint value” object.

This object can be changed any time via bus (limited by minimum or maximum valid setpoint value). If this object value is changed via bus that value is written as Heating comfort setpoint value. Also standby and night setpoints are updated as parameterized in ETS.

 

 

 

5

 

 

 

Cooling base setpoint

 

 

 

Define set point value

The Cooling base setpoint value is first specified via the application (ETS) at start-up and stored in the “Cooling base setpoint value” object.

This object can be changed any time via bus (limited by minimum or maximum valid setpoint value). If this object value is changed via bus that value is written as Cooling comfort setpoint value. Also standby and night setpoints are updated as parameterized in ETS.

 

6

 

Current Setpoint

 

Indicate/adjust set point

This object sends the current setpoint temperature to bus. Current setpoint value can be changed via this object from bus.
 

7

Heating Switching

Control Value

Transmit actuating value Sends the current heating actuating value (0-1)
Heating Continuous

Control Value

Transmit actuating value Sends the current heating actuating value (0…100%)
 

8

Cooling Switching Control Value Transmit actuating value Sends the current cooling actuating value (0-1)
Cooling Continuous

Control Value

Transmit actuating value Sends the current cooling actuating value (0…100%)
 

 

 

 

9

 

Switchover between heating and cooling

 

 

 

 

heating=1, cooling=0

The function of the object depends on the “Control Function” parameter on the “Controller General” parameter page.

 

Automatic:

Reports whether the room thermostat is currently operating in heating or cooling mode.

 

Via object:

Receives the switching command for switching between heating and cooling mode.

 

 

Report heating or cooling mode

10 Reset manual operations Reset=1
11 Fan mode (manual/auto) 0=manual, 1=auto Sends fan mode to bus.
 

 

12

 

Fan level

 

send/receive fan level 0-100 %

If a manual fan mode is selected on the device, this object sends a percentage value that corresponds to the configured threshold value.
Fan level send/receive fan level

0-3

This object sents counter value from 0 to 3 as fan level.
No
 

 

13

 

 

LCD backlight

 

 

on/off backlight

Enables switching on and off of LCD backlighting via the bus.

This means, for example, that all displays can be turned off simultaneously.

 

14

 

Time

 

Receive time

Receives time (with weekday) from the bus in KNX DPT 10.001 format in order to set the internal clock.
 

 

15

 

 

Time query

 

 

Request for time

Sends automatically a time query to the time transmitter after restoration of the bus, reset and/or download.

If the time cannot be received, then sends a new time query every 5 minutes.

 

16

 

Date

 

Receive date

Receives date from the bus in KNX DPT_Date (11.001) format in order to set the internal date.
 

 

17

 

 

Date query

 

 

Request for date

Sends automatically a date query to the time transmitter after restoration of the bus, reset and/or download.

If the date cannot be received, then sends a new date query every 5 minutes.

18 Switching program lock Lock=1 Makes the time program inoperative.
 

19

Heating PWM Control Value  

Transmit actuating value

The actuating value in object 7 is emitted as a PWM signal (ON/OFF).
 

20

Cooling PWM Control Value  

Transmit actuating value

The actuating value in object 8 is emitted as a PWM signal (ON/OFF).
21 Fan level send/receive fan level 1 Activates related fan level
22 Fan level send/receive fan level 2 Activates related fan level
23 Fan level send/receive fan level 3 Activates related fan level
 

24

 

Fan unit

 

Send on/off

If fan level Off is selected this object sends OFF telegram. If fan level auto, 1, 2 or 3 is selected this object sends ON telegram.

Parameters

The General parameter page

Designation Values Description
Settings menu on device  

 

Disable

 

Enable

Selection of setting menu on device: press and hold menu key for 3 seconds.

 

Operation not possible Operation possible

Operation mode after reset  

 

Comfort

 

Standby

Night Frost/Heat Protection

Operation mode after start-up or reprogramming.
Fan Control Disable

 

Enable

Fan control option is inactive

 

Fan control is active. “Fan Control” page and “Fan Objects” appears.

Transmit operation mode and fan step not cyclically, only at change

every 2 min.

every 3 min.

every 5 min.

every 10 min.

every 15 min.

every 20 min.

every 30 min.

every 45 min.

every 60 min.

How often should the current operation mode and current fan level be sent?

 

Fan level is sent only if “Fan Mode” is not in auto mode.

The Controller General parameters page

Designation Values Description
Switching program after reset  

 

No program User defined program 1 User defined program 2 Default program 1

Default program 2

 

 

Unchange

Device has 2 switching program PRG1 and PRG2.

 

After start-up or reprogramming, the device: runs without any switching program

 

Runs with PRG1.(If adjusted keeps user defined switching program settings)

 

Runs with PRG2.(If adjusted keeps user defined switching program settings)

 

Runs with PRG1. (Reset PRG1 to default settings)

 

Runs with PRG2.(Reset PRG2 to default settings)

 

Don’t change current switching program.

*Before select this setting Date-Time should be set from bus or manually.

Language after download  

Deutsch English Español Français

Polski Русский Türkçe

Select user interface language.
Select date-time object Time object only

 

 

Time + Date object

Only time of day object is active. Time and day of week could be adjusted from bus.

 

Time of day and date objects are active. Date and time can be changed from bus.

The Temperature Measurement parameter page

Designation Values Description
Offset for temperature sensor 0.1K Steps

(-50..50)

Value from -50 to 50

 

 

Default value = 0

Positive or negative adjustment of measured temperature in 1/10 increments.

 

Examples:

a) -This thermostat sends 20.3°C.

– The room temperature of 21.0°C is measured using a calibrated thermometer.

21.0 – 20.3 = 0.7K must be added to thermostat for correction.

0.7 / 0.1 = 7 must be entered as offset.

 

b) -This thermostat sends 21.5°C.

-The room temperature of 20.1°C is measured using a calibrated thermometer.

20.1 – 21.5 = -1.4K must be added to thermostat for correction.

-1.4/ 0.1 = -14 must be entered as offset.

Transmit actual temperature at change Inactive

 

 

0.2 K

0.3 K

0.5K

0.8K

1K

1.5K

2.0K

Don’t send actual temperature value on value change event.

 

Send actual value on specified change value.

Transmit actual temperature cyclically Not cyclically, only at change

every 2 min.

every 3 min.

every 5 min.

every 10 min.

every 15 min.

every 20 min.

every 30 min.

every 45 min.

every 60 min.

Sending period of actual temperature value to bus.

The Setpoints parameter page

Designation Values Description
Heating setpoint base  

15°C, 16°C ……31°C, 32°C

Base setpoint which is assigned to heating comfort setpoint value after ETS download.
Heating reduction standby 1K, 2K ….9K,10K Reduction value to optain standby setpoint value from base setpoint.

 

Ex: Heating base setpoint is 21°C,heating reduction value is 2K than standby setpoint value is; 21-2=19°C

Heating reduction night 1K, 2K ….9K,10K Reduction value to optain night setpoint value from base setpoint.
Heating setpoint frost

protection

1°C, 2°C ….14°C,15°C Setpoint value to start frost protection
Cooling setpoint base 15°C, 16°C ……31°C, 32°C Base setpoint which is assigned to cooling comfort setpoint value after ETS download.
Cooling increase standby 1K, 2K ….9K,10K Increase value to optain standby setpoint value from base setpoint.
Cooling increase night 1K, 2K ….9K,10K Increase value to optain night setpoint value from base setpoint.
Cooling setpoint heat

protection

30°C, 31°C ….39°C,40°C Setpoint value to start heat protection
Maximum allowed manual setpoint offset Manual offset not allowed

+/- 1K

+/- 2K

.

.

+/- 6K

+/- 7K

Manually maximum shift the setpoint values by user.
Transmit current setpoint cyclically Not cyclically, only at change

every 2 min.

every 3 min.

every 5 min.

every 10 min.

every 15 min.

every 20 min.

every 30 min.

every 45 min.

every 60 min.

Sending period of current setpoint value to bus.

The Heating Control parameter page

Designation Values Description
Heating controller type 2 Step

 

Continuous

This function allows you to specify the mode of control.

You can select “2-step control” or “Continuous control”

2 Step Parameters
Heating hysteresis 0.2K Set a hysteresis value to ensure that the valve
0.4K does not constantly switch with each minor
0.6K under and overshoot when using 2-step
0.8K control of the actuator.
1.0K The hysteresis value lies around the setpoint.
1.2K For example, if the setpoint is 21 °C and the
1.4K hysteresis is 1 K, the room thermostat only
1.6K sends an “on” signal at 21.5 °C and an “off”
1.8K signal at 20.5 °C. This parameter is only
2.0K available if “2-step ” is set as the control type.
Heating invert control value no

 

yes

This parameter is used to adjust the direction of control action of the control value to “de- energised open” or “de-energised closed” valves.
Continuous Parameters
Heating PI parameter type Via type of system

 

User defined

Standard applications

 

Professional applications. Adjust PI controller parameters.

Heating type of the system PI control with:
Warm water heating Integrated time = 100 minutes Bandwidth = 1.5K
Electric heating Integrated time = 50 minutes Bandwidth = 1.5K
Floar heating Integrated time =200 minutes Bandwidth = 4.0K
Split unit Integrated time = minutes Bandwidth = k
Designation Values Description
Heating proportional band 0.5K, 1.0K, 1.5K, 2.0K, 2.5K,

3.0K,3.5K, 4.0K, 4.5K, 5.0K, 5.5K,

6.0K, 6.5K, 7.0K, 7.5K, 8.0K, 8.5K,

9.0K, 9.5K, 10K

Professional setting for adapting control response to the room.

Small values cause large changes in control variables, larger values cause finer control variable adjustment.

Heating integral reset time Value from 0 to 250 Professional setting:

See appendix: Response of the PI controller This time can be adapted to suit particular circumstances.

If the heating system is over- dimensioned and therefore too fast, shorter values should be used. Conversely, under-dimensioned heating (slow) benefits from longer integrated times.

Heating PWM cyclic time(Min.) Value from 1 to 60 An actuation cycle consists of a switch-on and a switch-off

process and forms a PWM period.

 

Example:

Actuating value= 20%, PWM time = 10 min: In an actuating cycle of 10 min, 2min switched on and 8 min switched off

(i.e. 20% on/ 80% off).

Transmit control value at change of %1

%2

%3

%4

%5

%12

%13

%14

%15

After how much % change* in the control variable is the new value to be sent. Small values increase control accuracy but also the bus load.

 

*Change since last transmission

Heating transmit control value cyclically Not cyclically, only at change

every 2 min.

every 3 min.

every 5 min.

every 10 min.

every 15 min.

every 20 min.

every 30 min.

every 45 min.

every 60 min.

How often is the current heating actuating value to be sent (regardless of changes)?

The Cooling Control parameter page

Designation Values Description
Cooling controller type 2 Step

 

Continuous

See heating description.
2 Step Parameters
Cooling hysteresis 0.2K

0.4K

0.6K

0.8K

1.0K

1.2K

1.4K

1.6K

1.8K

2.0K

See heating description.
Cooling invert control value no

yes

See heating description.
Continuous Parameters
Cooling PI parameter type Via type of system

 

User defined

See heating description.
Cooling type of the system  

 

Cool ceiling

 

 

Split unit

PI control with:

 

Integrated time = 225 minutes Bandwidth = 5K

 

Integrated time = 90 minutes Bandwidth = 4K

Cooling proportional band 0.5K, 1.0K, 1.5K, 2.0K, 2.5K,

3.0K,3.5K, 4.0K, 4.5K, 5.0K, 5.5K,

6.0K, 6.5K, 7.0K, 7.5K, 8.0K, 8.5K,

9.0K, 9.5K, 10K

See heating description.
Cooling integral reset time Value from 0 to 250 See heating description.
Cooling PWM cyclic time(Min.) Value from 1 to 60 See heating description.
Transmit control value at change of %1

%2

%3

%4

%5

%12

%13

%14

%15

See heating description.
Designation Values Description
Cooling transmit control value cyclically Not cyclically, only at change

every 2 min.

every 3 min.

every 5 min.

every 10 min.

every 15 min.

every 20 min.

every 30 min.

every 45 min.

every 60 min

.

See heating description.
System type 2 pipe system

 

 

4 pipe system

Heating control value object and cooling control value object must have same group address.

 

Heating control value object and cooling control value object must be used in different group objects.

The Fan Control parameter page

Designation Values Description
Fan level object type 1-Byte object, percentage value 0-100

 

 

1-Byte object, counting value 0-3

 

 

1-Bit objects

The selected fan stage can be sent via a

1-byte object with the continuous value from 0 to 100 %.

 

The selected fan stage can be sent via a

1-byte object as a counter value from 0 to 3.

 

When 1-bit values are selected, a 1-bit communication object is available for every fan stage.

Value for fan level 1 Percentage from %0 to %100

 

10

Available if “1-Byte object, percentage value 0-100” is selected.

 

Threshold value for the specific stage.

Value for fan level 2 Percentage from %0 to %100

 

60

Available if “1-Byte object, percentage value 0-100” is selected.

 

Threshold value for the specific stage.

Value for fan level 3 Percentage from %0 to %100

 

100

Available if “1-Byte object, percentage value 0-100” is selected.

 

Threshold value for the specific stage.

Switchover fan auto and manual mode  

 

Via object ”Fan mode auto/manual”,

auto is 0

 

Via object ”Fan mode auto/manual”,

auto is 1

Effect of fan mode object to adapt to the used fan coil actuator.

User Interface

Keys and ScreenPanasonic -V1.00- KNX- Room- hermostat- 1

Change operation modePanasonic -V1.00- KNX- Room- hermostat- 2

Change current setpoint value

  • Press MENU (two times) to select current setpoint value.
  • PressPanasonic -V1.00- KNX- Room- hermostat- 16 to set the desired setpoint value.
  • Press OK to confirm.
  • You can instantly change the setpoint value via buttonsPanasonic -V1.00- KNX- Room- hermostat- 3

Change fan level

  • Press MENU (there times) to select fan level.
  • PressPanasonic -V1.00- KNX- Room- hermostat- 16 to set the desired fan level.
  • Press OK to confirm.
  • You can easy select fan level via OK button.Panasonic -V1.00- KNX- Room- hermostat- 4

Settings Menu

  • Press MENU for 3 seconds to enter settings menu
  • PressPanasonic -V1.00- KNX- Room- hermostat- 16 to select desired line.
  • Press OK to enter.
  • Press MENU to go back.Panasonic -V1.00- KNX- Room- hermostat- 5

Summer / Winter
This line is available only if “Via object ” is selected for parameter “Switchover between heating and cooling”.Panasonic -V1.00- KNX- Room- hermostat- 6

Temperature

  • Adjust setpoint values for different operation modes and different control functions.
  • Press OK to move betweet setpoints.
  • Each value can be set separately. Maximum and minimum limits are applied automaticallyPanasonic -V1.00- KNX- Room- hermostat- 7

Switching Program

  • Select program 1 or program 2 for configuration.
  • All Days This settings will effect all day. Every day same switching program will be executed.
  • Weekdays This settings will effect only weekdays.
  • Weekend This settings will effect only Saturday and Sanday.
  • Days Every day from Monday to Sunday can be set individually.
  • Reset  Clear this program to preset values. See appendix for preset program values
  • Set user defined switching program.
  • There are 4 time periods.
  • Start and end times of all periads can be set.
  • Operation modes for those time period can be set.
  • Ex: Lets see settingd on the left side picturePanasonic -V1.00- KNX- Room- hermostat- 8

Program 1 / Program 2

  • Select active switcing program.
  • PRG 1  Program 1 is active
  • PRG 2  Program 2 is active
  • NO PRG  Swithing programsa re disabled.Panasonic -V1.00- KNX- Room- hermostat- 9

Language

  • Select user language.
  • Press to select desired language.
  • Press OK to selectPanasonic -V1.00- KNX- Room- hermostat- 12

Date, Time

  • Adjust date and time.
    • If some field are “- -“ it means date is not set by user . Please set date.
    • Date and time can be set manually from thermostat or can be received from the bus.
    • Thermostat keeps date and time up to 10 hours when power off. After this time period date and time will be reset. Please check setting after long power off periods.Panasonic -V1.00- KNX- Room- hermostat- 13

Display

  • Adjust brightness level of the display and light on/off option.
  • Light : On  Light is always on
  • Off  Light is always on
  • Key Light is on when one of key is pressed.Panasonic -V1.00- KNX- Room- hermostat- 14

Startup Behaviour

Object number Object name Description
6 Current Setpoint Depending to current operation mode sends set point value.
7 Heating Switching Control Value  

If ETS parameter “Control function” is selected as “Heating and Cooling” both heating and cooling objects will be available. Otherwise only heating or

Heating Continuous Control Value

 

Object

number

Object name Description
 

8

Cooling Switching Control Value cooling objects will be available.

 

These objects send value different from

At start up thermostat runs controller functions ;

n  If controller decided to heat the room then cooling objects are set to 0.

n  If controller decided to cool the room then heating objects are set to 0

n  If no heating or cooling is required then both heating and cooling objects are set to 0.

Cooling Continuous Control Value
19 Heating PWM Control Value
20 Cooling PWM Control Value
9 Report heating or cooling mode This object reports if thermostat is in heating mode or cooling mode. This is not related with controller outputs.
11 Fan mode (manual/auto) Sends fan auto mode data to bus.
15 Time query Sends 1 bus.
17 Date query Sends 1 bus.

REFERENCE:

DOWNLOAD MANUALS:

Panasonic V1.00 KNX Room Thermostat User Manual

panasonic logo

Panasonic V1.00 KNX Room Thermostat User Manual


Posted

in

by

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *