Oventrop 1152453 Room Thermostat

Oventrop -1152453- Room- Thermostat - PRO

General information

The original operating instructions were drafted in German. The operating instructions in other languages have been translated from German.

Validity of the operating instruction
These operating instructions are valid for the Oventrop room thermostat with fan drive 230 V.

Extent of supply
Please check your delivery for any damages caused during transit and for completeness. Items included in the delivery:

Declaration of conformity
Oventrop GmbH & Co. KG hereby declares that this product complies with the basic requirements and other relevant provisions of the EC Directives concerned. The declaration of conformity can be obtained from the manufacturer.

Used symbols

  Highlights important information and further explanations.
„ Action required
List
1.

2.

Fixed order. Steps 1 to X.
w Result of action

Correct use
Operating safety is only guaranteed if the product is used correctly. The room thermostat with fan drive 230 V is an electronically controlled operating device. The room thermostat allows for the electrical activation of fan convectors (fan coil units) for demand-oriented heating and cooling. Any other use of the product will be considered incorrect use. Claims of any kind against the manufacturer and/or its authorized representatives due to damage caused by incorrect use will not be accepted. Observance of the operating instructions is part of compliance with correct use.

Warnings
Each warning contains the following elements:

Type and source of danger!
Possible consequences if the danger occurs or the warning is ignored.

Ways to avoid the danger.
The signal words identify the severity of the danger arising from a situation.

DANGER
Indicates an imminent danger with high risk. The situation will lead to death or serious injury if not avoided.

WARNING
Indicates a possible danger with moderate risk. The situation may lead to death or serious injury if not avoided.

CAUTION
Indicates a possible danger with lower risk. The situation will lead to minor and reversible injury if not avoided.

NOTICE
Indicates a situation that may lead to damage to property if not avoided.

Safety notes
We have developed this product in accordance with current safety requirements. Please observe the following notes concerning safe use.

Danger to life due to electric current

The danger caused by inadequately qualified personnel
Any work on this product must only be carried out by qualified tradesmen. As a result of their professional training and experience as well as their knowledge of the relevant legal regulations, qualified tradesmen are able to carry out any work on the described product professionally.

User
The user must be informed how to operate the product by a qualified tradesman.

Availability of the operating instructions

Technical description

ConstructionOventrop -1152453- Room- Thermostat - 1

Functional description

Operating elements and display
The room thermostat features an LCD display with backlighting.

Operating elementsOventrop -1152453- Room- Thermostat - 2

(1) ON/OFF
(2) Fan speed
(3) Operating mode
(4) Increase
(5) Decrease

DisplayOventrop -1152453- Room- Thermostat - 3

Remark
(1) Fan speed High, medium, low, automatic
 

 

 

 

During automatic op- eration, the fan speed will be governed by the difference between the measured room temper- ature (actual value) and the desired temperature (nominal value).
(2) Temperature display Actual or nominal value
(3) Days
(4) Time
(5) Switching point 1 e.g. getting up in the morning
(6) Switching point 2 e.g. leaving the house
(7) Switching point 3 e.g. coming home
(8) Switching point 4 e.g. going to bed
(9) Sleeping mode Automatic adjustment of a manually set temperature in case of deactivated time profiles (see section 7.3 on page 12).
(10) Fan Fan mode active
(11) Cooling Cooling mode active
(12) Heating Heating mode active
(13) Time profiles

active

Timed temperature control (see section 6.3 on page 11).
(14) Manual mode Manual settings active
(15) Settings Configuration menu active
(16) Active mode Shows whether heating or cooling is active

Technical data

Temperature setting range 5°C to 35°C
Operating voltage 100 – 240VAC 50/60Hz
Switching current –   Resistive load Last 3A

–   Inductive load 2A

Power consumption < 2W
Fuse Without
Switching temperature difference ±1K
Protection IP21
Dimensions (HxWxD) 88mm x 88mm x 45mm
Colour (casing) white

Transport and storage

Temperature range 0 °C to +50 °C
Relative air humidity 5 to 95%
Particles Store dry and free from dust
Mechanical influenc– es Protected from mechanical agitation
Weather influences Do not store outdoors
Protect from direct sunlight
Chemical influences Do not store together with

aggressive fluids

Installation

Oventrop -1152453- Room- Thermostat - 4

N Neutral conductor
L Phase
(1) Fan speed 1 (LOW)
(2) Fan speed 2 (MED)
(3) Fan speed 3 (HIGH)
(4) Valve control (Open/closed)

Commissioning

Basic settings
The configuration menu allows for the adaptation of different basic settings of the room thermostat to your requirements.

Selection of the configuration menu

Configuration table

Menu option De- fault Select- tion  

Description

 

 

 

 

 

 

 

 

 

 

The room thermostat is calibrated when leaving the factory.
0 -4° C

to

+4° C

If the room thermostat cannot be positioned in such a way that the room temperature is measured without being influenced by external disturbance factors, the deviations can be compensated by modifying the settings.
The value measured at a cold outer wall would, for instance, be lower than the actual room temperature. In this case, the value can be corrected upwards.
 

 

25°C  

20°C

to 35°C

Select the maximum nominal value. During operation, this setting cannot be exceeded.
 

 

 

 

5°C

 

5°C to 20°C

Select the minimum nominal value. During operation, this setting cannot be undercut.
 

 

 

 

 

 

 

rE rd/rE Behaviour after a power failure.
–   When set to “rE”, the ON or OFF position will be preserved and the last set position will be reactivated once the power supply will have been restored.
–   When set to “rd”, the device will be in the “OFF” position once the power supply has been restored.
 

 

 

 

 

OFF ON/ OFF Constant operation of the fan.
–   When set to “OFF”, the fan will run constantly when the device is switched on.
–   When set to “ON”, the fan will only be activated in case of “Heating” or “Cooling” demand.
 

 

 

 

OFF ON/ OFF Valve protection.
–   When set to “ON”, the valve will be opened for 30 seconds once every 24 hours.
–   When set to “OFF”, the valve protection will be deactivated.
 

 

 

CO CO/CH –   “CO” means “Cooling only”
–   “CH” means “Heating and Cooling”
  If you select “CO”, the “Heating mode” will not be available.
 

 

 

 

 

 

0 0/3/7 –   “0” means that all time-controlled functions are deactivated.
–   “3” means that you can set one time profile for 5 workdays, one time profile for Saturday and another one for Sunday.
–   “7” means that you can set a separate time profile for each day of the week.

The setting of the time

The setting of time profiles

Operation

Setting of the fan speed

The setting of the mode
You can operate the room thermostat in the heating mode, cooling mode, or fan mode, irrespective of the programmed time profiles.

Heating mode and cooling mode

Sleeping mode

Maintenance

NOTICE
Damage to the surfaces due to aggressive detergents

„ Do not use hard or sharp objects, scouring agents or detergents harmful to plastics for cleaning.

„ If required, clean the surfaces with a soft cloth. In case of heavy soiling, dampen the cloth slightly with water or a mild detergent. Do not apply pressure to the

LED display.

Removal and disposal

Removal

 DANGER
Danger to life due to electric current

Danger to life due to contact with live com- ponents.

„ Completely disconnect the product from the power supply.

„ Check that no voltage is present.

„ Secure the product against switching back on.

Disposal

Waste electrical and electronic equipment (WEEE) must not be disposed of with domestic waste, but must be dropped off at a collection point for the recycling of electrical and electronic appliances.

Appendix

Day Period 1 Period 2 Period 3 Period 4
Monday 06:00

o’clock

24°C 08:00

o’clock

28°C 18:00

o’clock

24°C 22:00

o’clock

25°C
Tuesday 06:00

o’clock

24°C 08:00

o’clock

28°C 18:00

o’clock

24°C 22:00

o’clock

25°C
Wednesday 06:00

o’clock

24°C 08:00

o’clock

28°C 18:00

o’clock

24°C 22:00

o’clock

25°C
Thursday 06:00

o’clock

24°C 08:00

o’clock

28°C 18:00

o’clock

24°C 22:00

o’clock

25°C
Friday 06:00

o’clock

24°C 08:00

o’clock

28°C 18:00

o’clock

24°C 22:00

o’clock

25°C
Saturday 06:00

o’clock

24°C 08:00

o’clock

28°C 18:00

o’clock

24°C 22:00

o’clock

25°C
Sunday 06:00

o’clock

24°C 08:00

o’clock

28°C 18:00

o’clock

24°C 22:00

o’clock

25°C
Day Period 1 Period 2 Period 3 Period 4
Monday 06:00

o’clock

21°C 8:00

o’clock

16°C 18:00

o’clock

21°C 22:00

o’clock

20°C
Tuesday 06:00

o’clock

21°C 8:00

o’clock

16°C 18:00

o’clock

21°C 22:00

o’clock

20°C
Wednesday 06:00

o’clock

21°C 8:00

o’clock

16°C 18:00

o’clock

21°C 22:00

o’clock

20°C
Thursday 06:00

o’clock

21°C 8:00

o’clock

16°C 18:00

o’clock

21°C 22:00

o’clock

20°C
Friday 06:00

o’clock

21°C 8:00

o’clock

16°C 18:00

o’clock

21°C 22:00

o’clock

20°C
Saturday 06:00

o’clock

21°C 8:00

o’clock

16°C 18:00

o’clock

21°C 22:00

o’clock

20°C
Sunday 06:00

o’clock

21°C 8:00

o’clock

16°C 18:00

o’clock

21°C 22:00

o’clock

20°C

Contact

REFERENCE

DOWNLOAD MANUALS:

Oventrop 1152453 Room Thermostat Operating Instructions

Oventrop logo

Oventrop 1152453 Room Thermostat Operating Instructions

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)