  1. General information
  2. Safety-related information
  3. Technical description
  4. Transport and storage
  5. Installation
  6. Commissioning
  7. Operation
  8. Maintenance
  9. Removal and disposal

General information
The original operating instructions were drafted in German. The operating instructions in other languages were translated from German.

Validity of the operating instructions
These operating instructions are valid for the surface-mounting room thermostat (heating and cooling) item number 1152064 and 1152065.

Type plate
The type plate is on the back of the device.

Extent of supply
Please check the delivery for any damages caused during transit and for completeness. The extent of supply described in these operating instructions includes:

  • Room thermostat surface-mounting (heating and cooling)
  • Fixing material
  • Operating instructions

Copyright and protective rights
These operating instructions are copyrighted. They are exclusively designed for persons involved with the product.

Declaration of conformity
Oventrop GmbH & Co. KG hereby declares that this product complies with the basic requirements and the other relevant provisions of the EU Directives concerned. The declaration of conformity can be obtained from the manufacturer.

Used symbols

Safety-related information
The constructional and commercial regulations must be observed during installation. The current standards, regulations and guidelines are valid.

  •  2014/35/EU (Low-voltage Directive)
  •  2014/30/EU EMC

Correct use

  • Safety in operation is only guaranteed if the product is used correctly.
  • The surface-mounting room thermostat is an electronically controlled operating device.
  • The room thermostat allows for the electrical activation of fan convectors (Fan Coil Units) for demand oriented heating and cooling.
  • Any use of the product outside the above applications will be considered as non-compliant and misuse.
  • Claims of any kind against the manufacturer and/or his authorised representatives, due to damages caused by incorrect use cannot be accepted.
  • The observance of the operating instructions is part of the compliance terms.

Foreseeable misuse
Constructive measures are not sufficient to exclude misuse.

The following must therefore be avoided:

  • Installation in the open
  • Installation in wet rooms
    Connection not in accordance with the technical data

Modifications to the product
Modifications to the product are not allowed. In case of modifications to the product, the warranty will become void. The manufacturer will not accept liability for damages and malfunctions caused by modifications to the product.

Warnings

  • Each warning contains the following elements:
  • Warning symbol SIGNAL WORD
  • Type and source of danger!
  • Possible consequences if the danger occurs or the warning is ignored.
  • Possibilities of avoiding the danger.
  • The signal words define the seriousness of the danger which arises from a situation.

DANGER
Indicates an imminent danger with high risk. It will lead to death or serious injury if the situation is not avoided.

WARNING
Indicates a possible danger with moderate risk. It may lead to death or serious injury if the situation is not avoided.

CAUTION
Indicates a possible danger with low risk. It may lead to minor and reversible injury if the situation is not avoided.

NOTICE
Indicates a situation which may lead to damage to property if not avoided.

Safety notes
This product is manufactured in accordance with the latest technical status and is fail-safe. Nevertheless, there might still be a residual danger for persons and property during installation and operation. The following safety notes must be observed.

Danger in case of inadequate personnel qualification
These operating instructions and all other valid documents (e.g. accessory manuals) have to be read, understood and applied by any person working on the product. Have all work on this product carried out by qualified tradesmen.

Electrician
The following work must only be carried out by a qualified electrician:

  • Connection of the appliance to the power supply
  • Disconnection of the appliance from the power supply

Due to professional training, knowledge and experience as well as knowledge of the relevant standards and regulations, the qualified electrician is in a position to carry out any work on electrical installations and connections. He has to recognize possible dangers.

Sanitary, heating and air-conditioning specialist
The following work must only be carried out by a qualified sanitary, heating and air-conditioning specialist:

  • Installation
  • Commissioning
  • Troubleshooting
  • Maintenance
  • Removal and disposal

Due to professional training, knowledge and experience as well as knowledge of the relevant standards and regulations, the sanitary, heating and air-conditioning specialist is in a position to carry out any work on heating and potable water installations. He has to recognize possible dangers.

User
The following work may be carried out by the user:

Operation of the device
The user has to be informed by the qualified tradesman as to the operation and must have read and applied the paragraph “Advice for the user”.

Danger to life due to electric current

  • Before starting work, disconnect the device from the power supply.
  • Cover adjacent live parts.

Availability of the operating instructions

  • These operating instructions have to be read and applied by any person working on the product.
  • The operating instructions have to be kept at the installation location.
  • Hand these operating instructions and all other valid documents (e.g. accessory manuals) over to the user.

Technical description

ConstructionOventrop -1152064- Room -Thermostat- 1

  1. Base plate
  2. Operating device

Functional description
The surface-mounting room thermostat serves the individual temperature control. It is designed for fan coil units with two- and four-pipe systems.

Functional description surface-mounting room thermostat for two-pipe systems (item no. 1152064)
The surface-mounting room thermostat for two-pipe systems features:

  • a 230 V fan drive (3 speeds)
  • a 0-10 V control for heating or cooling
  • a two point control for an additional heating
  • two inputs (temperature sensor, key card)

(see also: “Illustr. 5: Connection diagram 1152064“) With the help of an external sensor, the surface-mounting room thermostat for two-pipe systems detects whether the system is in heating and cooling operation. This information is shown on the display. Switching between heating and cooling has to be carried out manually.

Functional description of surface-mounting room
thermostat for four-pipe systems (item no. 1152065) The surface-mounting room thermostat for four-pipe systems features:

  •  a 230 V fan drive (3 speeds)
  •  a 0-10 V control for heating
  •  a 0-10 V control for cooling
  •  a two-point control for additional heating
  •  two inputs (temperature sensor, key card)

(see also: “Illustr. 6: Connection diagram 1152065“) With the help of an internal sensor, the surface-mounting room thermostat for four-pipe systems compares the actual and the nominal temperature and automatically switches between heating and cooling. The current operating mode is shown on the display.

Operating elements and displayOventrop -1152064- Room -Thermostat- 2

Oventrop -1152064- Room -Thermostat- 3

Oventrop -1152064- Room -Thermostat- 4

Technical data

Oventrop -1152064- Room -Thermostat- 5

Transport and storage
The product must be transported in the original packaging. The product must only be stored under the following conditionsOventrop -1152064- Room -Thermostat- 7

Installation

General installation advice
The room thermostat should be installed at a location where a good circulation of air is guaranteed. If possible, the room thermostat should be mounted onto an inner wall at a height of 140 cm to 170 cm. Please make sure that the room thermostat is not affected by influenced by heat or cold sources (e.g. sunlight, cold outer walls). This is the only way to achieve a high measuring accuracy.

Wall attachmentOventrop -1152064- Room -Thermostat- 8 Oventrop -1152064- Room -Thermostat- 9

  • Loosen the two screws at the bottom of the room thermostat and remove the operating device from the base plate.
  • Screw the base plate horizontally onto the wall. Use the drilling jig in the base plate for this purpose.
  • Suspend the operating device into the base plate from thetop.
  • Fix the base plate and the operating device with the help ofthe two screws removed under point

Commissioning
Cable the room thermostat according to the respective connectiondiagram (see “Illustr. 5: Connection diagram 1152064“ and “Illustr.Oventrop -1152064- Room -Thermostat- 10 Oventrop -1152064- Room -Thermostat- 11

Operation

Comfort and energy saving mode

  • Switching between comfort ( ) and night mode ( ) is carried out by pressing the “Night/Comfort mode” key (see illustr. 2).
  • In comfort mode, the night mode can be reached by keeping the “Night/Comfort mode” key pressed for at least 5 seconds.
  • In night mode, the comfort mode can be reached by pressing the “Night/Comfort mode” key once.Configuration
  • Switch the room thermostat off to reach the configuration menu.
  • Keep the “Night/Comfort mode” key pressed for at least 5 seconds.
  • The first menu option is now displayed.
  • Press the “Night/Comfort mode” key again to reach the next menu option.
  • Modifications are carried out with the help of the keys or 

Configuration options

Menu option Factory settings  Control range Function
FC °C °C/°F Select the required temperature unit.
 

 

 

 

CL

 

 

 

 

0

 

 

 

 

-4 up to +4

The room thermostat is calibrated when leaving the factory.

If the room thermostat cannot be positioned in such a way that the room temperature is measured without being influenced by external disturbance factors, the deviations can be compensated by modifying the settings.

The value measured at a cold outer wall would, for instance, be lower than the actual room temperature. In this case, the value can be corrected upwards.

The displayed temperature can be increased/decreased by up to +/- 4 °C/F compared to

the measured temperature.

 

CH

 

35°C

20°C to 35°C

68°F to 95°F

 

Select the maximum nominal value. During operation, this setting cannot be exceeded.

 

CC

 

5°C

5°C to 20°C

41°F to 68°F

 

Select the minimum nominal value. During operation, this setting cannot be undercut.

 

UC

 

18°C

10°C to 18°C

50°F to 64°F

 

Select the temperature for heating operation in night mode.

 

UH

 

25°C

25°C to 30°C

77°F to 86°F

 

Select the temperature for cooling operation in night mode.

PH 1 1-10 Select the height of the proportional band (P).
LP 5 0-10 Select the height of the integral part (I).
 

 

bL

 

 

1

 

 

1/2/3

Select between 3 types of lighting:

•      1 = Lighting is switched on by pressing a switch

•      2 = Permanent lighting

•      3 = Lighting is permanently switched off

 

 

HF

 

 

h2

 

 

h1/h2/h3

Select between 3 control options:

•      h1 = 0-10 V control for heating/cooling

•      h2 = 0-10 V control for heating/cooling + two point control for an additional heating

•      h3 = Two point control for an additional heating

 

En

 

AC

 

OU/AC

Select the used temperature sensor:

•      OU = Return temperature sensor

•      AC = Room temperature sensor

 

 

rC

 

 

SC

 

 

SC/OC/OO

Select the type of activation of the night mode via the key card function:

•      SC = Night mode with a closed electrical circuit

•      OC = <Night mode with an open electrical circuit

•      OO = Night mode is terminated

 

OU

 

2

 

1/2

(only for item no. 1152065)

•      1 = The room thermostat is working in the two-pipe system

•      2 = The room thermostat is working in the four-pipe system

Change analogue output signal
You can select between the analogue output signals 0-10 V or 0-20 mA. Position the jumper as follows to change the analogue output signal:Oventrop -1152064- Room -Thermostat- 15

You can select between the analogue output signals 0-10 V or 0-20 mA. Position the jumper as follows to change the analogue output signal

Oventrop -1152064- Room -Thermostat- 16

Replacement of the fuse
The room thermostat is protected by a fuse which can be accessed after having removed of the operating device. Pull off the blue protection cap, take the fuse out of the holder and replace it.

Maintenance
The product is maintenance-free

Removal and disposal

  • If no return or disposal agreement has been made, the product has to be disposed of.
  • If possible, the components are to be recycled.
  • Components, which cannot be recycled, are to be disposed of according to the local regulations
  • Disposal with the standard waste is inadmissible.

Contact

  • Address
  • OVENTROP GmbH & Co. KG
  • Paul-Oventrop-Straße 1
  • D-59939 Olsberg
  • Germany
  • Technical service
  • Phone: +49 (0) 29 62 82-234

REFERENCE

DOWNLOAD MANUAL:

Oventrop 1152064 Room Thermostat Operating Instructions

Oventrop logo

Oventrop 1152064 Room Thermostat Operating Instructions

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *