network thermostat X7-IP Ethernet Smart Touchscreen Thermostat
- Commercial Grade Ethernet Thermostat
- Gas/Electric to 2H/2C, Heat Pump to 3H/2C
- Humidity Sensing and Control
- CO2 Sensing and Control
- Advanced Remote Sensor Bus
- Two Configurable Relays
- Full-Color Touchscreen
- 7-Day Programmable ~ 4 Events/Day
- 80 Additional Event Schedules
- Onboard Data Logging
- ACnet/IP and Modbus TCP/IP Included a Complete Stand-Alone Solution
GENERAL DESCRIPTION
The X7C-IP is an Ethernet color touchscreen thermostat with an advanced remote sensor bus, designed for new or replacement commercial and residential applications. Use the X7C for either conventional or heat pump applications (Gas/Elect 2H/2C, HP 3H/2C), along with humidification, fresh air damper, IAQ controls, and more. The X7C also includes a revolutionary CO2 sensor, with no field calibration needed for five (5) years. DirectConnect™ helps deliver a near-effortless setup of your daily schedules (4 events per day) and up to 80 Additional Events (40 Special and 40 Calendar Events). The unique scheduling structure also supports the powerful features of adjustable temporary override times and temperature ranges, occupied and unoccupied events, keypad lockout, and many more features. The X7C-IP also includes full BACnet/IP support over Ethernet, directly on the thermostat. The X7C-IP is designed to operate with our CloudConnect™ Online Management software or, for maximum security, behind your firewall using DirectConnect™ or our PCConnect™ Software. Since all HVAC functions are stored in the thermostat, the X7C will continue to operate even during network outages, allowing you to maintain your energy savings. For ultimate control over energy usage, the X7C offers a digital lockout that can permit limited temperature overrides based on your requirements. Our onboard data collection allows for historical review, sub-metering, and run-time reporting.
STANDARD FEATURES:
Energy Savings
- Efficient Equipment Restart™ randomizes equipment and starts to minimize multiple units turning on simultaneously when there are multiple NetX thermostats at the location
- Random Restart on power-up staggers restart of the HVAC system after a
power outage to minimize peak inrush current - Adaptive Recovery for Schedules allows the system to achieve the desired setpoint at the beginning of the schedule
Monitoring
- 14 Remote Sensors: up to 6 indoor, 1 humidity, 1 outdoor, and up to 6 auxiliary sensors for monitoring items such as supply air, return air, walk-in refrigerators, and freezers, etc.
- CO2 current and max level display and recording. Meets CA Energy
Commission requirements. - 2 Digital Inputs for Fault Conditions, including Condensate and Equipment Faults
- Occupancy Sensor Input
- On-board Data Logging with Sub-Metering Support Connectivity
- CloudConnect™ Internet-Based Cloud Service
- PCConnect™ Software Local Network & Port Forwarded Access
- DirectConnect™ Integrated Web Server
- Integrated NetX™ API, Supports 3rd Party Apps
- BACnet/IP and Modbus TCP/IP Embedded
- Optional Modbus RTU Interface via NT-485 Module
- 2022 Network Thermostat, Grapevine, TX
Facility Management
- 4 independent schedules per day
- 80 Additional Schedules (40 Special and 40 Calendar Events)
- Commercial Lockout with Programmable Temporary Override Time and Temp Adjustment
- Email & Text Message Alerting for 4 Recipients
- Alerts include Hi/Lo Temps for Indoor, Outdoor, Supply, Return, and Aux
- Temps, Inefficient Equipment Runs, Change Filter Notifications, and Two
- Digital Inputs: 19 Alerts in All
General
- Color Selectable Touchscreen Display, Black or White Case
- Modes: Heat, Cool, Automatic Changeover
- Integrated Humidity Sensor & Humidification and Dehumidification Control
- Fan Selector for Automatic and up to 3-speed Fan Operation*;
Programmable Recirculation Fan
- Relay 1 & Relay 2 Flexible Control
- Humidification and Dehumidification Control
- Fresh-Air Damper Control
- IAQ Equipment Control Control
- Auxiliary General Purpose Relays with Scheduling
- Integrated Weather with Current Conditions and 7-Day Forecasts
SPECIFICATIONS
- Rated Voltage: 20V to 30VAC, 24VAC nominal
- Rated A.C. / D.C. Current: 0.05 to 0.75 AC / 0.0 to 0.75 DC Amp continuous, per output, surges to 3 Amps maximum
- Temperature Control Range: Heating: 38 to 88°F (6 to 30°C) in 1° steps Cooling: 60 to 108°F (16 to 40°C) in 1° steps
- Thermostat Sensing Range: 20 to 124°F (0 to 48°C) Control Accuracy: +/-1°F @ 68°F (0.5°C @ 20°C)
- CO2 Sensing: Range: 400-2,000ppm Accuracy: 40ppm Adjustable High CO2 Indication: 500-2000ppm
- Minimum Deadband: 2°F (1°C)
- Humidity Sensing: Range: 0% – 100% RH Accuracy: ±3% From 10% – 90%
- Humidity Control Range: Humidify: 10% to 60%RH in 5%RH steps Dehumidify: 35% to 75%RH in 5%RH steps
- Dimensions: 5.1”H x 4.7”W x 1.15”D (128mm x 119mm x 29mm)
- Equipment Terminations: R – 24V switching voltage, W1 – Heat1 or Aux/Emer Heat, G – Fan, Y1-Compressor1,
- Y2 – Compressor2, O/W2 – Heat2 or Rev. Valve in Cooling, B – Rev. Valve in Heating,
- Aux Relay Terminations: K/H/D – Humidify / Dehumidify / Relay 1 Schedule / Damper / IAQ, K2 – Relay 2 Schedule / Damper / IAQ
- Power Terminations: 24V(c) – Power Return, 24V – Separate Power (24VAC/DC) requires jumper removal
- Input Terminations: LED1 (Filter Icon Selectable), LED2 (Fault Icon Selectable), CLK1 ( + ), CLK2 ( – ) (Occupancy)
- Remote Sensor Terminations: RS+V – Power, RS2 – Return, RS1 – Data
- Ethernet: 10/100Mbps, 802.3, Auto-Negotiation, Auto-MDIX
- Accessory Port: SIM port for NetX CO2/VOC Sensor, NetX DECT/ULE Wireless Sensor Network Host Card
- Protocols: http, native NetX API, BACnet/IP and Modbus TCP/IP over Ethernet
WIRING DIAGRAMS
TERMINAL FUNCTIONS
- LED1 24Vac Input #1 for Filter or other Alert
- LED2 24Vac Input #2 for Condensate, Fault or Other Alert
- CLK1 For use with External Occupancy Sensor ( + )
- CLK2 For use with External Occupancy Sensor ( – )
- RS2 Remote Sensor Bus (Power Return)
- RS1 Remote Sensor Bus (Data)
- RS+V Remote Sensor Bus (Power)
- X2 N/A
- X1 N/A
- K2 Programmable Auxiliary Relay 2
- K/H/D Humidification or Dehumidification or Aux. Relay 1
- Y2 Energizes the compressor for second-stage cooling, or for
- heat pumps, either second-stage heating or cooling
- W1 Energizes heater for first-stage heating, or for heat pumps, aux/emer heat
- Y1 Energizes compressor for first-stage cooling, or for heat
- pumps, either first-stage heating or cooling
- G Energizes fan circuit with a call for heating or cooling
- R Independent Switching Voltage from HVAC equip
- 24V 24Vac
- 24V(c) 24Vac Common
- O/W2 Energizes heater for second-stage heating, or for heat pumps, energizes the reversing valve in cooling mode
- B Energizes the reversing valve in heating mode
REFERENCE:
DOWNLOAD MANUALS:
netwok thermostat X7-IP Ethernet Smart Touchscreen Thermostat Product Specification Guide
network thermostat X7-IP Ethernet Smart Touchscreen Thermostat Product Specification Guide
Leave a Reply