Luxpro-LOGO

LUXPRO P2000F Non-Programmable Thermostat 

LUXPRO-P2000F-Non-Programmable-Thermostat

Product Highlights

All that’s needed for radiant floor control

Product Features

Installation

Compatible With 

Not Compatible With 

SPECIFICATIONS LUXPRO-P2000F-Non-Programmable-Thermostat-fig-1

Dimensions 3.50″ (89mm) wide x 3.875″ (99mm) tall x 1.00″ (25mm) deep
Heat/Cool Terminals RH, C (output, if needed), W (output)
Electrical Ratings 2 AMPS @ 24 VAC, 60 HZ. System power only
Temperature Control Range ■    Room temp control 40°F to 86°F (5°C to 30°C)
■    Floor/slab temp control 40°F to 99°F (5°C to 45°C) Accuracy ±1°F ( ±1°C).
Environmental Limits ■    Moisture and Dust: meets IP20
■    Operating Humidity: 20% to 85% (non-condensing)
■    Operating temperature: +32°F to 104°F (+0°C to 40°C)
■    Storage temperature: +14°F to +122°F (-10°C to +50°C)
■    Electrical Immunity: meets relevant CE specifications
Compatible With ■    Radiant underfloor heating systems (up to 2 AMPS @ 24 VAC)
■    2-wire hydronic thermal actuators (up to 2 AMPS @ 24 VAC)
Not Compatible With ■    120V/240V line voltage systems (without transformer)
■    Conventional forced air heating/cooling systems
■    3-wire hydronic zone valves■    Systems without 24 VAC common wire present
Packaging ■    Master Carton: 5

■    UPC: 0 21079 13920 0

4747 South Broad Street I Building 101 – Suite 330 I Philadelphia, PA 19112 I
P: 856.234.7905 I
F: 856.234.7825
LuxProProducts.com

Reference

Download manual: 

LUXPRO P2000F Non-Programmable Thermostat Product Specifications

Other manuals:

LUXPRO P2000F Non-Programmable Thermostat Installation Manual

Luxpro-LOGO

LUXPRO P2000F Non-Programmable Thermostat Product Specifications

Leave a Reply

Your email address will not be published. Required fields are marked *

Your post must include a link to this post.

How does this work?
Write a response on your own website and include a link to this post. Then submit your response’s URL here. Your response may appear here after moderation. To update or remove it, edit or delete your original post and submit the same URL again. Learn more about Webmentions.