SPECIFICATIONS LUXPRO-P2000F-Non-Programmable-Thermostat-fig-1

Dimensions 3.50″ (89mm) wide x 3.875″ (99mm) tall x 1.00″ (25mm) deep
Heat/Cool Terminals RH, C (output, if needed), W (output)
Electrical Ratings 2 AMPS @ 24 VAC, 60 HZ. System power only
Temperature Control Range ■    Room temp control 40°F to 86°F (5°C to 30°C)
■    Floor/slab temp control 40°F to 99°F (5°C to 45°C) Accuracy ±1°F ( ±1°C).
Environmental Limits ■    Moisture and Dust: meets IP20
■    Operating Humidity: 20% to 85% (non-condensing)
■    Operating temperature: +32°F to 104°F (+0°C to 40°C)
■    Storage temperature: +14°F to +122°F (-10°C to +50°C)
■    Electrical Immunity: meets relevant CE specifications
Compatible With ■    Radiant underfloor heating systems (up to 2 AMPS @ 24 VAC)
■    2-wire hydronic thermal actuators (up to 2 AMPS @ 24 VAC)
Not Compatible With ■    120V/240V line voltage systems (without transformer)
■    Conventional forced air heating/cooling systems
■    3-wire hydronic zone valves■    Systems without 24 VAC common wire present
Packaging ■    Master Carton: 5

■    UPC: 0 21079 13920 0

4747 South Broad Street I Building 101 – Suite 330 I Philadelphia, PA 19112 I
P: 856.234.7905 I
F: 856.234.7825
LuxProProducts.com

Reference

Download manual: 

LUXPRO P2000F Non-Programmable Thermostat Product Specifications

Other manuals:

LUXPRO P2000F Non-Programmable Thermostat Installation Manual

Luxpro-LOGO

LUXPRO P2000F Non-Programmable Thermostat Product Specifications

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)