INTRODUCTION

HTW-61-EW001-B is a Noise-Free room climate controller application for water installations with fan coils. It is designed as a stand-alone device to operate the fan coil
unit of a zone and includes a set of functions for zone occupancy and window position-based climate control. A high level of comfort and appropriate climate control to ensure maximum energy savings are thus provided.

The device is a compact unit that includes a large backlit display screen, a built-in temperature sensor, pushbuttons on the front panel, and inputs and outputs built on a split remote relay module for room control.
This split thermostat application includes two parts:Hotowell-HTW-61-EW001-B-Room-Controller-THERMOSTAT-Instruction-Data-Sheet-FIG-3

  1. Manual operation display part: HTW-61-EW001-B
  2. Remote relay module part: HTW-61-EW001-RM

These two parts are communicated via 4-wire connections:

  • GND
  • 12V
  • TXD
  • RXD

It provides a totally Noise-Free application due to its remoted relay module.

General features

  • Wide, blue backlit LCD, 65 × 59 (mm)
  • Front panel built in pushbuttons: Mode/+T/-T/Fan speed/On-Off
  • Front panel built in temperature sensor
  • Two models available: 4 or 5 pushbuttons (HEAT/COOL)
  • Configurable for 2 pipe / 4 pipe systems
  • Selectable temperature units (ºC/ºF)
  • Configurable max/min/economy temperature setpoints
  • Keycard switch contact occupancy monitoring for energy saving
  • Configurable anti-humidity frequency:10/30,5/30,5/60
  • Configurable keycard switch input: keycard switch/lighting
  • Configurable fan coil: 3 speeds / 1 speed
  • Speed 1 configurable as blocked or unblocked on zero demand
  • Economy mode Heat/Cool temperature setpoint Heat/Cool dead band
  • Delayed switching to Economy when card is removed
  • Automatic device startup after loss of power
  • Configurable NO/NC valve outputs
  • Noise-Free application

Device Inputs and Outputs

Inputs:

  1. Digital, keycard switch contact / lighting auxiliary contact 1 Digital, window contact
  2. Analog, ambient temperature external sensor
  3. Temperature sensor, built in on device front panel

Outputs:

  • 3 Relays, fan coil speed (I,II,III)
  • 1 Relay, chilled water valve
  • 1 Auxiliary relay (hot water valve on 4 pipe systems / lighting on 2 pipe systems)
  • 1 Auxiliary relay for lamp

Product description

The split controller Noise-Free application is designed for room climate control at hotels, offices and homes with water and fan coil installations. The device includes all the necessary inputs and outputs to operate a 2 pipe or a 4 pipe system; control over one or two on/off valves and a 3 speed fan coil is provided to maintain room or zone temperature to user requirements.

The device includes a built in temperature sensor on its front panel for room temperature measurement, and features an advanced control algorithm for fan coil speed and valve position control. Two digital inputs are also provided, one to detect zone occupancy from a keycard switch contact-used in hotels to indicate that the room is occupiedand another one to connect to a window contact-used to temporarily disconnect operation when the window is open. The keycard switch input may alternatively be configured to control zone lighting on 2 pipe systems. In this case, one of the valve outputs converts to lighting control output.

The device includes a simple configuration menu that allows configuring up to 28 parameters. The unit can thus be adapted to the requirements of each installation.
More importantly, the device is designed with a remote relay module, in order to provide a totally Noise-Free application.

Configuration Parameters

Special Note

  1. During power-off status, push and hold “Fan” and “+” buttons together for 6s to entry the configuration parameter setting;
  2. There are two lighting output.
    • lighting 1:when P10 configured as 2P,the Aux is working as a courtesy lighting;
    • Lighting 2: Lamp output(terminals 14-15) associated with window contact input.
Special Note
  1. During power-off status, push and hold “Fan” and “+” buttons together for 6s to entry the configuration parameter setting;
  2. There are two lighting output.

lighting 1: when P10 configured as 2P,the Aux is working as a courtesy lighting;
Lighting 2: Lamp output(terminals 14-15) associated with window contact input.

Parameter Description Possible values Default values Setting display
1 Displaying temperature in ℃ or ℉ ℃ or ℉ C/F
2 Fan-coil speed(1 speed,3speeds) 1/3 3 1/3
3 1 fan-coilspeed active when there’s no demand in cooling mode NO/YES YES NO/YES
4 1 fan-coilspeed active when there’s no demand in heating mode NO/YES NO NO/YES
 

5

OFF or ECO or Anti-humidity mode when key-card is removed

-Note 1

 

OFF/ECO/ANTI

 

ECO

 

OFF/ECO/ANTI

6 Time to change to OFF or ECO or Anti-humidity mode 1-250s 20s 1-250S
 

7

Change mode COOLING/HEATING as per water temperature entry

-Note 2 & Note 3

 

NO/YES

 

NO

 

NO/YES

 

8

Change mode COOLING/HEATING as per set-point/temperature difference  

NO/YES

 

NO

 

NO/YES

 

9

Displaying value(set-point/room temperature/set-point&temp.)

-Note 4

 

SET/TEP/SET&TEP

 

SET

 

SET/TEP/ALL

10 Installation type(2piles/4pipes) 2P/4P 2P 2P/4P
11 Key-card input system working mode(Card/Auxiliary lighting) CA/LI CA CA/LI
 

12

Contact type for key-card input setted up as auxiliary lighting(Push/Switch)  

PSH/STH

 

PSH

 

PSH/STH

13 Dead-band temperature between cool/heat +1℃~+6.0℃ 3℃ +1℃~+6.0℃
14 Offset temperature -3.0℃~+3.0℃ 0.0℃ -3.0℃~+3.0℃
15 Configurable set-point maximum temperature +22.0℃~+32.0℃ 32.0℃ +22.0℃~+32.0℃
16 Configurable set-point minimum temperature +15.0℃~+21.0℃ 15.0℃ +15.0℃~+21.0℃
17 Set-point temperature in cool and occupied mode +15.0℃~+32.0℃ 23.0℃ +15.0℃~+32.0℃
18 Set-point temperature in cool and ECO mode +15.0℃~+32.0℃ 26.0℃ +15.0℃~+32.0℃
19 Set-point temperature in heat and occupied mode +15.0℃~+32.0℃ 21.0℃ +15.0℃~+32.0℃
20 Set-point temperature in heat and ECO mode +15.0℃~+32.0℃ 16.0℃ +15.0℃~+32.0℃
21 Equipment start-up after reset(OFF/ON) -Note 5 OFF/ON ON OFF/ON
22 Equipment start-up internal mode(COOL/HEAT) CO/HE CO CO/HE
23 Closed electro-valves output control status NO/NC NO NO/NC
24 Active lighting time(aux) from key-card detection -Note 6 0-250s 20s 0-250S
25 Default value for all parameters NO/YES NO NO/YES
26 Modbus address setting(ID) 1~255 1 1~255
 

 

 

 

27

Window contact input working algorithm :

1).when window contact open,valve outputs stop,fan speed stops 2).when window contact open,valve outputs stop,but fan speed switches to slow;

3).this contact is associated with LAMP output: a.when window contact closed,Lamp on ; b.when window contact open,Lamp off

 

 

 

 

1/2/3

 

 

 

 

1

 

 

 

 

1/2/3

28 Delay time to switch after window contact open 1-250s 20s 1-250s
 

 

29

The frequence of Anti-humidity: 1).10mins every 30mins;

2). 5mins every 30mins; 3). 5mins every 60 mins

 

 

1/2/3

 

 

2

 

 

1/2/3

 

 

30

Time delay for Auto-Speed switch: 1). 1—1 min delay;

2).  3—3 min delay;

3).  5—5 min delay

 

 

1/3/5

 

 

1

 

 

1/3/5

Notes
 

 

1)

Anti-humidity algorithm:when the key card pulled out,the device automatically switch to work at set-point 24 degrees for a period of time every confirgured mintues depending on the configuration of P29
2) Priority parameter on P8
 

 

3)

The internal/external temperature sensor is selected by placing jumper J1 on position IN or OUT; The IN & OUT dual sensor mode could be configured by removing the jumper.
 

4)

If P9 is confirgured as ALL, defaulting display SET, and display TEP by pushing and holding “+”&”-” buttons together, 6s later return to SET display.
 

5)

When this parameter is programmed as ON, if the parameter number 5 is setted up as ECO and the room is unoccupied, the equipment will start in ECO mode.
 

 

6)

If it shows 0 seconds, the auxiliary output will remain active while the key-card input is active and it will be disconnected when the key-card input is switched off and exceed the settedtime in parameter number 6.

MODBUS RTU
Baud rate: 4800 No Parity bit, 8 Data bit 1 Stop bit:

Basic description

No. Parameter Protocol provision
1 Operating mode RS-485 connection, master-slave
2 Physical interface A(+),B(-) 2-wire system
3 Baud rate 4800
4 Byte format No Parity bit, 8 Data bit,1 Stop bit
5 Transmission mode RTU format
6 Thermostat address 1-255
7 Command code 03-read data, 06/10-set data
8 CRC check code CRC-16
9 CRC verification mode CRC-16

Command frame
Command code 03: Read data (“x” can only be “0x01”-read single data or “0x27”-read all data
Command frame given by upper computer

01 03 9C 40 00 x CRC_L CRC_H
Device ID Command code Starting address Register address number CRC check

Response frame given by thermostat

01 03 x*2 Data1_H Data1_L DataX_H DataX_L CRC_L CRC_H
Device ID Command

code

Data byte

length

Data 1 Data x CRC Check

Command code 06: Write single data Command frame given by upper computer

01 06 9C 40 Data_H Data_L CRC_L CRC_H
Device ID Command code Starting address Register address CRC Check

Command code 10: Write all data Total 35 items can be written Command frame given by upper computer

01 10 9C 40 00 23 46 Data1_H Data1_L
Device ID Command code Starting address Register address number byte length Data 1
Data2_H Data2_L …… Data35_H Data35_L CRC_L CRC_H
Data 2 …… Data 35 CRC Check

Command frame given by thermostat

01 10 9C 40 00 23 CRC_L CRC_H
Device ID Command code Starting address Register address number CRC Check

Register address

Address Meaning Read/Write Value
40000 On/off control R/W On=0x55    off=0xaa
40001 Keyboard lock R/W Lock=0x55    unlock=0xaa
40002 Working model R/W Cool=0x11 heat=0x22
40003 Fan speed R/W Auto=0x00 low=0x01 middle=0x02 high=0x03
40004 Rely output status R BIT=1,relay has output;BIT=0,relay has no output BIT0:low fan

BIT1:mid fan BIT2:high fan BIT3:valve status

BIT4:AUX status(when 4pipes)

40005 Room temp R Communicate data=room temp*10
40006 Water temp R Communicate data=water temp*10
40007 Seting temp R/W Communicate data=seting temp*10
40008 Room card status R No card=0x00    with card=0x01
40009 Aux control R/W Aux on=0x55    aux off=0xaa
40010 Lamp control R/W Lamp on=0x55    lamp off=0xaa
40011 Parameter1 R/W C=0x00    F=0x01
40012 Parameter2 R/W 1fan=0x00    3fan=0x01
40013 Parameter3 R/W No=0x00    yes=0x01
40014 Parameter4 R/W No=0x00    yes=0x01
40015 Parameter5 R/W eco=0x01    anti=0x02   off=0x03
40016 Parameter6 R/W Communicate data= Parameter6 time
40017 Parameter7 R/W No=0x00    yes=0x01
40018 Parameter8 R/W No=0x00    yes=0x01
40019 Parameter9 R/W Set=0x01    temp=0x02    all=0x03
40020 Parameter10 R/W 2 P=0x00    4P=0x01
40021 Parameter11 R/W CA=0x00    LI=0x01
40022 Parameter12 R/W PSH=0x00    STH=0x01
40023 Parameter13 R/W Communicate data= Parameter13*10
40024 Parameter14 R/W Communicate data= Parameter14*10
40025 Parameter15 R/W Communicate data= Parameter15*10
40026 Parameter16 R/W Communicate data= Parameter16*10
40027 Parameter17 R/W Communicate data= Parameter17*10
40028 Parameter18 R/W Communicate data= Parameter18*10
40029 Parameter19 R/W Communicate data= Parameter19*10
40030 Parameter20 R/W Communicate data= Parameter20*10
40031 Parameter21 R/W Off=0x00   on=0x01
40032 Parameter22 R/W CO=0x00    HE=0x01
40033 Parameter23 R/W NO=0x00    NC=0x01
40034 Parameter24 R/W Communicate data= Parameter24 time
40035 Parameter25 R/W Reset=0x01
40036 Parameter27 R/W 1=0x01    2=0x02    3=0x03
40037 Parameter28 R/W Communicate data= Parameter28 time
40038 Parameter29 R/W 1=0x01    2=0x02    3=0x03

REFERENCE:

DOWNLOAD MANUALS:

Hotowell HTW-61-EW001-B Room Controller THERMOSTAT PRODUCT SPECIFICATION SHEET

 

HOTOWELL LOGO

Hotowell HTW-61-EW001-B Room Controller THERMOSTAT PRODUCT SPECIFICATION SHEET

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post’s permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post’s URL again. (Find out more about Webmentions.)