HONEYWELL-TH5320C-Non-Programmable-Digital-Thermostat-featured

HONEYWELL TH5320C Non-Programmable Digital Thermostat Installation Guide

Honeywell logo

HONEYWELL TH5320C Non-Programmable Digital Thermostat 

HONEYWELL-TH5320C-Non-Programmable-Digital-Thermostat-product

To be used with up to 3 Heat 2 Cool conventional and heat pump systems with W8835 Zone Panel or W8635 or THM5241 Equipment Interface Modules (EIM).

Use With

  • W8835 Zone Panel—up to 3H/2C conventional or heat pump system
  • W8635A EIM—up to 2H/2C conventional system
  • W8635B EIM—up to 2H/1C heat pump system
  • THM5421 EIM—up to 3H/2C conventional or heat pump

System Types

  • Gas, oil, or electric heat with air conditioning
  • Warm air, hot water, high-efficiency furnaces, heat pumps, steam, gravity
  • Heat only — two-wire systems, three-wire zone valves (Series 20), and normally open zone valves
  • Heat only with a fan
  • Cool only

Must be installed by a trained, experienced technician
Read these instructions carefully. Failure to follow these instructions damages the product or causes a hazardous condition.
Need Help?
For assistance with this product please visit http://yourhome.honeywell.com
or call Honeywell Customer Care toll-free at 1-800-468-1502 U.S. Registered Trademark. Patents pending. Copyright © 2008 Honeywell International Inc. All rights reserved

Wallplate installation

HONEYWELL-TH5320C-Non-Programmable-Digital-Thermostat-fig-1

  1. Separate wallplate from thermostat.
  2. Mount wallplate as shown below

CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.

MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal

Wiring

Terminal designations
Thermostat Terminals (connect to network zone panel or EIM)

  1. Data communication
  2. Power
  3. Common

This thermostat does not use batteries. Installing batteries could lead to corrosion of the batteries and damage the thermostat

Thermostat mounting
Once the wallplate is securely mounted on the wall:

  1. Push excess wire back into the wall opening.
  2.  Plug the wall opening with non-flammable insulation.
  3. Align the 4 tabs on the wallplate with the slots on the back of the thermostat.
  4. Gently push the thermostat onto the wallplate; the thermostat will snap into place.

Installer setup

HONEYWELL-TH5320C-Non-Programmable-Digital-Thermostat-fig-2
Follow the procedure below to configure the thermostat to match the installed heating/cooling system, and customize feature operation as desired

Setup function Settings & options (factory default in bold)

Setup function

0 Zone Instance

Settings & options (factory default in bold)

0      Not Zoned

1–9 Zoned (default setting 2)

1 System type 0      1 heat/1 cool conventional

1      1 heat/1 cool heat pump (no aux. heat)

2      Heat only — 2-wire systems, 3-wire zone valves (Series 20), and nor- mally open zone valves

3      Heat only with fan

4      Cool only

5      2 heat/1 cool heat pump (with aux. heat)

6      2 heat/2 cool conventional

7      2 heat/1 cool conventional

8      1 heat/2 cool conventional

9      2 heat/2 cool heat pump (no aux. heat)

10    3 heat/2 cool heat pump (with aux. heat) A      Auto Discover

2 Changeover valve (O/B terminal) 0      Changeover valve (O/B terminal energized in cooling)

1      Changeover valve (O/B terminal energized in heating)

3 Fan control (heating) 0      Gas or oil furnace — equipment controls fan in heating

1      Electric furnace — thermostat controls fan in heating

5 Stage  1  heat  cycle rate (CPH: cycles/hour) 5      For gas or oil furnaces of less than 90% efficiency

1      For steam or gravity systems

3      For hot water systems & furnaces of over 90% efficiency

9      For electric furnaces

6 Second Stage Heat Cycle Rate 5      Standard Gas or Oil Furnace

1      Steam or Gravity

3      90% + Efficient Furnace or Hot Water

9      Electric Furnace

[Other options: 2, 4, 6, 7, 8, 10, 11, 12 for Special Applications] A      Auto Discover

7 Third Stage Heat Cycle Rate 5      Standard Gas or Oil Furnace

1      Steam or Gravity

3      90% + Efficient Furnace or Hot Water

9      Electric Furnace

[Other options: 2, 4, 6, 7, 8, 10, 11, 12 for Special Applications] A      Auto Discover

8 Emergency Heat Cycle Rate 9      Electric Furnace

[Other options: 1–8, 10, 11, 12 for Special Applications] A      Auto Discover

9 Stage 1 compressor cycle rate (CPH) 3      Recommended for most compressors

[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]

10 Second Stage Compressor Cycle Rate 3      Compressor Cycle Rate

[Other options: 1, 2, 4, 5, 6 for Special Applications] A      Auto Discover

12 Manual/Auto changeover 0      Manual  changeover (Heat/Cool/Off)

1      Auto changeover (Heat/Cool/Auto/Off)

2      Auto changeover only (Auto)

14 Temperature display 0      Fahrenheit

1      Celsius

15 Compressor protection 5      Five-minute compressor off time

[Other options: 0, 1, 2, 3 or 4-minute off time]

19 Service Indicator 00–199 Diagnostic Codes

See Special function section on page 5.

23 Backlight Mode 0          Disabled

1          Enabled

26 Aux Control 0      Comfort

1      Economy

See Special function section on page 5.

27 Heat temperature range stops 90 Max. heat temperature setting is 90 °F (32 °C)

[Other options: 40 °F to 89 °F (4.5 °C to 31.5 °C)]

28 Cool temperature range stops 50 Min. cool temperature setting is 50 °F (10 °C)

[Other options: 51 °F to 99 °F (10.5 °C to 37 °C)]

Installer system test

HONEYWELL-TH5320C-Non-Programmable-Digital-Thermostat-fig-5

10 Heating system 0       Heat and fan turn off.

1       Stage 1 heat turns on. Fan turns on if Setup Function 1 is set to 1, 5, 9 or 10 OR Setup Function 3 is set to 1.

2       Stage 2 heat turns  on.

3       Stage 3 heat turns  on.

20 Emergency heating system 0       Heat and fan turn off

1       Heat and fan turn on

30 Cooling system 0       Compressor and fan turn off

1       Compressor and fan turn on

2       Stage 2 compressor turns on

40 Fan system 0       Fan turns off

1       Fan turns on

System test

70 Thermostat information (for reference only)

System status

71     Software Revision Number (major  revisions)

72     Software Revision Number (minor  revisions)

73     Configuration Identification Number (major)

74     Configuration Identification Number (minor)

75     Production configuration date code (week)

76     Production configuration date code (year)

CAUTION: Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly

Special function

Auxiliary heat control (Setup Function 26):

  • Comfort Setting: The thermostat will prioritize comfort over economy depending on heat pump performance, load conditions and whether the thermostat is calling for the heat pump. Raising the temperature just a few degrees will often activate the auxiliary heat.
  • Economy Setting: The thermostat will attempt to reach the temperature setting without activating the auxiliary heat. The thermostat will wait to activate the auxiliary heat depending on heat pump performance, load conditions and how many degrees the temperature setting is changed.

Diagnostic Codes (Setup Function 19):
When Error Codes are present the home screen of the thermostat will display “SERVICE NEEDED” and scroll through all active error codes. Setup Function 19 will display a list of the 10 most recent error codes, both active and inactive. The number on the right of the thermostat will show the number of active and inactive error codes saved in the thermostat. To view the error codes press the up arrow. To clear the list, press and hold both the up and down arrow keys. Active errors can not be cleared; the source of the error must be resolved prior to clearing from the list.

Accessories & replacement parts

Please contact your distributor to order replacement parts.

  • Part Description Part Number
  • Small cover plate assembly* 50001137-001
  • Medium cover plate assembly* 50002883-001
  • 12 packs of small cover plates* 50007297-001
  • 12 packs of medium cover plates* 50007298-001
  • EnviraZONE Zone panel W8835A1004
  • Equipment Interface Module for 2H/2C conventional systems W8635A1006
  • Equipment Interface Module for 2H/2C heat pump systems W8635B1004
  • Telephone Access Module W8735B1003
  • 2-Channel Telephone Access Module W8735D1009
  • 4-Channel Telephone Access Module W8735D1017

Specifications

Temperature Ranges
Heat: 40° to 90°F (4.5° to 32°C)
Cool: 50° to 99°F (10° to 37°C)

Operating Ambient Temperature
32° to 120°F (0° to 48.9°C)

Shipping Temperature
-20° to 120°F (-28.9° to 48.9°C)

Operating Relative Humidity
5% to 90% (non-condensing)

Physical Dimensions
TH5220D
3-9/16” H x 5-13/16” W x 1-1/2” D
91 mm H x 147 mm W x 38 mm D

TH5110D
3-7/16” H x 4-1/2” W x 1-5/16” D
86 mm H x 114 mm W x 33 mm D

Reference

Download Manual:

HONEYWELL TH5320C Non-Programmable Digital Thermostat Installation Guide