Honeywell TH1000 Programmable Thermostat
This manual covers the following models:
(Remove the thermostat from the wallplate and turn it over to find the model number.)
System Types
- Central heating (gas, oil, electric or highefficiency furnace)
- Central heating (see above) with air conditioning
- Hot water system (steam or gravity) with or without pump
- Central air conditioners
- 750 mV heating systems
- 1-Heat/1-Cool heat pumps
- 2-Heat/1-Cool heat pumps
Must be installed by a trained, experienced technician
Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.
Need Help?
For assistance with this product please visit http://yourhome.honeywell.com or call Honeywell Customer Care toll-free at 1-800-468-1502.
Wallplate installation
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
- Loosen the locking screw at the bottom of the thermostat. Note that the screw is captive and cannot be removed from the wallplate.
- Separate the thermostat from the wallplate as per Figure 1.
- Position the wallplate against the wall and mark hole positions with a pencil.
NOTE: Levelling is for aesthetics only and will not affect the performance of the thermostat. - Drill holes at the marked positions and insert supplied wall anchors.
- Pass the wires through the large opening located at the bottom center of the wallplate as per Figure 2.
- Secure the wallplate to the wall with supplied mounting screws as per Figure 3.
- Connect the wires to the terminals.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal
Wiring
- Power supply. Provide disconnect means and overload protection as required.
- Set the O/B jumper according to the type of reversing valve (see page 4).
- Use a piece of wire (not supplied) to connect W and Y terminals to each other.
- Optional 24 VAC common connection. If this connection is not made, use batteries to power the thermostat.
- This connection is not required for systems that provide heating only
- This connection is not required for systems that provide cooling only
- This connection is not required for systems that do have an air-recirculating fan.
Gas, oil, or electric heating and/or air conditioning (1H / 1C / 1H1C)
Heat pump without auxiliary heating (1H1C)
Heat pump with auxiliary heating (2H1C)
Reversing valve setting
NOTE: This setting is necessary only if the thermostat is connected to a heat pump. The jumper is located on the back of the thermostat faceplate. Set it according to the type of reversing (changeover) valve used by the heat pump.
- O (factory setting): The reversing valve is energized when the System switch is set to Cool (cooling mode).
- B: The reversing valve is energized when the System switch is set to Heat (heating mode).
- Incorrect jumper setting: The heat pump operation will be reversed; i.e., it will cool in Heat mode and will heat in Cool mode.
Fan operation setting
NOTE: This setting is not applicable if a fan is not connected to the G terminal. The jumper is located on the back of the thermostat faceplate. It determines how the fan operates when placed in Automatic mode.
- HG (factory setting): Leave the jumper in this position for gas or oil heating systems. In In this position, the heating system controls the fan operation and activates the fan only
when the plenum air is sufficiently warm. - HE: Place the jumper to this position for the heat pump or electric heating systems. In this position, the thermostat activates the fan only when there is a call for heat.
- Incorrect jumper setting: An incorrect setting is noticeable in a gas or oil heating system.
- When heating starts, you will initially feel cold air coming out of the vents as the fan is running before the furnace has enough time to heat up the air.
Battery installation
If 24 VAC common wire is connected to the C terminal, batteries are optional and serve to provide backup power. If 24 VAC common wire is not connected to the C terminal, the batteries
are necessary to power the thermostat. Install 2 AAA batteries on the back of the thermostat faceplate as shown.
Thermostat mounting
- Align the two brackets on the top of the thermostat with the corresponding slots on the top of the wall plate.
- Push the faceplate against the wallplate.
- Tighten the screw at the bottom of the thermostat.
Installer setup
Follow the procedure below to personalize and configure the thermostat according to the heating/ cooling system.
- Press and for three seconds. The display
will appear as shown on the right. - Press or to change the option.
- Press and for three seconds to advance to
the next function. - Press Run to exit the menu and save any
changes.
NOTE: You will also exit the menu if you press and for three seconds when the last function is displayed.Function Default setting Options 1 Temperature display format 0 0: Fahrenheit 1: Celsius
2 Time display format1 0 0: 12-hour display 1: 24-hour display
3
Heating cycles per hour
5
2 to 6 cycles per hour • 2: 30 min (steam, gravity)
• 3: 20 min (hot water, 90%+ high-efficiency furnace)
• 4: 15 min (gas or oil)
• 5: 12 min (gas or oil)
• 6: 10 min (electric)
4 Cooling cycles per hour 3 2 to 6 cycles per hour 5 Compressor protection2 0 0: enabled (for systems without a compressor)) 1: disabled (for systems equipped with a compressor)
6 Adaptive Intelligent Recovery3 1 0: Off 1: On
Applicable to programmable models (TH2110D & TH2210D) only. Damage can occur if the compressor is restarted too soon after shutdown. This feature forces the compressor to wait 5 minutes before restarting. During the wait time, the message Cool On or Heat On flashes on the screen. When the safe wait time has elapsed, the message stops flashing and the compressor turns on. Applicable to programmable models (TH2110D & TH2210D) only. Adaptive Intelligent Recovery™ allows the thermostat to “learn” how long your furnace or air conditioner takes to reach the set temperature. Simply program the desired times and desired temperatures into the schedule. The thermostat will determine when to activate heating or cooling so that the desired temperature is attained at the desired time.
Specifications
Temperature Ranges
Heat: 40 °F to 90 °F (4.5 °C to 32 °C)
Cool: 50 °F to 99 °F (10 °C to 37 °C)
Operating Ambient Temperature
32 °F to 122 °F (0 °C to 50 °C)
Shipping Temperature
-40 °F to 130 °F (-40 °C to 55 °C)
Operating Relative Humidity
5% to 90% (non-condensing)
Physical Dimension
4.7” H x 2.9” W x 1.1” D (120 mm H x 74 mm W x 28 mm D)
Power Supply
24 VAC or 2 AAA batteries
Maximum Load
1 A @ 24 VAC per output
Automation and Control Systems
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
http://yourhome.honeywell.com
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario M1V 4Z9
Reference
Download Manual:
Honeywell TH1000 Programmable Thermostat Installation Manual
Honeywell TH1000 Programmable Thermostat Installation Manual
Leave a Reply