Honeywell T874A Zone Thermostat
Application
These T874A,D Zone Thermostats and Q674B,D,E Subbases provide 24 to 30 Vac temperature control in Honeywell Trol-A-Temp heating/cooling zone systems. See Table 1 for thermostat/subbase and system compatibil-ity; see Table 2 for thermostat specifications. For complete Honeywell Trol-A-Temp System specification and appli-cation information, refer to the system specification in-cluded with the control panel.
TABLE 1—THERMOSTAT/SUBBASE AND SYSTEM COMPATIBILITY.
Thermostat/
Subbase Model Numbera |
Application |
Stages |
||
Mini-Zone | Mabs II, Mabs II-L | Mabs XX | ||
T874A/Q674B | Zone 1; conventional heat-cool. | Zone 1; conventional heat-cool. | Any zone; conventional heat-cool. | Single-stage |
T874A/Q674D | Zones other than zone 1;
conventional heat-cool. |
Zones other than zone 1;
conventional heat-cool. |
Not applicable | Single-stage |
T874A/Q674E | Not applicable | Not applicable | Any zone; conventional heat-cool. | Single-stage |
T874D/Q674B | Not applicable | Zone 1; conventional
heat-cool. |
Any zone; conventional heat-cool. | Multistage |
T874D/Q674D | Not applicable | Zones other than zone 1;
conventional heat-cool and heat pump. |
Not applicable | Multistage |
T874D/Q674E | Not applicable | Not applicable | Any zone; conventional heat-cool. | Multistage |
Subbase not included with thermostat; order separately.
TABLE 2—THERMOSTAT/SUBBASE SPECIFICATIONS.
Thermostat/Subbase Order Numbera |
Switching |
Thermostat/
Subbase Color |
Anticipator Range (A) | |||
Heating
(Adj.) |
Cooling
(Fixed) |
|||||
System | Fan | |||||
T874A1465/Q674B1471 | HEAT-OFF-COOL | ON-AUTO | White/Gray | Stg. 1—
0.1 to 1.2 |
Stg. 1—
0 to 1.5 |
|
T874A1465/Q674D1123 | None | None | White/Gray | |||
T874A1465/Q674E1379 | HEAT-OFF-COOL-AUTO | ON-AUTO | White/Gray | |||
T874D1801/Q674B1463 | HEAT-OFF-COOL | ON-AUTO | Beige/Brown | Stg. 1—
0.1 to 1.2; Stg. 2— 0.1 to 1.0. |
Stg. 1—
0 to 1.2; Stg. 2— 0 to 1.0. |
|
T874D1827/Q674B1471 | HEAT-OFF-COOL | ON-AUTO | White/Gray | |||
T874D1801/Q674D1115 | None | None | Beige/Brown | |||
T874D1827/Q674D1123 | None | None | White/Gray | |||
T874D1827/Q674E1379 | HEAT-OFF-COOL-AUTO | ON-AUTO | White/Gray |
Subbase not included with thermostat; order separately.
Operation
On a 2-heat thermostat, the two stages of heat make sequentially as the temperature drops. Make refers to the mercury switch initiating a call for heat or cool.
There are about 2° F [1° C] between stages so that the second stage makes only when the first stage cannot handle the load. This is the interstage differential.
Recycling Notice
This control contains mercury in a sealed tube. Do not place control in the trash at the end of its useful life.
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control, or of an old control containing mercury in a sealed tube. If you have questions, call Honeywell at 1-800-468-1502.
Installation
WHEN INSTALLING THIS PRODUCT…
- Read these instructions carefully. Failure to fol-low them could damage the product or cause a hazard-ous condition.
- Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
- Installer must be a trained, experienced service technician.
- After installation is complete, check out product operation as provided in these instructions.
CAUTION
- Disconnect power supply to prevent electrical shock or equipment damage.
- To prevent interference with the thermostat linkage, keep wire length to a minimum and run wires as close as possible to the subbase.
- Do not overtighten thermostat captive mount-ing screws, because damage to subbase threads can result.
- Do not short across terminals of systems con-trols. This can burn out the thermostat heat anticipator.
IMPORTANT: Thermostats are calibrated at the factory by using subbases mounted at true level. Inaccurate sub-base leveling will cause thermostat control deviation.
LOCATION
Locate the subbase about 5 ft [1.5 m] above the floor in an area with good air circulation at average temperature.
Do not mount the subbase where the thermostat may be affected by:
- drafts or dead spots behind doors and in corners.
- hot or cold air from ducts.
- radiant heat from sun, appliances or fireplace.
- concealed pipes and chimneys.
- unheated (uncooled) areas such as an outside wall behind the thermostat.
MOUNTING THE SUBBASE
The thermostat subbase can be mounted on a horizontal outlet box or directly on the wall.
- To mount on a horizontal outlet box, install the sub-base on the outlet box as shown in Fig. 1.
For a wall installation, hold the subbase in position and mark holes for the anchors (Fig. 2). Obtain wall anchors locally. Take care that the wires do not fall back into the wall opening. Set aside subbase. Drill two 3/16 in. [4.8 mm] holes and gently tap anchors into the holes until flush with the wall. - Pull electrical wires through the cover plate (if used) and subbase cable opening (Fig. 3). See Wiring the Sub-base section before pulling any wires.
IMPORTANT: Use 18 gauge, color-coded thermostat cable for proper wiring.
- Secure the subbase with the screws provided. Do not fully tighten the subbase screws.
- Level the subbase using a spirit level, as shown in Fig. 3, and firmly tighten the subbase mounting screws. The subbase mounting holes allow minor out-of-level adjustments.
IMPORTANT: An incorrectly leveled subbase will cause the temperature control to deviate from set point.
WIRING THE SUBBASE
All wiring must comply with local electrical codes and ordinances. Follow equipment manufacturer wiring instructions when available. To wire subbase:
- Connect wires to the subbase terminals. Refer to Figs. 6-10 for wiring diagrams of typical zone systems. A letter code is located near each subbase terminal for identi-fication. The terminal barrier permits straight or conven-tional wraparound wiring connection (Fig. 4).
- Some Q674 Subbases have RC and RH terminals for isolated heating and cooling transformers. For zoning systems, jumper RC and RH terminals as shown in Fig. 5 and wire as single R terminal.
- Firmly tighten each terminal screw.
- Fit wires as close as possible to the subbase. Push excess wire back into hole.
- Plug the hole with nonflammable insulation to pre-vent drafts from affecting the thermostat.
Fig. 6—Typical hookup for MM-2 Mini-zone
Control Panel with T874A Thermostat/Q674B,D Subbase in single-stage heating-cooling two-zone system.
MOUNTING THE THERMOSTAT
- Remove the thermostat cover by pulling the bottom edge of the cover outward away from the base until it snaps free from the cover clip.
NOTE: The cover is hinged at the top and is removed by pulling out at the bottom. - Carefully remove and discard the polystyrene packing insert that protects the mercury switches during shipment.
- Turn over the thermostat base and note the spring fingers that engage the subbase contacts. Make sure the spring fingers are not bent flat, preventing proper electri-cal contact with the subbase.
Set the heat anticipator indicator(s) to 0.1A for proper system operation (Fig. 11). - Note the two tabs on the top inside edge of the thermostat base. The tabs fit into the corresponding slots on the top of the subbase. Mount the thermostat on the subbase. See Fig. 12.
- Align the two captive mounting screws in the thermo-stat base with the posts on the subbase (Fig. 12). Tighten both screws. Do not overtighten the screws or damage to the subbase posts can result.
Fig. 7—Typical hookup for MABS II and MABS II-L
Control Panels with T874A Thermostat/Q674B,D Subbases in single-stage heating-cooling zone system. MABS II Control Panel shown; MABS II-L Control Panel hookup is the same.
Fig. 8—Typical hookup for MABS II and MABS II-L
Control Panels with T874D Thermostat/Q674B,D Subbases in a multistage heating-cooling zone system. MABS II Control Panel shown; MABS II-L Control Panel hookup is the same.
Fig. 9—Typical hookup for MABS XX
Control Panel with T874A Thermostat/Q674B,E Subbases in a single-stage heating-cooling zone system.
Fig. 10-Typical hookup for MABS XX
Control Panel with T874O Thermostat/0674B,E Subbases in multistage heating-cooling zone system.
Settings
TEMPERA TlJRE SETTING
Move the heating and cooling set point levers (Fig. 13) to the desired comfort positions. One lever controls all stages of heating, and the other lever controls all stages of cooling. The minimum differential between the heating and cooling set point is 3° F [2° C].
SUBBASE SETTING (Q6748 AND E ONLY)
Refer to Tables 3 and 4 for descriptions of subbase switching positions
TABLE 3-SUBBASE SYSTEM SWITCHING POSITIONS
Switching Position | Mini-Zone, Mabs II,
Mabs II-L System |
Mabs XX System |
OFF | Both heating and cooling systems are off. If the fan is at AUTO position,
the cooling fan is also off. |
Zone thermostat will not call for heating or woling. |
HEAT | The system operates in heating m0<.Je.
The cooling is off. |
Zone thermostat calls for heating
only. |
COOL | System operates
in cooling mode. Heating is off. |
Zone thermostat calls for cooling only. |
AUTO | Not applicable. | ‘.I.one thermostat calls for heating or cooling depending upon
indoor temperature. |
TABLE 4—-SUBBASE FAN SWITCHING POSITIONS
Switching Po ition | Mini-Zone, Mabs II,
Mabs ll-L System |
Mabs XX System |
ON | Fan operates continuously. | Wilh any zone set to ON, fan will operate continuously. |
AUTO | In cooling, fan operates with cooling equipment; in heating. fan operates as controlled by the plenum
fan control. |
If all zones are set to AUTO, the fan operates as controlled by the plenum fan control in heating and with cooling equipment in cooling. If any zone is set to ON, the fan
will operate continuously. |
Checkout
To move the sub-base switches to the desired control pos1t10ns, use thumb and mdex finger to slide the lever. Stop the lever over the desired function indicator position for proper circuit operation. Before beginning checkout of thermostat operation, set switches on the control panel for the desired system operation. See the instructions provided with the control panel. To set up the system for thermostat checkout, adjust each thermostat setting as shown in Table 5.
TABLE 5—SYSTEM SET-UP FOR THERMOSTAT CHECKOUT.
Control Panel |
Heating | Cooling | ||
Zone 1 | Zones Other
Than Zone 1 |
Zone 1 | Zones Other
Than Zone 1 |
|
Mini-zone MABS II MABS II-L | Set the thermostat system switch to HEAT; set fan switch to AUTO. Move the heating set point lever 10° F [6° C] below room
temperature. |
Move the heating set point lever 10° F
[6° C] below room temperature. |
Set the thermostat system switch to COOL; set fan switch to AUTO. Move the cooling set point lever 10° F [6° C] above room
temperature. |
Move the cooling set point lever 10° F
[6° C] above room temperature. |
MABS XX | On all zone thermostats, set the system switch to HEAT; set the fan switch to AUTO. Move the heating set point lever 10° F [6° C] below room temperature.
NOTE: The control panel provides a three- minute time delay when 24V is applied to the control panel and at the end of each equipment cycle. The high-speed fan runs during this time delay. |
On all zone thermostats, set the system switch to COOL; set the fan switch to AUTO. Move the cooling set point lever 10° F [6° C] above room temperature.
NOTE: The control panel provides a three- minute time delay when 24V is applied to the control panel and at the end of each equipment cycle. The high-speed fan runs during this time delay. |
HEATING
NOTE: If a plenum fan control is used in the heating system, there will be a short delay on a call for heat to allow the furnace to heat the plenum. The fan starts immediately in electric heat systems. Allow 30 seconds for the damper to open or close completely.
Make sure all zone thermostats are set as instructed in the Heating column in Table 5. Check each zone thermo-stat as follows:
- If thermostat has a fan switch, set it to ON. See Fig. 13. After 30 seconds, place your hand in front of an air register in that zone to check for air flow at the register.
- Reset fan switch, if provided, to AUTO. After 30 seconds, make sure air flow at register has stopped.
- Move heating set point lever on zone thermostat 10° F [6° C] above room temperature to call for heat.
- After 30 seconds (longer, if necessary, for time delay on plenum fan control), check for warm air at the register.
- Move heating set point lever on the zone thermostat 10° F [6° C] below room temperature to end a call for heat. After 30 seconds (longer, if necessary, for time delay on plenum fan control or control panel), check that air flow at the register has stopped.
- Repeat steps 1-5 for each zone thermostat.
COOLING
CAUTION Do not operate cooling equipment if outdoor temperature is below 50° F [10° C]. Refer to manufacturer recommendations. Make sure all zone thermostats are set as instructed in the Cooling column in Table 5. Check each zone thermo-stat as follows:
- Move cooling set point lever on the zone thermostat 10° F [6° C] below room temperature to call for cooling.
- After 30 seconds, place your hand in front of an air register in that zone to check for cool air at the register.
- Move the cooling set point lever on the zone thermostat 10° F [6° C] above room temperature to end the call for cooling. After 30 seconds (longer, if necessary, for time delay on control panel), check that air flow at the register has stopped.
- Repeat steps 1-3 for each zone thermostat.
When system checkout is complete, return all thermo-stats to the desired settings for normal system operation.
Calibration
THERMOSTAT
T874 thermostats are accurately calibrated at the factory. They do not have provision for field calibration.
THERMOMETER
The thermometer in your thermostat has been accu-rately calibrated at the factory. The thermometer should only need adjustment if it has been dropped or shifted due to mishandling.
If the set point lever and the thermometer reading do not agree:
- Remove the thermostat cover by pulling up from the bottom of cover until it clears the mounting slots.
- Set the thermostat cover on a table near an accurate thermometer.
- Allow ten minutes for the cover thermometer to sense the area temperature; compare the readings. Be care-ful not to touch the thermometer or breathe on it.
- If the readings are the same, replace the cover and put the system into operation.
- If the readings are different, insert a small screwdriver in the thermometer slot (Fig. 14) and turn it until the thermometers have the same reading.
- Replace the thermostat cover and put the system into operation.
NOTE: Hand heat will offset the thermometer reading. After making each adjustment, wait ten minutes for the thermometer to stabilize before comparing.
Home and Building Control Honeywell Inc.
1985 Douglas Drive North Golden Valley, Minnesota 55422
Printed in U.S.A.
Home and Building Control Honeywell Limited—Honeywell Limitée 740 Ellesmere Road
Scarborough, Ontario
M1P 2V9
Reference
Download Manual:
Honeywell T874A Zone Thermostat Installation Instruction
Leave a Reply