HONEYWELL-T8600D-Programmable-Thermostats-fig-40

HONEYWELL T8600D Programmable Thermostats USER MANUAL

Honeywell logo

HONEYWELL T8600D Programmable Thermostats

HONEYWELL-T8600D-Programmable-Thermostats-product

APPLICATION
The T8600, T8601, and T8602 Chronotherm® IV Deluxe Programmable Thermostats provide electronic control of 24 Vac single-stage heating and cooling systems.

FEATURES AND BENEFITS

  • Full seven-day program capability; different schedules and temperature setpoints may be selected for every day to match the homeowner’s flexible schedule.
  • Copy key makes programming easier and faster for the installer and homeowner.
  • Daylight Savings Time (DST) key for a quick change in and out of Daylight Savings Time.
  • Models available with programmable fan operation for added homeowner comfort.
  • Easy temporary temperature setpoint changes for the current period, vacation hold (1 to 255 days), or indefinite hold add to the homeowner’s comfort and energy savings.
  • Frequently used keys are located by the Liquid Crystal Display (LCD) for quick and easy access to information.
  • Attractive styling complements any decor to the homeowner’s delight.
  • Backlighting the large display makes the LCD very easy to read.
  • Models available with outdoor temperature sensor capability for homeowner convenience. The sensor is also more accurate than a thermometer.
  • Configurable features allow one model to be used to replace many different models (less inventory, no longer need to carry separate models to get these
    features).
    • °F or °C temperature display;
    • Automatic or manual changeover;
    • Electric or conventional heat fan operation
    • Adjustable heating cycle rate.
  • Minimum off time for cooling compressors and heat pumps protects the equipment and extends the equipment’s life.
  • Easy installation, setup, and system testing save the installer time and increase productivity.
  • Self-test simplifies troubleshooting and saves time by overriding the time delays.
  • Adaptive Intelligent Recovery™ control brings the room temperature to the temperature setpoint at the programmed time, maximizing comfort and energy savings.
  • Setpoints are permanently held in memory (no batteries used) and retained during power outages for the increased installer and homeowner convenience.
  • Power-stealing, hardwired and battery-powered models are available for virtually all equipment and application needs.
  • Universal Versaguard™ Thermostat guards available for added security

SPECIFICATIONS

IMPORTANT
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit might not exactly match the listed
specifications. This product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those
conditions are changed.

Thermostat Models
T8600, T8601, and T8602 Thermostats provide features listed in Table 1.
Electrical Rating (Nominal Range): 24 Vac, 50/60 Hz. 20 to 30 Vac, 50/60 Hz.

Batteries
Only T8602 models require batteries.

Loss of Power
The thermostat will maintain programmed times and temperatures for the life of the product. The clock and day information is retained for a minimum of thirty minutes

System Current Load Ratings
6 VA maximum at 30 Vac, 50/60 Hz.
Output Relay Load Rating: See Table 2.
Temperature
Ratings:
Operating Ambient: 40°F to 110°F (4°C to 43°C).
Shipping: -30°F to +150°F (-34°C to +65°C).
Display Accuracy: ±1°F (±0.5°C).

Setpoint
Range:
Heating: 40°F to 90°F (4.5°C to 32°C).
Cooling: 45° F to 99°F (7°C to 35°C)
Differential: 3°F (1.5°C).

Default Settings: see Table 3
Minimum Stage Operation Time:
Minimum Off (Heat and Cool ): factory setting 5 minutes;
option 0 to 5 minutes.

Humidity Ratings
5% to 90% RH, non-condensing.
Clock Accuracy:
+1 minute per month

Table 1. Thermostat Features

 

System

 

Changeover

System Selection Fan Selection  

Comments

T8600 (powered by either the heating or cooling system)
D Heat-Cool Automatic Heat-Off-Cool-Auto On-Auto System and fan selections are done by keyboard.
T8601 (powered by common wire to supply power)
D Heat-Cool Automatic Heat-Off-Cool-Auto On-Auto System and fan selections are done by keyboard.
T8602 (powered by batteries)
D Heat-Cool Automatic Heat-Off-Cool-Auto On-Auto System and fan selections are done by keyboard.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for the complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

  1. Your local Home and Building Control Sales Office (check the white pages of your phone directory).
  2.  Home and Building Control Customer Logistics

Honeywell Inc., 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

Table 2. Maximum Amps at 30 Vac

Relay Running (A) Inrush (A)
Fan 0.5 2.5
Heat 1.5 3.5
Cool 1.5 7.5

Table 3. Default Setpoints

 

Period

 

Time

Heat Setpoint Cool Setpoint Fan Setting
Wake 6:00 AM 70°F (21°C) 78°F (25.5°C) Auto
Leave 8:00 AM 62°F (16.5°C) 85°F (29.5°C) Auto
Return 6:00 PM 70°F (21°C) 78°F (25.5°C) Auto
Sleep 10:00 PM 62°F (16.5°C) 82°F (28°C) Auto

Finish:
Taupe color.

Dimensions:
See Fig. 1.

Mounting Means:
The thermostat mounts on a wallplate. The wall plate mounts horizontally on a wall or outlet box with two no. 6 x 32 screws (included).

Accessories:
C7089B Outdoor Temperature Sensors (69-1020). Universal Versaguard™ Thermostat guards.

RECYCLING NOTICE

HONEYWELL-T8600D-Programmable-Thermostats-fig-1
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.

INSTALLATION

When Installing this Product…

  1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
  2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
  3. Installer must be a trained, experienced service technician.
  4. After completing the installation, use these instructions to check out the product operation.

Location
Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at an average temperature. See Fig. 2. Do not install the thermostat where it can be affected by:

  • drafts, or dead spots behind doors and in corners.
  • hot or cold air from ducts.
  • radiant heat from the sun or appliances.
  • concealed pipes and chimneys.
  • unheated (uncooled) areas such as an outside wall behind the thermostat.

Wallplate Installation
The thermostat can be mounted horizontally on the wall or a 2 in. x 4 in. wiring box. Position the wallplate horizontally on the wall or on a 2 in. x 4 in. wiring box.

  1. Position and level the wallplate (for appearance only). The thermostat will function properly even when not level.
  2.  Use a pencil to mark the mounting holes. See Fig. 3.
  3. Remove the wallplate from the wall and drill two 3/16 inch holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 inch holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
  4. Position the wallplate over the holes, pulling wires through the wiring opening.
  5. Loosely insert the mounting screws into the holes. Tighten mounting screws.

WIRING
All wiring must comply with local electrical codes and ordinances. Follow equipment manufacturer wiring instructions when available. Refer to Fig. 15 through 20 for typical hookups. A letter code is located near each terminal for identification. Refer to Table 4 for terminal designations.

CAUTION

HONEYWELL-T8600D-Programmable-Thermostats-fig-2HONEYWELL-T8600D-Programmable-Thermostats-fig-3
Disconnect power before wiring to prevent electrical shock or equipment damage.

  1. Loosen the terminal screws on the wallplate and connect the system wires. See Fig. 4
    IMPORTANT
    Use 18 gauge, color-coded thermostat cable for proper wiring.
  2.  Securely tighten each terminal screw.
  3. Push excess wire back into the hole.
  4. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat

Mounting Thermostat Wallplate
The thermostat mounts on the wallplate after they are installed.

  1. Engage tabs at the top of the thermostat and wallplate. See Fig. 5.
  2. Press the lower edge of the case to latch
    NOTE: To remove the thermostat from the wall, first pull out at the bottom of the thermostat; then remove the top.HONEYWELL-T8600D-Programmable-Thermostats-fig-4

Table 4. Terminal Designations and Descriptions

Standard Terminal Designations Alternate Terminal Designations  

 

Typical Connection

 

 

Function

 

 

Terminal Type

B Heating damper or changeover valve Output 24V powered contact
C Ba, C, X1, X2 Common Input
G F Fan relay Output 24V powered contact
O R Cooling damper or changeover valve Output 24V powered contact
OT, OT Outdoor temperature sensor (C7089B) Input
R V 24V system or heating transformer Input
RC 24V cooling transformer Input
W H1, R3 Heating relay Output 24V powered contact
Y C1, M Compressor contactor Output 24V powered contact

Some OEM models label the terminal for transformer common B.

HONEYWELL-T8600D-Programmable-Thermostats-fig-5

SETTINGS

Using Thermostat Keys
The thermostat keys are used to:

  • set current day and time,
  • program times and setpoints for heating and cooling,
  • temporarily override program temperatures,
  • display present setting,
  • configure Installer Setup,
  • check System Test,
  • display outdoor temperature (select models),
  • set the system operation,
  • set the fan operation.
  • See Fig. 6 for the location of the keys.

System and Fan Settings
The system’s default setting is Heat and the fan’s default setting is Auto. Use the System and Fan keys to change the settings. See Fig. 7. The fan settings can be set for each program period individually. The system selection is for all the program periods.

HONEYWELL-T8600D-Programmable-Thermostats-fig-6

System settings control the thermostat operation as follows:
Heat: The thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: The thermostat controls the cooling.
Auto: The thermostat automatically changes between heating and cooling operations, depending on the indoor temperature.
Fan settings control the system fan as follows:
On: Fan operates continuously.
Auto: Fan operates with equipment

HONEYWELL-T8600D-Programmable-Thermostats-fig-7
NOTE: Always press the keys with your fingertip or a similar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.

Temperature Settings
Refer to Table 5 for the default program. If the daytime energy savings period is not used, press the period key (Leave or Return) until the time is blank. The fan setting feature is available on select thermostat models. See ProgrammingSection for complete instructions on changing the program.

Table 5. Default Program Settings

 

Period

 

Time

Heat Setpoint Cool Setpoint Fan Setting
Wake 6:00 AM 70°F (21°C) 78°F (25.5°C) Auto
Leave 8:00 AM 62°F (16.5°C) 85°F (29.5°C) Auto
Return 6:00 PM 70°F (21°C) 78°F (25.5°C) Auto
Sleep 10:00 PM 62°F (16.5°C) 82°F (28°C) Auto

INSTALLER SETUP
NOTE: For most applications, the thermostat factory settings will not need to be changed. Review the factory settings in Table 6 and if no changes are
necessary, go to the Installer System Test section The Installer Setup is used to customize the thermostat to specific systems. Some of the options include temperature display, changeover, and outdoor temperature display. Installer Setup numbers are listed in Table 6. The table includes all the configuration options and the factory settings for the thermostat.
A combination of key presses is required to use the Installer Setup feature.

  • To enter the Installer Setup, press and hold the Information i key with the increase ▲ and decrease ▼ keys until the first number is displayed. All display
    segments appear for approximately three seconds before the number is displayed. See Fig. 8 and 9.
  • To advance to the next Installer Setup, press the Time ▲ key.
  • To change a setting, use the increase ▲ or decrease ▼ key.
  • To scroll the Installer Setup numbers backward, press the Time ▼ key.
  • To exit the Installer Setup, press Run Program.HONEYWELL-T8600D-Programmable-Thermostats-fig-11

CAUTION
Heat pump and electric heat systems must be configured to 1 in Installer Setup number 2 to prevent equipment damage caused by the system running
without the fan.

IMPORTANT
Only configurable numbers are shown on the device. Example: If the thermostat does not have a system key, Installer Setup Number 12 will not be displayed. Review Table 6 factory settings and mark any desired changes in the Actual Settings column. When Installer Setup is complete, review the settings to confirm that they match the system.

Table 6. Thermostat Installer Setup Options

 

 

 

Select

Installer Setup Number (Press Time key to  

 

Factory-Setting

 

Other Choices

(Press or key to change)

 

 

Actual

change) Display Description Display Description Setting
Not used 1
Fan operationa 2 0 Conventional applications where equipment controls fan operation in heat mode 1 Heat pump or electric heat applications where thermostat controls fan operation in heat mode
Not used 3
Heating cycle rate 4 6 6—6 cph used for conventional heat 1, 3 or 9 1—1 cph used for radiant floor heat, gravity system

3—3 cph used for hot water systems or high efficiency furnaces

9—9 cph used for electric heat systems

Not used 5 thru 11
System setting adjustment 12 1 Manual changeover 0 or 2 0—Auto changeover 2—Fixed auto changeover
Adaptive Intelligent Recovery™ control 13 0 Adaptive Intelligent Recovery™ control is activated (system starts early so setpoint is reached by start of program period) 1 Conventional recovery (system starts recovery at programmed time)
Degree temperature display 14 0 Temperature is displayed in °F 1 Temperature is displayed in °C
Not used 15
Clock format 16 0 12-hour clock format 1 24-hour clock format
Not used 17 and 18
Extended fan operation in heatinga 19 0 No extended fan operation after the call for heat ends 1 Fan operation is extended 90 seconds after the call for heat ends.
Extended fan operation in cooling 20 0 No extended fan operation after the call for cool ends 1 Fan operation is extended 90 seconds after the call for cool ends.
Not used 21 thru 23
Outdoor temperature display (select models) 24 0 No outdoor temperature is displayed 1 Outdoor temperature is displayed. Needs a C7089B1000 Outdoor Sensor to operate
Not used 25 thru 29
Deadband 30 3 Heating and cooling setpoints can be set no closer than 3°F (1.5°C) 4 thru 10 Heating and cooling setpoints can be set no closer than the chosen value:

4—4°F (2°C)

5—5°F (2.5°C)

6—6°F (3°C)

7—7°F (3.5°C)

8—8°F (4°C)

9—9°F (4.5°C)

10—10°F (5°C)

Table 6. Thermostat Installer Setup Options (continued).

 

 

 

Select

Installer Setup Number (Press Time key to  

 

Factory-Setting

 

Other Choices

(Press or key to change)

 

 

Actual

change) Display Description Display Description Setting
Not used 31 and 32
Minimum off time for the compressor 33 5 5 minute minimum off time for the compressor 0 thru 4 Minimum number of minutes (0 thru 5) the compressor will be off between calls for the compressor
Temperature range stops in heating 34 90 Highest setpoint heating can be set to 40 to 89 Temperature range (1°F increments) heating setpoint can be set to
Temperature range stops in cooling 35 45 Lowest setpoint cooling can be set to 46 to 99 Temperature range (1°F increments) cooling setpoint can be set to
Not used 36
Temperature display adjustment 37 0 No difference in displayed temperature and actual room temperature 3 thru -3 1—Display adjusts to 1°F higher than actual room temperature

2—Display adjusts to 2°F higher than actual room temperature

3—Display adjusts to 3°F higher than actual room temperature

-1—Display adjusts to 1°F lower than actual room temperature

-2—Display adjusts to 2°F lower than actual room temperature

-3—Display adjusts to 3°F lower than actual room temperature

Number 2 must be set to 1 to extend fan operation

IMPORTANT
Review the settings to confirm that they match the system. Press Run Program to exit the Installer Setup. The thermostat has saved the Installer Setup
changes and initiated a reset to operate with these new settings. Be sure to set the current day and time immediately.

Setting Current Day and Time

HONEYWELL-T8600D-Programmable-Thermostats-fig-12

  1. Press Set Current Day/Time.
    NOTE: On initial power-up or after an extended power loss, 1:00 pm flashes on the display until a key is pressed.
  2. Press Day until the current day is displayed.HONEYWELL-T8600D-Programmable-Thermostats-fig-12
    NOTE: Sun=Sunday, Mon=Monday, Tue=Tuesday, Wed=Wednesday, Thu=Thursday, Fri=Friday, Sat=Saturday.
  3. Press Day until the current day is displayed.HONEYWELL-T8600D-Programmable-Thermostats-fig-14
    NOTE: Sun=Sunday, Mon=Monday, Tue=Tuesday, Wed=Wednesday, Thu=Thursday, Fri=Friday, Sat=Saturday.HONEYWELL-T8600D-Programmable-Thermostats-fig-15
  4. Press Run ProgramHONEYWELL-T8600D-Programmable-Thermostats-fig-16

INSTALLER SYSTEM TEST
Use the Installer System Test to check the thermostat’s operation. Refer to Table 7 for a list of the available system tests. To start the system test:

CAUTION
The minimum off time for compressors is bypassed during the Installer System Test. Equipment damage can occur if the compressor is cycled too quickly.
Press and hold the increase ▲ and ▼ decrease keys, at the same time, until 10 appears. All segments of the display are displayed for three seconds before 10 appears. See Fig. 10 and 11.

HONEYWELL-T8600D-Programmable-Thermostats-fig-17

Table 7. Tests Available in Installer System Test

Test Number  

System Test Description

10-19 Heating equipment can be turned on and off
30-39 Cooling equipment can be turned on and off
40-49 Fan equipment can be turned on and off
60 0 to

60 19

Keyboard keys test
70-79 Thermostat information including date code and software versions are displayed

Refer to Table 8 for the directions and results of the specific tests.
NOTE: Press Time ▲ to advance to the next test and Time ▼ to go to the previous test. Press Run Program to exit the system test.

Table 8. Installer System Test Options

 

Key to Press

Test Number  

Description

Heating Equipment System Test
Time 10 Enter heating equipment system test.
11 Heat comes on. When Installer Setup number 2 is 1, the system fan is also energized.
10 Heat and system fan turn off.
Cooling Equipment System Test
Time 30 Change from heating to cooling equipment system test.
31 Cool and system fan come on.
30 Cool and system fan turn off.
Fan Equipment System Test
Time 40 Change from cooling to fan equipment system test.
41 Fan comes on.
40 Fan turns off.
Key Operation System Test
Time 60 2 Change from fan to key operation system test.

NOTE: Press any key and the numbers will change on the display. Press Time ▼ to scroll backward and Time ▲ to scroll forward. The Run Program, Key will not exit from this test. To exit, go to a different test and press Run Program

THERMOSTAT INFORMATION

  1. Press the Time ▲ key to access the thermostat informationHONEYWELL-T8600D-Programmable-Thermostats-fig-20
  2. Press the increase ▲ key to display the production date code. The first two large digits are the month and the third digit is the last digit of the year (Example: 027=February 1997).HONEYWELL-T8600D-Programmable-Thermostats-fig-21
  3. Press the increase ▲ key again to display the software identification code. (Example: 02 = software ID code 2)HONEYWELL-T8600D-Programmable-Thermostats-fig-22
  4. Press the increase ▲ key again to display the software revision number (Example: 001=Revision number 1).HONEYWELL-T8600D-Programmable-Thermostats-fig-23
  5. Press the increase ▲ key again to display the EEPROM identification code. (Example: 314 = EEPROM ID 314)HONEYWELL-T8600D-Programmable-Thermostats-fig-24
  6. Press the Run Program key to exit the system test.

PROGRAMMING

The keyboard is located behind the thermostat cover with three frequently used keys by the display. The thermostat display shows day, time, program period, temperature, system, and fan operation selection. The thermostat can be set for four times and up to eight temperatures for each day of the week (28 independent times and 56 temperature settings). The ▲ and ▼ keys provide quick temporary temperature changes to increase comfort. The Hold Temp key provides energy-efficient operation for extended periods. Before starting the programming procedure, use Table 9 to organize the program schedule. The factory preprogrammed time, temperature, and fan settings are shown in brackets. If a daytime energy savings period is not used, press the period key (Leave or Return) until the time is blank. The fan setting feature is available on select thermostat models. Setting the Current Day and Time

IMPORTANT
Always press the keys with your fingertip or a similar blunt tool. Sharp instruments like pens and pencil points can damage the keyboard.

  1. Press Set Current Day/Time.HONEYWELL-T8600D-Programmable-Thermostats-fig-25
    NOTE: On initial power-up or after an extended power loss, 1:00 pm flashes on the display until a key is pressed.
  2. Press Day until the current day is displayed.HONEYWELL-T8600D-Programmable-Thermostats-fig-26
    NOTE: Sun = Sunday, Mon = Monday, Tue = Tuesday, Wed = Wednesday, Thu = Thursday, Fri = Friday, Sat = Saturday
  3. Press Time ▲ or Time ▼ until the current time is displayed.HONEYWELL-T8600D-Programmable-Thermostats-fig-27
    NOTE: Tapping the Set Current Day/Time will change the time in one-hour increments.HONEYWELL-T8600D-Programmable-Thermostats-fig-28
  4. Press Run ProgramHONEYWELL-T8600D-Programmable-Thermostats-fig-29

Programming the First Day
Start by programming the Wake time and temperature (and fan operation on select models) for any one day:

Table 9. Default Time, Setpoints, and Fan Settings.

Period Start Time Heat Setpoint Cool Setpoint Fan Setting
Wake [6:00 AM] [70°F (21°C)] [78°F (25.5°C)] [Auto]
Leave [8:00 AM] [62°F (16.5°C)] [85°F (29.5°C)] [Auto]
Return [6:00 PM] [70°F (21°C)] [78°F (25.5°C)] [Auto]
Sleep [10:00 PM] [62°F (16.5°C)] [82°F (28°C)] [Auto]
Wake [6:00 AM] [70°F (21°C)] [78°F (25.5°C)] [Auto]
Leave [8:00 AM] [62°F (16.5°C)] [85°F (29.5°C)] [Auto]
Return [6:00 PM] [70°F (21°C)] [78°F (25.5°C)] [Auto]
Sleep [10:00 PM] [62°F (16.5°C)] [82°F (28°C)] [Auto]
Wake [6:00 AM] [70°F (21°C)] [78°F (25.5°C)] [Auto]
Leave [8:00 AM] [62°F (16.5°C)] [85°F (29.5°C)] [Auto]
Return [6:00 PM] [70°F (21°C)] [78°F (25.5°C)] [Auto]
Sleep [10:00 PM] [62°F (16.5°C)] [82°F (28°C)] [Auto]
Wake [6:00 AM] [70°F (21°C)] [78°F (25.5°C)] [Auto]
Leave [8:00 AM] [62°F (16.5°C)] [85°F (29.5°C)] [Auto]
Return [6:00 PM] [70°F (21°C)] [78°F (25.5°C)] [Auto]
Sleep [10:00 PM] [62°F (16.5°C)] [82°F (28°C)] [Auto]
Wake [6:00 AM] [70°F (21°C)] [78°F (25.5°C)] [Auto]
Leave [8:00 AM] [62°F (16.5°C)] [85°F (29.5°C)] [Auto]
Return [6:00 PM] [70°F (21°C)] [78°F (25.5°C)] [Auto]
Sleep [10:00 PM] [62°F (16.5°C)] [82°F (28°C)] [Auto]
Wake [6:00 AM] [70°F (21°C)] [78°F (25.5°C)] [Auto]
Leave [8:00 AM] [62°F (16.5°C)] [85°F (29.5°C)] [Auto]
Return [6:00 PM] [70°F (21°C)] [78°F (25.5°C)] [Auto]
Sleep [10:00 PM] [62°F (16.5°C)] [82°F (28°C)] [Auto]
Wake [6:00 AM] [70°F (21°C)] [78°F (25.5°C)] [Auto]
Leave [8:00 AM] [62°F (16.5°C)] [85°F (29.5°C)] [Auto]
Return [6:00 PM] [70°F (21°C)] [78°F (25.5°C)] [Auto]
Sleep [10:00 PM] [62°F (16.5°C)] [82°F (28°C)] [Auto]
  1. Press WakePress Day until the desired day is displayedHONEYWELL-T8600D-Programmable-Thermostats-fig-30
  2. Press Time ▲ or Time ▼ until the desired Wake time is displayed.HONEYWELL-T8600D-Programmable-Thermostats-fig-30
    NOTE: The program times are in fifteen-minute intervals. (Example: 8:00, 8:15, 8:30)
  3. Press the increase ▲ or decrease ▼ key until the desired Wake temperature is displayed.HONEYWELL-T8600D-Programmable-Thermostats-fig-32
    NOTE: The setpoint temperature range is 40 to 90°F (7 to 31°C) for heating and 45 to 99°F (9 to 37°C) for cooling.
  4. Press Heat/Cool Settings to switch to another system temperature setpoint.HONEYWELL-T8600D-Programmable-Thermostats-fig-33
    NOTE: The program times are the same for both heating and cooling.
  5. Press the  increase ▲ or decrease ▼ key until the desired temperature setpoint is displayedHONEYWELL-T8600D-Programmable-Thermostats-fig-34
  6. Press Leave, Return or Sleep and repeat steps 3, 4, 5, and 5 for programming the rest of the day. The first day is now programmed.HONEYWELL-T8600D-Programmable-Thermostats-fig-35
  7. Press Leave, Return or Sleep and repeat steps 3, 4, 5, and 5 for programming the rest of the day. The first day is now programmed.HONEYWELL-T8600D-Programmable-Thermostats-fig-38

Copying a Day
NOTE: The thermostat must be in program mode to use the copy feature. Go to step 2 if the thermostat is already in program mode.

  1. Press WakeHONEYWELL-T8600D-Programmable-Thermostats-fig-38
  2. Press Day to select the day to be copied if different from the day displayed.
  3. Press Copy.HONEYWELL-T8600D-Programmable-Thermostats-fig-39
  4. Press Day until the day to be copied to is displayedHONEYWELL-T8600D-Programmable-Thermostats-fig-40
  5. Press Copy.HONEYWELL-T8600D-Programmable-Thermostats-fig-41
    NOTE: do will be displayed for two seconds and then the normal program display will be shown.
  6. Repeat steps 2 through 5 for all the days desired.
  7. Press Run Program

Clearing Program Period
NOTE: The thermostat must be in program mode to use the clear feature. Go to step 2 if the thermostat is already in program mode.

  1.  Press Wake, Leave, Return or Sleep.HONEYWELL-T8600D-Programmable-Thermostats-fig-42
  2. Press Day until the desired day is displayed.HONEYWELL-T8600D-Programmable-Thermostats-fig-42
  3. Press Leave, Return or Sleep until the start time and temperature setting are cleared (approximately 3 seconds).HONEYWELL-T8600D-Programmable-Thermostats-fig-44
    NOTE: Wake cannot be cleared.
  4. Repeat steps 2 and 3 for all the periods to be cleared.
  5. Press Run Program.

Setting Temporary Temperatures
Changing Temperature Setting Until the Next Program Period Press the increase ▲ or decrease ▼ key until the desired temperature setpoint is displayed.
NOTE: If ▼ or ▲ appear under the temperature display, it means that both the heating and cooling setpoints are being adjusted. Tapping the key will change both the heat and cool setpoints by one degree. Press I after the desired setpoint is reached to check the setpoints.HONEYWELL-T8600D-Programmable-Thermostats-fig-46

Changing Temperature Setting Indefinitely

  1. Press Hold TempHONEYWELL-T8600D-Programmable-Thermostats-fig-47
  2. Press the increase ▲ or decrease ▼ key to change the setting, if desiredHONEYWELL-T8600D-Programmable-Thermostats-fig-48
  3. Press Heat/Cool Settings to change between heat and cool settingsHONEYWELL-T8600D-Programmable-Thermostats-fig-49
  4. Press the increase ▲ or decrease ▼ key to adjust temperature settingsHONEYWELL-T8600D-Programmable-Thermostats-fig-50
  5. Press Run Program to cancel the Hold and to return to the program

Changing the Temperature Setting Until a Designated Day and Period

  1. Press Hold Temp twiceHONEYWELL-T8600D-Programmable-Thermostats-fig-54
  2. Press Time ▲ or Time ▼ until the desired number of days is displayed (1 to 255 days). (Example: 18 = Hold will override the daily programs for 18 days)HONEYWELL-T8600D-Programmable-Thermostats-fig-52
  3. Press Wake, Leave, Return or Sleep to select the period the program will start. (Example: Return = the thermostat will stop the Hold at the Return period start timeHONEYWELL-T8600D-Programmable-Thermostats-fig-54
  4. Press the increase ▲ or decrease ▼ key to adjust the temperature setting, if desired. (Example: Heat 54° = heating equipment will operate when the room temperature is below 54°F)HONEYWELL-T8600D-Programmable-Thermostats-fig-57
  5. Press Heat/Cool Settings to change between heat and cool settings.
  6. Press the increase ▲ or decrease ▼ key to adjust the temperature setting, if desired. (Example: Cool 84° = cooling equipment will operate

NOTE: In this example, the thermostat uses the Hold setting for eighteen days and returns to the daily programs at the Return period start time. The temperature settings are heating 54°F and cooling 84°F. Only the heating temperature is used because the System is set for Heat. The thermostat will use both the heating and cooling temperature settings when the System is set to Auto (select models).

IMPORTANT
If the Hold needs to be canceled before the designated time, press Run Program to return to the program.

Setting System and Fan

HONEYWELL-T8600D-Programmable-Thermostats-fig-58
The system’s default setting is Heat and the fan’s default setting is Auto. Use the System and Fan keys to change the settings. See Fig. 12. The fan settings can be set for each program period individually. The system selection is for all the program periods.
System settings control the thermostat operation as follows:
Heat: The thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: The thermostat controls the cooling.
Auto: The thermostat automatically changes between heating and cooling operations, depending on the indoor temperature.
Fan settings control the system fan as follows:
On: Fan operates continuously.
Auto: Fan operates with equipment

Setting Temporary Fan Operation
If your thermostat has a Fan key and this feature, press Fan until the desired fan operation is selected. This fan setting will be in effect until the next regularly scheduled period starts.

Using Daylight Savings Time Feature

This feature allows you to change in and out of Daylight Savings Time with a key press. When the Daylight Time Key is pressed in the fall, the time will go back one hour. In the spring, the time will go ahead one hour and the display will show DST. See the Setting the Current Day and Time section for initial setting instructions.
NOTE: Pressing the Daylight Time Key more than once within five minutes will scroll through various time options (For example one hour earlier or later with or without DST). Pressing the Daylight Time Key six times in five minutes will return you to your original settings.

HONEYWELL-T8600D-Programmable-Thermostats-fig-59

Displaying the Outdoor Temperature
If your thermostat is equipped with an outdoor sensor, you can check the temperature at the sensor by pressing I once.

HONEYWELL-T8600D-Programmable-Thermostats-fig-60

OPERATION

P+I Control
The thermostat microprocessor-based control requires that the user understands temperature control and thermostat performance. A conventional electromechanical or electronic thermostat does not control temperature precisely at the setpoint. Typically, there is an offset (droop) in the control point as the system load changes. This is a phenomenon that most people in the industry know and accept. Many factors contribute to offset including switch differential, thermal lag, overshoot, cycle rates and system load.

The thermostat microprocessor simultaneously gathers, compares and computes data. Using this data, it controls a wide variety of functions. The special proprietary algorithm (program) in the thermostat eliminates the factors causing offset. This makes temperature control more accurate than conventional electromechanical or electronic thermostats. The temperature control algorithm is called proportional plus integral (P+I) control.

The thermostat sensor, located on the thermostat or remote, senses the current space temperature. The proportional error is calculated by comparing the sensed temperature to the programmed setpoint. The deviation from the setpoint is the proportional error.

The thermostat also determines integral error, which is a deviation based on the length of error time. The sum of the two errors is the (P+I) error. The cycle rate used to reach and maintain the setpoint temperature is computed using the P+I. The addition of the integral error is what differentiates the thermostat from many other electronic and electromechanical thermostats. See Fig. 13.HONEYWELL-T8600D-Programmable-Thermostats-fig-61

Operation Sequence
The thermostat energizes specific terminals depending on what the Fan and System are set to. The LCD will display the time, room temperature, system, and fan selection. Symbols will be displayed when the heating, cooling or fan is energized. See Table 10 for specific information.
NOTE: Not all the thermostat models have all the terminals listed in the Energize column.

Table 10. Conventional System Sequence of Operation

HONEYWELL-T8600D-Programmable-Thermostats-fig-62

  • When the electric heat fan is selected, G is energized and fan symbol is displayed.
  • Based on the last piece of equipment called (cooling = O or heating = B) and Installer Setup selection.

Equipment Protection
As part of the operational sequence, the thermostat microprocessor also incorporates minimum off time for all cooling stages. Using the minimum off time assures that rapid cycling of equipment does not occur, which extends equipment life. Minimum off times are set in the Installer Setup.

Thermostat Operation
Startup
When power to the thermostat is turned on, a startup and initialization program begins. The startup occurs only on initial power-up. After total loss of power for an extended period, the current time and day may need to be set, but the user program is held. See Table 11 for the default values.
NOTE: Immediately following initialization, the user can enter new setpoints to be used in place of the default values

Table 11. Default Time, Setpoint, and Fan Settings

 

Period

 

Time

Heat Setpoint Cool Setpoint Fan Setting
Wake 6:00 AM 70°F (21°C) 78°F (25.5°C) Auto
Leave 8:00 AM 62°F (16.5°C) 85°F (29.5°C) Auto
Return 6:00 PM 70°F (21°C) 78°F (25.5°C) Auto
Sleep 10:00 PM 62°F (16.5°C) 82°F (28°C) Auto

Adaptive Intelligent Recovery® Feature Adaptive Intelligent Recovery® ensures that the comfort the setting is achieved at the programmed time regardless of
weather conditions. Conventional recovery, however, starts recovery at the beginning of the programmed period and uses the equipment to achieve comfort settings as soon as possible

Adaptive Intelligent Recovery® calculates the recovery ramp based on the number of degrees away from the desired setpoint, previous equipment performance, and weather history to initiate recovery at the optimal time to achieve the comfort setting at the desired time. Once the recovery ramp is intersected, the setpoint changes from the setback setpoint to the comfort setpoint. This change snaps on the equipment and runs the equipment until the setpoint is reached. If the setpoint is reached too early or too late, the ramp is adjusted for the next day’s recovery.

HONEYWELL-T8600D-Programmable-Thermostats-fig-63

TROUBLESHOOTING GUIDE

Symptom Possible Cause Action
Display will not come on. Thermostat is not being powered. •      Check for 24 Vac between R and C or W terminals.

—              If missing 24 Vac:

—              check if the circuit breaker is tripped—reset the circuit breaker.

—              check if the system fuse is blown—replace the fuse.

—              check if the power switch on the HVAC equipment is in the Off position—set to the On position.

—              check wiring between thermostat and HVAC equipment— replace any broken wires and tighten any loose connections.

—              If 24 Vac is present, proceed with troubleshooting.

Temperature display is incorrect. Room temperature display has been reconfigured. Enter Installer Setup number 37 and reconfigure the display.
Thermostat is configured for °F or °C display. Enter Installer Setup number 14 and reconfigure the display.
Bad thermostat location. Relocate the thermostat.
Temperature settings will not change. (Example: Cannot set the The upper or lower temperature limits were reached. Check the temperature setpoints:

•      Heating limits are 40 to 90°F (4.5 to 32°C)

•      Cooling limits are 45 to 99°F (7 to 35°C) except D model cooling limits are 48 to 99°F.

heating higher or the cooling lower.) The setpoint temperature range stops were configured. Check Installer Setup numbers 34 and 35 and reconfigure the setpoint stops.
Heating will not come on. No power to the thermostat. •      Setpoint is above room temperature.

•      Check for 24 Vac between R and C or W terminals.

—              If missing 24 Vac:

—              check if the circuit breaker is tripped—reset the circuit breaker.

—              check if the system fuse is blown—replace the fuse.

—              check if the power switch on the HVAC equipment is in the Off position—set to the On position.

—              check wiring between thermostat and HVAC equipment— replace any broken wires and tighten any loose connections.

—              If 24 Vac is present, proceed with troubleshooting.

Heating will not come on. Thermostat minimum off time is activated. Wait up to five minutes for the system to respond.
System selection is not set to Heat. Set system selection to Heat.
Heating setpoint is below room temperature. Check heating setpoint. Set heating setpoint to desired temperature.
Cooling will not come on. No power to the thermostat. •      Setpoint is below room temperature.

•      Check for 24 Vac between R or RC and C or Y terminals (D models requires power to R at all times).

—              If missing 24 Vac:

—              check if the circuit breaker is tripped—reset the circuit breaker.

—              check if the system fuse is blown—replace the fuse.

—              check if the power switch on the HVAC equipment is in the Off position—set to the On position.

—              check wiring between thermostat and HVAC equipment— replace any broken wires and tighten any loose connections.

—              If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off time is activated. •      Wait up to five minutes for the system to respond.

•      Enter Installer Setup number 33. Reconfigure minimum off time (if required).

System selection is not set to Cool. Set system selection to Cool.
Cool setpoint is above room temperature. Check cooling setpoint. Set cooling setpoint to desired temperature.

Refer to Table 12 for troubleshooting information

Table 12. Troubleshooting Information

Symptom Possible Cause Action
Heating or cooling come on momentarily and shut off Heat or cool circuit is opening up or becoming high impedance. Add resistor in parallel with load or install interface relay.
System on indicator (flame=heat, snowflake=cool) is displayed, but no Fan operation set for 0 (conventional heat) when it should be set for 1 (electric heat). Enter Installer Setup number 2 and reconfigure the fan operation.
warm or cool air is coming from the registers. Conventional heating equipment turns on the fan when the furnace has warmed up to a setpoint. Wait a minute after seeing the on indicator and then check the registers.
Heating or cooling equipment is not operating. Verify operation of heating or cooling equipment in self-test.
Outdoor temperature not displayeda Option not activated. Enter Installer Setup number 24 and set to 1. Thermostat must have OT terminals and a C7089B1000 installed.
Outdoor temperature Outdoor sensor is connected incorrectly. Refer to C7089B1000 installation instructions and check wiring between the thermostat and sensor.
display is incorrecta Wrong sensor. Replace sensor with C7089B1000 sensor.

CROSS-REFERENCE
All SUPER TRADELINE® Chronotherm® IV thermostats are different from the existing Chronotherm® III devices as summarized in Table 13.
Refer to Table 14 for thermostat cross-referencing information.

Table 13. Differences Between Chronotherm® III Thermostats and Chronotherm® IV Thermostats.

Feature/Function Chronotherm® III Family Chronotherm® IV Family
Programming 5-1-1 day programming 7-day programming
Changeover Automatic or manual changeover models available Automatic/manual changeover selectable
Installer configuration Field settings made via screws on the back of the thermostat Field settings made through the keyboard
System switching Mechanical switch Keyboard entry
Fan switching Mechanical switch Keyboard entry
Device color Beige or Premier White® color Taupe or Premier White® color

Table 14. Thermostat Cross Reference Information

 

Model Number

 

Description

TRADELINE®

Replacement

 

Remarks

T8600A One-stage heat conventional thermostat; system powered; system switch—none; fan switch—none.
T8600A1000 Honeywell logo. T8600D2028 Heat/cool model can be used for heat only; system selection Heat-Off-Cool- Auto; duel fuel.
T8600A1018 Canadian TRADELINE® thermostat; Honeywell logo; degree C. T8600D2028 Heat/cool model can be used for heat only; system selection Heat-Off-Cool- Auto; configure for °C in Installer Setup 14; duel fuel.
T8600A1034 Canadian TRADELINE® thermostat; Honeywell logo; Premier White® color; degree C. T8600D2028 Heat/cool model can be used for heat only; system selection Heat-Off-Cool- Auto; configure for °C in Installer Setup 14; duel fuel.
T8600B One-stage heat and one-stage cool conventional thermostat; system powered
T8600B1008 TRADELINE® thermostat; Honeywell logo; system switch—HEAT-OFF; fan switch—none. T8600D2028 Heat/cool model can be used for heat only; system selection Heat-Off-Cool- Auto; fan selection On-Auto; duel fuel; no positive off.
T8600B1016 TRADELINE® thermostat; Honeywell logo; system switch—none; fan

switch—ON-AUTO.

T8600D2028 Heat/cool model can be used for heat only; system selection Heat-Off-Cool- Auto; duel fuel.
T8600C One-stage heat and one-stage cool thermostat; system powered; system switch—HEAT-OFF- COOL; fan switch—ON-AUTO
T8600C1014 TRADELINE® thermostat; Honeywell logo; conventional. T8600D2028 Separate O & B terminals; duel fuel.
T8600C1030 Canadian TRADELINE® thermostat; Honeywell logo; conventional; degree C; O and B terminals. T8600D2028 Configure for °C in Installer Setup 14; duel fuel; jumper R to Rc.
T8600C1048 York logo; conventional; part no. 2ET07700124A. T8600D2028 Separate O & B terminals; duel fuel.
T8600C1055 Canadian TRADELINE® thermostat; Honeywell logo; conventional; degree C. T8600D2028 Configure for °C in Installer Setup 14; duel fuel; jumper R to Rc.
T8600C1063 Trane logo; conventional; part no. THT0594. T8600D2028 Separate O & B terminals; duel fuel.
T8600C1071 Trane logo; electric heat; O and B terminals; part no. THT0595. T8600D2028 Configure for electric heat in Installer Setup 2; jumper R to Rc.
T8600C1089 Texfan logo; conventional. T8600D2028 Separate O & B terminals; duel fuel.
T8600C1097 Glowcore logo; conventional; part no. THC-3. T8600D2028 Separate O & B terminals; duel fuel.
T8600C1105 York logo; conventional; part no. 025-27653 and 2ET0770224A. T8600D2028 Separate O & B terminals.
T8600C1113 Canadian York thermostat; conventional; degree C. T8600D2028 Separate O & B terminals; configure for

°C in Installer Setup 14; duel fuel.

T8600C1121 Arcoaire logo; conventional: part no. 1506-745. T8600D2028 Separate O & B terminals; duel fuel.
T8600C1147 Trane logo; conventional; part no. TAYSTAT300. T8600D2028 Separate O & B terminals; duel fuel; jumper R to Rc.
T8600C1154 American Standard logo; conventional; part no. ASYSTAT600. T8600D2028 Separate O & B terminals; duel fuel; jumper R to Rc.
T8600C1162 SUPER TRADELINE® thermostat; Honeywell logo; duel fuel fan control; O and B terminals. T8600D2028 Jumper R to Rc.
 

Model Number

 

Description

TRADELINE®

Replacement

 

Remarks

T8600C1170 Carrier thermostat; conventional; part no. HH07AX006. T8600D2028 Separate O & B terminals; duel fuel; jumper R to Rc.
T8600C1188 Carrier thermostat; conventional; part no. HH641-101. T8600D2028 Separate O & B terminals; duel fuel; jumper R to Rc.
T8600C1196 Canadian TRADELINE® thermostat; Honeywell logo; Premier White® color; conventional; degree C. T8600D2028 Separate O & B terminals; configure for

°C in Installer Setup 14; duel fuel; jumper R to Rc.

T8600C1204 Canadian Lennox thermostat; conventional; degree C. T8600D2028 Separate O & B terminals; configure for

°C in Installer Setup 14; duel fuel; jumper R to Rc.

T8600C1212 SUPER TRADELINE® thermostat; Honeywell logo; duel fuel fan control; O and B terminals. T8600D2028 Jumper R to Rc; taupe color.
T8600C1220 Servel logo; Premier White® color; conventional; Robur part no. 15471-82. T8600D2028 Separate O & B terminals; duel fuel; taupe color.
T8600C1238 ICP logo; Premier White® color; duel fuel fan control; O and B terminals; part no. HQ1149371HW. T8600D2028 Jumper R to Rc; taupe color.
T8600C1246 ICP logo; Premier White® color; duel fuel fan control; O and B terminals; part no. HQ1149372HW. T8600D2028 Jumper R to Rc; taupe color.
T8600C1253 Consolidated Industries logo; Premier White® color; conventional; part no. 412360. T8600D2028 Separate O & B terminals; duel fuel; taupe color.
T8600C1279 Canadian TRADELINE® (French) thermostat; conventional. T8600D2028 English only keyboard; separate O & B terminals; duel fuel.
T8600D One-stage heat and one-stage cool conventional thermostat; system powered; automatic changeover; system switch— HEAT-OFF-COOL-AUTO; fan switch— ON-AUTO
T8600D1004 TRADELINE® thermostat; Honeywell logo. T8600D2028 Separate O & B terminals; duel fuel.
T8600D1012 Canadian TRADELINE® thermostat; Honeywell logo; degree C. T8600D2028 Separate O & B terminals; configure for

°C in Installer Setup 14; duel fuel.

T8600D1020 Energy Sensor. T8600D2028 Separate O & B terminals; duel fuel.
T8600D1038 Canadian Carrier thermostat; degree C; part no. HH07AT101. T8600D2028 Separate O & B terminals; configure for

°C in Installer Setup 14; duel fuel;

T8600D1046 Trane. T8600D2028 Separate O & B terminals; duel fuel.
T8600D1053 Heil Quaker thermostat; Honeywell logo; part no. HQ1000776HW. T8600D2028 Separate O & B terminals; duel fuel.
T8600D1061 Carrier. T8600D2028 Separate O & B terminals; duel fuel.
T8600D1079 Lennox logo; part no. 27H3101. T8600D2028 Separate O & B terminals; duel fuel.
T8600D1103 Carrier. T8600D2028 Separate O & B terminals; duel fuel.
T8600D1111 TRADELINE® thermostat; Honeywell logo; Premier White® color. T8600D2028 Separate O & B terminals; duel fuel; taupe color.
T8600D1129 Canadian TRADELINE® thermostat; Honeywell logo; Premier White® color; degree C. T8600D2028 Separate O & B terminals; configure for

°C in Installer Setup 14; duel fuel.

T8600D1137 Solitaire logo; Premier White® color; Nordyne part no. 9132400. T8600D2028 Separate O & B terminals; duel fuel; taupe color.
T8600D1145 Canadian Carrier thermostat; Premier White® color; degree C; part no.

HH07AT101-W.

T8600D2028 Separate O & B terminals; configure for

°C in Installer Setup 14; duel fuel.

 

Model Number

 

Description

TRADELINE®

Replacement

 

Remarks

T8601A One-stage conventional heat thermostat; powered direct from 24 Vac transformer
T8601A1017 Canadian TRADELINE® thermostat; Honeywell logo; system switch—none; fan switch—none; degree C. T8601D2019 Heat/cool model can be used for heat only; system selection Heat-Off-Cool- Auto; configure for °C in Installer Setup 14; Premier White® color.
T8601B One-stage conventional heat with fan thermostat; powered direct from 24 Vac transformer
T8601B1007 TRADELINE® thermostat; Honeywell logo; system switch—none; fan

switch—ON-AUTO .

T8601D2019 Heat/cool model can be used for heat only; system selection Heat-Off-Cool- Auto; jumper R to Rc for fan control; Premier White® color.
T8601C One-stage heat and one-stage cool conventional thermostat; powered direct from 24 Vac transformer; system switch—HEAT-OFF-COOL; fan switch—ON-AUTO; O and B terminals
T8601C1003 TRADELINE® thermostat; Honeywell logo. T8601D2019 Jumper R to Rc; Premier White® color.
T8601C1013 Canadian TRADELINE® thermostat; Honeywell logo; degree C. T8601D2019 Configure for °C in Installer Setup 14; jumper R to Rc; Premier White® color.
T8601C1021 New Construction thermostat. T8601D2019 Jumper R to Rc; Premier White® color.
T8601C1039 Carrier logo; part no. HH641-104. T8601D2019 Jumper R to Rc; Premier White® color.
T8601C1047 New Construction thermostat; Premier White® color. T8601D2019 Jumper R to Rc.
T8601C1054 Trol-A-Temp® thermostat; Premier White® color. T8601D2027a Configure manual changeover in Installer Setup12; replacement has Oc terminals.
T8601C1062 Trol-A-Temp® by Honeywell logo. T8601D2027a Configure manual changeover in Installer Setup12; replacement has Oc terminals; Premier White® color.
T8601D One-stage heat and one-stage cool conventional thermostat; powered direct from 24 Vac transformer; automatic changeover; system switch—HEAT-OFF-COOL-AUTO; fan switch—ON- AUTO
T8601D1011 Canadian TRADELINE® thermostat; Honeywell logo; degree C. T8601D2019 Separate O & B terminals; configure for

°C in Installer Setup 14 and changeover in 12; jumper R to Rc; Premier White® color.

T8601D1029 New Construction thermostat. T8601D2019 Separate O & B terminals; configure changeover in Installer Setup 12; jumper R to Rc; Premier White® color.
T8601D1045 Trol-A-Temp® by Honeywell thermostat; Premier White® color. T8601D2027a Separate O & B terminals; replacement has Oc terminals.
T8601D1052 New Construction thermostat; Premier White® color. T8601D2019 Separate O & B terminals; configure changeover in Installer Setup 12; jumper R to Rc.
T8601D1060 California Economizer logo; Premier White® color. T8601D2019 Separate O & B terminals; configure changeover in Installer Setup 12; jumper R to Rc.
T8601D1078 Amana logo; Premier White® color; part no. P1213701F. T8601D2019 Separate O & B terminals; configure changeover in Installer Setup 12; jumper R to Rc.
 

Model Number

 

Description

TRADELINE®

Replacement

 

Remarks

T8602A One-stage heat conventional thermostat; battery powered; system switch—none; fan switch— none
T8602A1008 TRADELINE® thermostat; Honeywell logo. T8602D2000 Heat/cool model can be used for heat only; separate O & B terminals; system selection Heat-Off-Cool-Auto; fan selection Auto-On.
T8602B One-stage heat conventional with fan thermostat; battery powered; system switch—none; fan switch—ON-AUTO
T8602B1006 TRADELINE® thermostat; Honeywell logo. T8602D2000 Heat/cool model can be used for heat only; separate O & B terminals; system selection Heat-Off-Cool-Auto; fan selection Auto-On; jumper R to Rc for fan operation.
T8602B1014 TRADELINE® thermostat; Honeywell logo; Premier White® color. T8602D2000 Heat/cool model can be used for heat only; separate O & B terminals; system selection Heat-Off-Cool-Auto; fan selection Auto-On; jumper R to Rc for fan operation; taupe color.
T8602C One-stage heat and one-stage cool thermostat; battery powered; system switch—HEAT-OFF- COOL; fan switch—ON-AUTO
T8602C1004 TRADELINE® thermostat; Honeywell logo. T8602D2000 Separate O & B terminals; jumper R to Rc.
T8602C1012 Amana logo; conventional; part no.: none. T8602D2000 Separate O & B terminals; jumper R to Rc.
T8602C1020 Rheem logo; conventional; part no.: none. T8602D2000 Separate O & B terminals; jumper R to Rc.
T8602C1046 SUPER TRADELINE® thermostat; Honeywell logo; duel fuel fan control; O and B terminals. T8602D2000
T8602C1061 Trol-A-Temp® by Honeywell thermostat; Premier White® color; conventional; O and B terminals. T8602C2051a
T8602C1079 Trol-A-Temp® by Honeywell thermostat; conventional; O and B terminals. T8602C2051a Premier White® color.
T8602C1095 SUPER TRADELINE® thermostat; Honeywell logo; Premier White® color; duel fuel fan control; O and B terminals. T8602D2000 Taupe color.
T8602C1103 Canadian TRADELINE® thermostat; Honeywell logo; duel fuel fan control; degree C; O and B terminals. T8602D2000 Configure for °C in Installer Setup 14 .
T8602C1129 Universal Parts logo; Rheem part no. 41-21615-05; conventional. T8602D2000
T8602C1137 ICP logo; duel fuel fan control; O and B terminals; part no. HQ1149373HW. T8602D2000
T8602C1145 ICP logo; Premier White® color; duel fuel fan control; O and B terminals;

part no. HQ1149374HW.

T8602D2000 Taupe color.

 

Model Number

 

Description

TRADELINE®

Replacement

 

Remarks

T8602D One-stage heat and one-stage cool conventional thermostat; battery powered; automatic changeover
T8602D1010 Trol-A-Temp® by Honeywell thermostat; Premier White® color; system switch—none; fan switch—none; field terminals: W/4, R/5, Y/6. T8602D2026a
T8602D1028 Trol-A-Temp® by Honeywell thermostat; system switch—none; fan switch—none; field terminals: W/4, R/5, Y/6. T8602D2026a Premier White® color.
CT8602C One-stage heat and one-stage cool retail thermostat battery powered
CT8602C1001 Retail Honeywell logo; off-white color; duel fuel fan control; system switch HEAT-OFF- COOL; fan switch ON-AUTO; separate O and B terminals; clamshell packaging. T8602D2000 TRADELINE® packaging.

WIRING DIAGRAMS (Fig. 15-20)

HONEYWELL-T8600D-Programmable-Thermostats-fig-63HONEYWELL-T8600D-Programmable-Thermostats-fig-65

  1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.HONEYWELL-T8600D-Programmable-Thermostats-fig-66
  2. JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A ONE TRANSFORMER SYSTEM. CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT PUMP SYSTEMS.
  3. AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A
  4. SEPARATE THE CABLE FROM THE THERMOSTAT CABLE.
  5. T8600D MODELS REQUIRE POWER TO R TERMINAL AT ALL TIMES

 

  1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOADvHONEYWELL-T8600D-Programmable-Thermostats-fig-67
    PROTECTION AS REQUIRED. JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A ONE TRANSFORMER SYSTEM.
  2. CAN BE USED FOR CHANGEOVER VALVES ON SINGLE-STAGE HEAT PUMP SYSTEMS.
  3. AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A SEPARATE CABLE FROM THE THERMOSTAT CABLE.
  4. T8600D MODELS REQUIRE POWER TO R TERMINAL AT ALL TIMES

 

  1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.HONEYWELL-T8600D-Programmable-Thermostats-fig-69
  2. JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A ONE TRANSFORMER SYSTEM.
  3. CAN BE USED FOR CHANGEOVER VALVES ON SINGLE-STAGE HEAT PUMP SYSTEMS.
  4. AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A SEPARATE THE CABLE FROM THE THERMOSTAT CABLE.
  5. T8601D MODELS REQUIRE POWER TO R TERMINAL AT ALL TIMES.

Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis MN 55408-052

Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 3N7

Honeywell Asia Pacific Inc.
Room 3213-3225
Sun Hung Kai Centre
No. 30 Harbour Road
Wanchai
Hong Kong

Honeywell Latin American Region
480 Sawgrass Corporate Parkway
Suite 200
Sunrise FL 33325

Honeywell Europe S.A.
3 Avenue du Bourget
B-1140 Brussels Belgium

REFERENCE:

Download Manual:

HONEYWELL T8600D Programmable Thermostats USER MANUAL

Honeywell logo

HONEYWELL T8600D Programmable Thermostats USER MANUAL

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *