HONEYWELL-T8511G-Heat-Pump-Thermostats-featured

HONEYWELL T8511G Heat Pump Thermostats Installational Instruction

Honeywell logo

HONEYWELL T8511G Heat Pump Thermostats

HONEYWELL-T8511G-Heat-Pump-Thermostats-product

APPLICATION
The T8511 Microelectronic Heat Pump Thermostat provides electronic control of 24 Vac two-stage heating and one-stage cooling heat pump systems. Refer to Table 1 for a general description of the thermostat. All T8511 Thermostats require a common wire to supply power.

Table 1. Description of T8511 Thermostats

 

T8511

 

Changeover

 

System Selection

Fan Selection  

Comments

G Automatic Em. Heat-Heat-Off-Auto-Cool On-Auto System and fan selections are by keyboard.
R Manual Em. Heat-Heat-Off-Cool On-Auto System and fan selections are by switches.

MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat

INSTALLATION

When Installing this Product…

  1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
  2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
  3. Installer must be a trained, experienced service technician.
  4. After completing the installation, use these instructions to check out the product operation.

CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry. Disconnect the power supply before installation.

Location
Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at an average temperature. See Fig. 1. Do not install the thermostat where it can be affected by:

  • drafts, or dead spots behind doors and in corners.
  • hot or cold air from ducts.
  • radiant heat from the sun or appliances.
  • concealed pipes and chimneys.
  • unheated (uncooled) areas such as an outside wall behind the thermostat.

Wallplate Installation
The thermostat can be mounted horizontally on the wall or a 2 in. x 4 in. wiring box. Position the wallplate horizontally on the wall or a 2 in. x 4 in. wiring box.

  1. Position and level the wallplate (for appearance only). The thermostat will function properly even when not level.HONEYWELL-T8511G-Heat-Pump-Thermostats-fig-1
  2. Use a pencil to mark the mounting holes. See Fig. 2.HONEYWELL-T8511G-Heat-Pump-Thermostats-fig-2
  3. Remove the wallplate from the wall and drill two 3/16 inch holes in the wall (if drywall) as marked. For firmer materials such as plaster or wood, drill two
    7/32 inch holes. Gently tap anchors (provided) into the drilled holes until flush with the wall
  4. Position the wallplate over the holes, pulling wires through the wiring opening.
  5. Loosely insert the mounting screws into the holes.
  6. Tighten mounting screws.HONEYWELL-T8511G-Heat-Pump-Thermostats-fig-3

WIRING
All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 through 5 for typical hookups. A letter code is located near each terminal for
identification.

HONEYWELL-T8511G-Heat-Pump-Thermostats-fig-3

CAUTION

HONEYWELL-T8511G-Heat-Pump-Thermostats-fig-5
Disconnect power before wiring to prevent electrical shock or equipment damage.

  1. Loosen the terminal screws on the wallplate and connect the system wires. See Fig. 6.
    IMPORTANT
    Use 18 gauge, color-coded thermostat cable for proper wiring.
  2. Securely tighten each terminal screw.
  3. Push excess wire back into the hole.
  4. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat

Mounting Thermostat

HONEYWELL-T8511G-Heat-Pump-Thermostats-fig-6

  1. Engage tabs at the top of the thermostat and wallplate. See Fig. 7.
  2. Press the lower edge of the case to close and latch.

NOTE: To remove the thermostat from the wall, first pull out at the bottom of the thermostat; remove the top last.

Using Thermostat Keys
The thermostat keys are used to:

  •  set temperature,
  • display present setting,
  • configure Installer Setup,
  • check System-Test,
  • display outdoor temperature (select models).

The T8511G has keys to:

  • set the system operation,
  • set the fan operation.
  • See Fig. 8 for the key information.

SETTINGS

System and Fan Settings
System settings control the thermostat operation as follows:
Em. Heat: The emergency heat relay is automatically controlled by the thermostat. The cooling system is off. The compressor is de-energized.
Heat: The thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: The thermostat controls the cooling.
Auto: The thermostat automatically changes between heating and cooling operations, depending on the indoor temperature.
Fan settings control the system fan as follows:
On: Fan operates continuously.
Auto: Equipment controls fan.
The system’s default setting is Heat and the fan’s default setting is Auto. Use the keyboard or system and fan switches, depending on the model, to change the desired settings. See Figs. 9 and 10.

HONEYWELL-T8511G-Heat-Pump-Thermostats-fig-6

NOTE: Always press the system and fan keys with your fingertip or similar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.

Temperature Settings

The default setpoint for heat is 70°F (21°C) and for cool is 78°F (25.5°C). Press the increase ▲ or decrease ▼ key to change the present setting. To change between heat and cool, press the Information I key until the setting to be changed appears.

INSTALLER SETUP

NOTE: For most applications, the thermostat factorysettings do not need to be changed. Review the factory settings in Table 2 and if no changes are necessary, go to the Installer System-Test section. The Installer Setup is used to customize the thermostat to specific systems. Some of the options include temperature
display, changeover, minimum equipment on time, and minimum off time. Installer numbers are listed in Table 2. The table includes all the configuration options and the factory settings available for the T8511.

HONEYWELL-T8511G-Heat-Pump-Thermostats-fig-8

IMPORTANT
The Installer Setup must be set correctly for the HVAC equipment, thermostat, and subbase to operate properly. A combination of key presses are required to use the Installer Setup feature.

  •  To enter the Installer Setup, press and hold the Information i key with the increase ▲ and decrease ▼ keys until the first number is displayed. All display
    segments appear for approximately three seconds before the number is displayed. See Figs. 11 and 12.
  • To advance to the next Installer Setup, press the Information i key.
  • To change a setting, use the increase ▲ or decrease ▼ key.
  • To exit the Installer Setup, press and hold the Information i key until the display returns to normal (approximately three seconds). The display scrolls the
    numbers backward to get to the normal display. The Installer Setup is automatically exited if no key presses are made for five minutes.

Table 2. Thermostat Installer Setup Options

 

 

 

Select

Installer Setup Number  (Press I key

to change)

 

Factory-Setting

 

Other Choices

(Press or key to change)

 

 

Actual

Display Description Display Description Setting
Not used 01 thru 04
Heating cycle 05 03 Stage 2 03, 06 03—3 cph used for stage 1
rate 06 Not used or 09 heat pump systems

06—6 cph used for conventional systems

09—9 cph used for electric heat systems

07 09 Emergency heat
Not used 08 thru 11
Changeover (T8511G only) 12 01 Manual changeover   00—Automatic changeover
Not used 13
Degree temperature display 14 00 Temperature is displayed in °F 01 Temperature is displayed in

°C

Not used 15 thru 18

Table 2. Thermostat Installer Setup Options (Continued).

 

 

 

Select

Installer Setup Number  (Press I key

to change)

 

Factory-Setting

 

Other Choices

(Press or key to change)

 

Actual Setting

Display Description Display Description
Extended fan operation in heating 19 00 No extended fan operation after the call for heat ends 01 Fan operation is extended 90 seconds after the call for heat ends
Extended fan operation in cooling 20 00 No extended fan operation after the call for cool ends 01 Fan operation is extended 90 seconds after the call for cool ends
Not used 21 thru 23
Outdoor temperature display 24 00 No outdoor temperature is displayed 01 Outdoor temperature is displayed. Needs a C7089B1000 Outdoor Sensor to operate.
Not used 25 thru 28
O/B terminal energized in heating or cooling 29 00 O/B terminal is energized for reversing valve in cooling 01 O/B terminal is energized for reversing valve in heating
Not used 30 thru 32
Minimum off time for the compressor 33 05 5 minute minimum off time for the compressor 00, 01,

02, 03

or 04

Minimum number of minutes (0 thru 5) the compressor will be off between calls for the compressor
 

Heating setpoint range stop

34 90 Heating setpoint can be set no higher than 90°F 40 thru

90

Number can be set anywhere between 40 and 90 in 1°F increments
Cooling setpoint range stop 35 45a Cooling setpoint can be set no lower than 45°Fa 45a thru 99 Number can be set anywhere between 45a and 99 in 1°F increments
System On display 36 00 LCD On symbol is displayed when system is energized 01 Display is disabled, usually set for 01 for a zoned system
Temperature display adjustment 37 00 No difference in displayed temperature and actual room temperature -3 thru

03

01—Display adjusts to 1°F higher than actual room temperature

02—Display adjusts to 2°F higher than actual room temperature

03—Display adjusts to 3°F higher than actual room temperature

-1—Display adjusts to 1°F lower than actual room temperature

-2—Display adjusts to 2°F lower than actual room temperature

-3—Display adjusts to 3°F lower than actual room temperature

INSTALLER SYSTEM-TEST

HONEYWELL-T8511G-Heat-Pump-Thermostats-fig-9
Use the Installer System Test to check the thermostat configurations and operation. Refer to Table 3 for a list of the available system tests. To start the system test:
NOTE: The minimum off time for compressors is bypassed during the Installer System Test. Press and hold the increase ▲ and decrease ▼ keys, at
the same time, until two zeros appear. All segments of the LCD is displayed before the two zeros appear

NOTE: Press and hold the increase ▲ and decrease ▼ keys for three seconds to exit the system test. The system test times out after five minutes without any key presses.

Table 3. Tests Available in the Installer System-Test.

Key To Press Test Number  

Description

Heating Equipment System-Test
I 10 Enter heating equipment system-test. (Set T8511R system switch to HEAT and fan switch to AUTO.)
11 Stage-one heat comes on. The system fan is also energized.
12 Stage-two heat comes on. Stage-one heat and system fan remain on.
11 Stage-two heat turns off.
10 Stage-one heat and system fan turn off.
Emergency Heating Equipment System-Testa
I 20 Change from heating to emergency heating equipment system-test. (Set T8511R system switch to EM. HT.)
▲ b 21 Emergency heat comes on. System fan also comes on.
▼ b 20 Emergency heat turns off. (Set T8511R system switch to OFF.)
Cooling Equipment System-Test
I 30 Change from heating or emergency heating to cooling equipment system-test. (Set T8511R system switch to COOL.)
31 Stage-one cooling and system fan come on.
30 Stage-one cool and system fan turn off.

Refer to Table 4 for the directions and results of the specific tests

Table 4. Installer System-Test Options.

Key To Press Test Number  

Description

Fan Equipment System-Test (T8511G only)
I 40 Change from cooling to fan equipment system-test.
41 Fan comes on.
40 Fan turns off.
T8511G System Key or T8511R System Switch Operation System-Test

IMPORTANT

Test numbers will only be displayed when the system is configured for the selected function.

EXAMPLE: Numbers 60, 61 and 62 are the only numbers that will be displayed when a system is configured for heat only.

SYSTEM KEY OR SWITCH SYSTEM-TEST (When system switch is used, move switch to see Test Number.)
I 60 Change from fan to key operation system-test.
System 61 Heat Test number is displayed. (Set T8511R system switch to HEAT.)
System 62 Off Test number is displayed. (Set T8511R system switch to OFF.)
System 63 Cool Test number is displayed. (Set T8511R system switch to COOL.)
System 64 Auto Test number is displayed.
System 65 Emergency heat Test number is displayed. (Set T8511R system switch to EM.HT.)

NOTE: Press system key again to repeat the System Key System-Test.

FAN KEY SYSTEM-TEST (T8511G only)
Fan 68 Fan on Test number is displayed.
Fan 69 Fan off Test number is displayed.
  • Available on select models.
  • T8511R models with fixed emergency heat output will not respond to this keypress.

Thermostat Information

  1. Press the Information i key to access the thermostat informationHONEYWELL-T8511G-Heat-Pump-Thermostats-fig-10
  2. Press the increase ▲ key to display the production date code. The first two large digits are the month and the third digit is the last digit of the year. (Example: 026 = February 1996)
  3. Press the increase ▲ key again to display the software identification code. (Example: 02 = software ID code 2)HONEYWELL-T8511G-Heat-Pump-Thermostats-fig-11
  4. Press the increase ▲ key again to display the software revision number. (Example: 001 = revision number 1
  5. Press the increase ▲ key again to display the EEPROM identification code. (Example: 222 = EEPROM ID 222)
  6. Press and hold the increase ▲ and decrease ▼ keys together, until the room temperature is displayed, to exit the system test. The system test times out after five minutes without any key pressesHONEYWELL-T8511G-Heat-Pump-Thermostats-fig-12

CHECKOUT
Outdoor Temperature Sensor (Where Applicable)
Allow the outdoor temperature sensor to soak in the outdoor air for a minimum of five minutes before taking a reading. With an accurate thermometer (±1°F [±0.5°C]), measure the temperature at the sensor location, allowing time for the thermometer to stabilize before reading. Match the thermometer reading to the outdoor temperature display at the thermostat.

TROUBLESHOOTING GUIDE

Symptom Possible Cause Action
Display will not come on. Thermostat is not being powered. •   Check that C terminal is connected to the system transformer.

•   Check for 24 Vac between C and R or RH terminals.

—   If missing 24 Vac:

—   check if the circuit breaker is tripped—reset the circuit breaker.

—   check if the system fuse is blown—replace the fuse.

—   check if the power switch on the HVAC equipment is in the Off position—set to the On position.

—   check wiring between thermostat and HVAC equipment—replace any broken wires and tighten any loose connections.

—   If 24 Vac is present, proceed with troubleshooting.

Thermostat microprocessor is locked up. Remove the thermostat from the wallplate for 2 minutes. After 2 minutes, replace the thermostat on the wallplate.
Temperature display is incorrect. Room temperature display has been reconfigured. Enter Installer Setup mode number 37 and reconfigure the display.
Thermostat is configured for °F or °C display a. Enter Installer Setup mode number 14 and reconfigure the display.
Bad thermostat location. Relocate the thermostat.
Temperature settings will not change. (Example: Cannot set the The upper or lower temperature limits were reached. Check the temperature setpoints:

•   Heating limits are 40 to 90°F (4.5 to 32°C)

•   T8511R cooling limits are 45 to 99°F (7 to 35°C) and T8511G cooling limits are 48 to 99°F

heating higher or

the cooling lower.)

The setpoint temperature range stops were configured. Check Installer Setup mode numbers 34 and 35 and reconfigure the setpoint stops.
Heating will not come on. No power to the thermostat. •   Check that C terminal is connected to the system transformer.

•   Check for 24 Vac between C and R or RH terminals.

—   If missing 24 Vac:

—   check if the circuit breaker is tripped—reset the circuit breaker.

—   check if the system fuse is blown—replace the fuse.

—   check if the system switch at the equipment is in the Off position—set to On position.

—   check wiring between thermostat and HVAC equipment—replace any broken wires and tighten any loose connections.

—   If 24 Vac is present, proceed with troubleshooting.

TROUBLESHOOTING GUIDE (Continued)

Symptom Possible Cause Action
Heating will not come on. Thermostat minimum off time is activated. Wait up to five minutes for the system to respond.
(Continued) System selection is not set to Heat. Set system selection to Heat.
O/B terminal configured incorrectlya. Check Installer Setup mode number 29 and reconfigure correctly.
O or B terminal miswireda. Check system description to determine whether changeover should be energized in heat (B) or cool (O). Rewire if necessary.
Cooling will not come on. No power to the thermostat. •   Check that C terminal is connected to the system transformer.

•   Check for 24 Vac between C and R or RC and Y terminals.

—   If missing 24 Vac:

—   check if the circuit breaker is tripped—reset the circuit breaker.

—   check if the system fuse is blown—replace the fuse.

—   check if the system switch at the equipment is in the Off position—set to the On position.

—   check wiring between thermostat and HVAC equipment—replace any broken wires and tighten any loose connections.

—   If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off time is activated. •   Wait up to five minutes for the system to respond.

•   Enter Installer Setup mode number 33. Reconfigure minimum off time (if required).

System selection is not set to Cool. Set system selection to Cool.
O/B terminal configured incorrectlya. Check Installer Setup mode number 29 and reconfigure correctly.
O or B terminal miswireda. Check system description to determine whether changeover should be energized in heat (B) or cool (O). Rewire if necessary.
System On indicator is lit, but no heat is being delivered. Heating equipment is not operating. Verify operation of heating equipment in self-test.

Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422

Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario
M1V 4Z

Reference

Download Manual:

HONEYWELL T8511G Heat Pump Thermostats Installational Instruction

Honeywell logo

HONEYWELL T8511G Heat Pump Thermostats Installational Instruction

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *