Honeywell T6380 Electronic Thermostats FEA

Honeywell T6380 Electronic Thermostats PRODUCT SPECIFICATION Guide

Honeywell logo

Honeywell T6380 Electronic Thermostats  

Honeywell T6380 Electronic Thermostats PRO

APPLICATION

The T6380 series of electronic fan coil thermostats provide precision line voltage control of fan-forced Heating, Ventilating and Air Conditioning equipment. Models are available for the cooling-only, manual heat-cool changeover, or remote heat cool changeover systems. Hydronic source heat-cool systems may be two or four-pipe configurations with 0, 1, or 2 valves. Fan control options include constant, cycled, or user selectable “On-Auto” operations. Manual fan speed selection is standard. All models feature an “Off” switch.

FEATURES

  • Electronic temperature sensing provides energy-efficient, precision operation for maximum comfort.
  • Contemporary white sculpted styling.
  • Vertical or horizontal mounting configurations.
  • Adjustment ranges 55° to 90°F or 13° to 32°C.
  • Easy-to-use set point knob.
  • LED system status indicator. “OFF” de-energizes all connected loads.
  • Three level fan speed selection.
  • Constant, cycled, or on-auto selectable fan operation available.
  • Models for manual or remote heat-cool changeover, heating-only, or cooling-only systems.
  • Models for 2 or 4-pipe systems.
  • Rugged molded thermoplastic housing with captive mounting screws, mounts on single-gang NEMA standard (U.S.) electrical box.
  • Screw terminal block connections.
  • Suitable for inductive-rated loads such as valves, relays, contactors and fans.
  • Range stops and cover locking kit available.
  • UL Listed. CSA Certified.

SPECIFICATIONS

MODELS:

Fan Coil System

3-Speed Fan Operation

Constant       Cycled      On-Auto

2- pipe System

•   Cooling only

 

•   Heating only

 

T6383A

Fig. 2a

 

T6381A

Fig. 5a

 

T6387A

Fig. 8a

T6383A

Fig. 2b

T6381A

Fig. 5b

T6387A

Fig. 8a

2- pipe Heat-Cool

•   Manual Change/Over

 

•   Seasonal, auto C/O

 

•   Seasonal, auto C/O with aux. electric heat

 

T6383B

Fig. 3

 

T6381B

Fig. 6

 

N/A

T6383A

Fig. 2c

T6381A

Fig. 5c

T6387A

Fig. 8c

T6383B

Fig. 4b

T6381B

Fig. 7b

N/A
4- pipe Heat-Cool

•   Manual C/O

 

T6383B

Fig. 4a

 

T6381B

Fig. 7a

 

N/A

Electrical Ratings:

  • T6380 Series – Power Supply: 110-130 or 208-277 Vac +10/-15%, 50-60 Hz.
  • T6381, T6387 – Output Rating, cycled (“Auto”) fan control
50-60 Hz 120 V 208 V 230 V 277 V
Full Load Amps* 3.8 2.1 1.9 1.6
Locked Rotor 22.8 12.6 11.4 9.5
Pilot Duty 125 VA

Thermostat (Heat and Cool outputs

50-60 Hz 120 V 208 V 230 V 277 V
Full Load Amps 3.8 2.1 1.9 1.6
Locked Rotor A 22.8 12.6 11.4 9.5
Pilot Duty 125 VA
Resistive (heat only) 10.0 A N/A N/A 5.6

Fan (Air Handler):

50-60 Hz 110-130V 208 V 220-240V 277 V
Full Load Amps** 5.8 3.2 2.9 2.4
Locked Rotor 34.8 19.2 17.4 14.4

Operating range:
32 to + 104 F [0 to +40 C], 5 to 95% RH, non-condensing.

Performance Specifications:
Precision: ±1°F temperature swing [0.9°C differential]. Accuracy: 2°F [1°C] droop with 4 A load.

Dimensions:
See Fig. 1 – Nominal Dimensions.

Mounting:
Direct mounting on single-gang NEMA 2″ x 3″ flush-mount or 2″ x 4″ surface-mount electrical box, or on 4″ x 4″ box Models available for vertical or horizontal mount.

Wiring Connections:
Screw terminal block suitable for 1 – 14 AWG, 2 – 18 AWG, or 1 – 1.5 mm2 copper wire.

Approvals:
CSA Certified LR1322 Underwriters Laboratories Listed E47434.

Accessories:
272824A-T6380 Range stop/cover locking kit. 272827A-T6380 replacement cover with Cool-Warmer

Honeywell T6380 Electronic Thermostats 1

ORDERING INFORMATION

Before ordering please determine the following:

  •  The body type: 2-way or 3-way
  •  The actuator voltage : 24V/50-60Hz
  •  The pipe fitting, size, and flow capacity rating (Cv) required.
  •  Order Specification Number
  •  Accessories, if desired. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
  •  Your local Home and Building Control Sales Office (please check the white pages of your phone directory).
  •  Honeywell Limited, 155 Gordon Baker Rd., North York, ON M2H 3N7.
  • In U.S.A. – Honeywell Inc., 1885 Douglas Drive North, Minneapolis, Minnesota 55422-4386 (612) 951-1000. International Sales and Service Offices in all principal cities of the world. Manufacturing in
  • Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

INSTALLATION

MOUNTING

  • Mount the thermostat on an inside wall 4’ to 5′ [1.5 m] above the floor. Do not mount where thermostat can be affected by drafts, radiant heat from the sun, or other sources of heat.
  • T6380’s mount on NEMA standard 2″x3″ single gang flush or 2″x4″ surface mount electrical box, or on 4″x4″ box with mud ring adaptor (not provided).

WIRING

Internal schematic and external wiring connections are shown in Fig. 2a through Fig. 8c. Wiring connections may be made to the 8 position screw terminal block with 1- 14 AWG, or 2- 18 AWG, solid or stranded copper wiresHoneywell T6380 Electronic Thermostats 2 Honeywell T6380 Electronic Thermostats 3 Honeywell T6380 Electronic Thermostats 4 Honeywell T6380 Electronic Thermostats 5 Honeywell T6380 Electronic Thermostats 6 Honeywell T6380 Electronic Thermostats 7 Honeywell T6380 Electronic Thermostats 8

OPERATION

As the temperature changes, the thermostat makes to open a valve and/or power a blower to provide heating or cooling. The speed at which the air is circulated is controlled by the FAN switch. Continuous (ON) or intermittent (AUTO) fan operation is determined by model number

CHECK-OUT

  • Turn power on. Check out operation according to the SYSTEM switch present.
  • SYSTEM switch OFF de-energizes valve and fan circuits

Models T6381B,: T6383B

  • SYSTEM: HEAT – OFF – COOL Set the SYSTEM switch to HEAT. Rotate the thermostat knob clockwise to energize the heating valve and/or fan (fan auto/cycled mode).
  • The system LED on the thermostat will light when the heating circuit is energized Set the SYSTEM switch to COOL. Rotate the thermo stat knob counter-clockwise to energize the cooling valve and/or fan (fan auto/cycled mode). The system LED on the thermostat will light

Model T6387A

  • SYSTEM: ON -AUTO – OFF
  • Set the SYSTEM switch to ON. The valve will operate on heating or cooling cycle depending on whether hot or chilled water is being supplied. The fan will run continuously.
  • Set the SYSTEM to AUTO. The fan will cycle with the heating or cooling operation

Models: T6381A; T6383A

  • SYSTEM: HI-OFF-MED-LO
  • Set the SYSTEM switch to HI. Rotate the thermostat knob clockwise to energize the heating\cooling valve and/or fan ( constant or cycled fan). The system LED on the thermostat will light when the heating or cooling circuit is energized.

SETTING:

  • The T6380 temperature scale is marked 55 to 90°F or 13 to 32°C, depending on the model. Set the dial indicator marker to the desired temperature.

CALIBRATION:

  • T6380 thermostats are accurately calibrated at the factory under controlled conditions. Do not attempt to field calibrate this device.This thermostat has line voltage connections.

Honeywell

  • Home and Building Control
  • Honeywell Ltd.
  • 155 Gordon Baker Road
  • North York, Ontario
  • M2H 3N7
  • In U.S.A.
  • Honeywell Inc.
  • 1985 Douglas Drive North
  • Golden Valley, MN 55422-3992

Reference

Download Manual:

Honeywell T6380 Electronic Thermostats PRODUCT SPECIFICATION Guide

Honeywell logo

Honeywell T6380 Electronic Thermostats PRODUCT SPECIFICATION Guide

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *