Honeywell T6 Lyric Thermostat Product  

Honeywell- T6- Lyric- Thermostat -Product- PRO -

PRODUCT SPECIFICATION SHEET

The Lyric T6/T6R smart thermostats are designed to provide automatic time and temperature control of heating systems in homes and apartments. It’s compatible with 24-230V on/off and OpenTherm® appliances such as gas boilers, combi-boilers and heat pump. Also works with zone valve applications but not with electric heating (240V). The Lyric T6 is for wired on the wall installations and the Lyric T6R for table stand installations (wireless). Both consist of a thermostat and a Receiver box. The solution is designed with the installer in mind and includes a Receiver module with mounting options for directly on the wall or on a wall box. Wiring can be from below or from the back by lifting the terminal platform, which makes installation quick and easy. The thermostat has a high contrast PMVA display with dynamic text line and touch screen buttons. The thermostat has a simple programming philosophy to make it easier to install and very user friendly.. The Lyric T6 is ideal for consumers who want to control their comfort remotely and is based on a modern design, which is simple to program and easy to use.

FEATURES

THERMOSTAT DISPLAY/BUTTON LAYOUTHoneywell- T6- Lyric- Thermostat -Product-1

Reference to the icons

RECEIVER BOX INTERFACEHoneywell- T6- Lyric- Thermostat -Product-16

SPECIFICATIONS

Lyric T6/T6R Thermostat

Control form : Adaptive Fuzzy Logic
Room Temperature display range : From 0 oC to 50 oC
Dimensions (w x h x d) : Lyric T6 (wired) 103 x 103 x 28 mm

Lyric T6R (wireless) 108 x 103 x 68 mm

Time display : 24-hour or 12-hour AM/PM format
Timekeeping accuracy : Synchronized with the Internet when connected or typically better than 10 minutes per year
Program : 5+2 or daily schedule with 6 daily time and temperature level changes
Time setting resolution : Program – 10-minute steps
Sensing element : 100K (@ 25 oC ) NTC thermistor
Temperature setting range : Program: 5 to 37oC in 0.5 oC steps OFF: 5 oC
Power : Lyric T6 (wired) ~20VDC/300mA by Receiver box

Lyric T6R (wireless) 5VDC power adapter

Wiring : Lyric T6 (wired) terminal block capable of accepting wires up to 1.5 mm2

RF communication

RF operation

band

: ISM (868.0-868.6) MHz, 1% duty cycle
Max. power : 25mW
:
Protocol : Encrypted
Comm. Range : 30 m in a residential building environment
Comm. technology : short, high-rate transmissions to minimize air time and avoid collisions
Receiver class R.E.D. : RX Cat 2 (ETSI EN300 220-1 version 1.3.1)
RF binding method : Factory pre-bound
:
Wi-Fi : IEEE 802.11b/g/n – 2.4GHz
Max. power : 10mW

Receiver box

Power : 230VAC
Electrical rating : 230 V~, 50…60 Hz, 0.5 A to 5 A resistive

0.5 A to 3 A inductive (0.6 pf)

24 V~, 50…60 Hz, 0.5 A to 5 A resistive

0.5 A to 3 A inductive (0.6 pf)

Cycle rate : Selectable by application (see installer set up)
Wiring : Terminal block capable of accepting wires up to 1.5 mm2
Wire access : From back via large wall box opening. From bottom with cable clamps.

Mains wiring – left.

Low voltage wiring – right.

Dimensions : 110 x 110 x 40 mm (w x h x d)
IP class : 30

Environmental and standards

Operating temperature range : 0 to 40oC
Shipping and storage temperature : -20 to 55oC
Humidity range : 10 to 90% rh, non-condensing
EMC : 2014/30/EU
LVD : 2014/35/EU
R&TTE: : 1995/5/EC
:
ErP : Class V (+3%), (EU) 811/2013
Honeywell, declares that this thermostat is in compliance with the essential requirements and other relevant provisions of Directive 2014/53/EU

ADVANCED MENU

Specific Applications Setting What do you need to change?
Cycle

/ Hour

Minimu m

ON time

(in minutes)

Note :

a.     To change Cycle/Hour,

b.     To change Minimum ON Time,

Heating Gas Boilers (<30KW) 6 1 No action required
Oil Boiler 3 4 1.   Set Minimum ON Time to 4 minutes.

2.   Set Cycle/Hour to 3.

Thermal Actuator 12 1 Set Cycle/Hour to 12.
Zone valve 6 1 No action is required.
Special Features Description
OpenTherm If the Receiver box is connected to an OpenTherm appliance various appliance-specific data can be viewed. The data displayed is depending on what the appliance is providing.
Heat Range The normal lower temperature limit of 5 oC can be increased up to 21 oC to protect the inhabitants from cold conditions. This is a useful feature aimed at supporting the elderly, children and disabled inhabitants.

The normal upper-temperature limit of 35 oC can be reduced down to 21 oC to save energy. This feature is useful for leased homes and apartments.

Schedule options The thermostat has 2 default schedules: daily (every day) and 5+2 (week + weekend days)
External Temperature Sensor (only with wired version) An external temperature sensor can be fitted, allowing the thermostat to control the temperature from another room or space, where it is inconvenient to locate the thermostat. It will read the remote sensor every 1 minute. The sensor can be connected up to 50 meters from the unit. This feature is useful for commercial premises where the public may tamper with the product.
Optimisation (optimal start, optimal stop and delayed start) Optimal Start: learns how long it takes your system to reach the programmed temperature. It turns on the heating system earlier to make sure it’s comfortable at the scheduled time.

Optimal Stop: Saves energy and money by switching off a little bit earlier than the normal programmed time. If the home is up to temperature, it will not notice the effect on the temperature, but will show a difference in the fuel bill.

Delayed start: Saves energy by slightly delaying the start of heating depending on the difference between the scheduled temperature and the actual room temperature

Clock setting Change display format (default 24hr) and adjust time and date. When connected to Internet time and date will be synchronized
Low Load Control If the Receiver box is connected to an OpenTherm appliance this setting is used in the demand control. When an appliance is no longer able to modulate lower the control switches from modulating control to low/off control.
Temperature Offset If the Thermostat is located in a hot/cold location and cannot be moved because of wiring then the measured/ displayed temperature can be adjusted by +/- 1,5 oC. This feature is useful if the homeowner wants the reading to match another appliance temperature display.
Binding (only with wireless version) Menu to bind the Thermostat and the Receiver box, test the RF signal strength of the radio communication and to clear an existing binding.
Reset Menu to reset the thermostat back to factory default settings, reset the schedule to default settings, reset the Wi-Fi and Homekit settings.
Failsafe (only with wireless version) When the radio communication between the Thermostat and Receiver box is lost for longer than 1 hour the Receiver box will start to cycle the demand 20% on / 80% off.

DIMENSIONSHoneywell- T6- Lyric- Thermostat -Product-19

INSTALLATION

Prepare Receiver BoxHoneywell- T6- Lyric- Thermostat -Product-21

Needed during installation

Install Receiver Box

Install the Lyric T6 wired thermostat

Optional cover plate (ACC400)
For mounting on an Italian wall box or in case of a larger foot print of the old thermostat a cover plate can be mounted behind the wall plate. Dimensions 117×117 mmHoneywell- T6- Lyric- Thermostat -Product-24

Install the Lyric T6R wireless thermostat

Complete installation
Turn ON mains power to the Heating Appliance and Receiver Box.

Honeywell- T6- Lyric- Thermostat -Product-26

Setup and configuration
After power up, SETUP is displayed on the thermostat’s screen.Honeywell- T6- Lyric- Thermostat -Product-27

BINDING

To bind/rebind

WIRINGHoneywell- T6- Lyric- Thermostat -Product-32

TROUBLESHOOTING

Symptom (Fault message) Possible Cause Remedy
The Receiver box button LED is green but the boiler does not switch on.  

Boiler wiring might be incorrect or broken

 

 

Check the Receiver box wiring

 

 

The status LED on the Receiver box is red (Communication loss)

The Receiver box receives no communication from the thermostat: RF communication might be too far or is blocked due to Receiver box location.

Thermostat is no longer powered.

 

 

Try to move thermostat or Receiver box closer or re-locate.

Check the power to the thermostat

Thermostat alert messages
WIFI RADIO ERROR The Wi-Fi radio of thermostat is faulty.  

Replace thermostat

INTERNAL MEMORY ERROR The internal memory of thermostat is faulty.  

Replace thermostat

INDOOR TEMPERATURE SENSOR ERROR (wired only) The external temperature sensor is not connected or the wiring is faulty.  

 

Check external sensor wiring and sensor

NO COMMUNICATION RECEIVER BOX The thermostat receives no communication from the thermostat: RF signal is blocked due to the location of the thermostat.

Receiver box is no longer powered.

 

RF communication might be too far or is blocked due to the location of the Thermostat or Receiver box.

Check the power to the Receiver box

RF SIGNAL OFRECEIVER

BOX LOW

There is a weak radio signal from the Receiver box Try to move thermostat or Receiver box closer or re-locate.
NO RECEIVER BOX The thermostat is not bound with the Receiver box Bind or re-bind the Receiver box
NO INTERNET Thermostat has no longer Internet connection. End user needs to check their Internet connection via router.
NO WIFI SIGNAL Thermostat has no longer a Wi-Fi connection. End user needs to check their Wi-Fi network of router.
REGISTER ONLINE Thermostat is connected to Internet but not yet registered to an account. End user needs to download the App, create an account and register the thermostat.
 

WIFI NOT CONFIGURED

Thermostat is not connected to a Wi-Fi network. End user needs to download the App, create an account, connect and register the thermostat.
 

BOILER FAILURE FAULT xx

The OpenTherm boiler reported a failure number XX.  

Check the boiler

 

BOILER LOW WATER PRESSURE

The boiler reported low water pressure.  

Fill up the hydronic system with water.

ORDERING SPECIFICATION

Description Model EAN code Literature
Smart Thermostat wired Smart Thermostat wired (UK) Smart Thermostat wireless

Smart Thermostat Wireless (UK)

Large cover plate Lyric T6

Y6H810WF1005 Y6H910WF1011 Y6H910RW4013 Y6H910RW4022

ACC400

5025121381239

5025121381031

5025121381222

5025121381024

5025121381123

All packaging contains 6 languages: English, Dutch, French, German, Italian and Spanish

REFERENCE

DOWNLOAD MANUAL

Honeywell T6 Lyric Thermostat Product Specifications Guide

Other Manual:

Honeywell T6 Pro Wi-Fi Programmable Thermostat Installation Guide

Honeywell logo

Honeywell T6 Lyric Thermostat Product Specifications Guide

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)