Honeywell T16812A1000 Digital Thermostat Operating Instructions

Honeywell logoHoneywell T16812A1000 Digital Thermostat 

Honeywell-T16812A1000-Digital-Thermostat-PRODUCT

CAUTION: ELECTRICAL HAZARD. Can cause electrical shock or equipment damage. Disconnect the power before removing the cover.

Terminal Designations

Terminal Description
L Live
Ch/Cc Heating close / Cooling close
W/Y Heating open / Cooling open
N Neutral
Gl Low fan speed
Gm Medium fan speed
Gh High fan speed

Wiring

Typical wiring for ON / OFF control in 2 pipe systems (VC4 valves)Honeywell-T16812A1000-Digital-Thermostat-FIG.1
Typical wiring for ON / OFF control in 2 pipe systems (VC6valves)Honeywell-T16812A1000-Digital-Thermostat-FIG.2

Thermostat Installation

Honeywell-T16812A1000-Digital-Thermostat-FIG.3

Installer Parameters Table

No Parameter Setting
1 System type 0 = 2 pipe system, heat only
1 = 2 pipe system, cool only
2 = 2 pipe system, heat or cool, manual changeover (default)
9 Temperature Scale 0 = °F
1 = °C (default)
13 Cycles Per Hour value for HEATING 1 – 12 (default = 4)
14 Cycles Per Hour value for COOLING 1 – 6 (default = 3)
18 Temperature display offset -2.0°C to +2.0°C increment 0.5°C

/ -4°F to +4°F increment 1.0°F

(default = 0°)

19 Temperature display mode 0 = Display room temperature (default)
1 = Display setpoint
20 Heating range stops 10 – 32°C (default maximum

= 32°C) / 50 – 90°F (default maximum = 90°F)

21 Cooling range stops 10 – 32ºC (default minimum = 10ºC) / 50 – 90ºF (default minimum

= 50ºF)

22 Keypad lockout 0 = All keys available (default)
1 = All keys locked