CAUTION: ELECTRICAL HAZARD. Can cause electrical shock or equipment damage. Disconnect the power before removing the cover.

Terminal Designations

Terminal Description
L Live
Ch/Cc Heating close / Cooling close
W/Y Heating open / Cooling open
N Neutral
Gl Low fan speed
Gm Medium fan speed
Gh High fan speed

Wiring

Typical wiring for ON / OFF control in 2 pipe systems (VC4 valves)Honeywell-T16812A1000-Digital-Thermostat-FIG.1
Typical wiring for ON / OFF control in 2 pipe systems (VC6valves)Honeywell-T16812A1000-Digital-Thermostat-FIG.2

Thermostat Installation

Honeywell-T16812A1000-Digital-Thermostat-FIG.3

Installer Parameters Table

No Parameter Setting
1 System type 0 = 2 pipe system, heat only
1 = 2 pipe system, cool only
2 = 2 pipe system, heat or cool, manual changeover (default)
9 Temperature Scale 0 = °F
1 = °C (default)
13 Cycles Per Hour value for HEATING 1 – 12 (default = 4)
14 Cycles Per Hour value for COOLING 1 – 6 (default = 3)
18 Temperature display offset -2.0°C to +2.0°C increment 0.5°C

/ -4°F to +4°F increment 1.0°F

(default = 0°)

19 Temperature display mode 0 = Display room temperature (default)
1 = Display setpoint
20 Heating range stops 10 – 32°C (default maximum

= 32°C) / 50 – 90°F (default maximum = 90°F)

21 Cooling range stops 10 – 32ºC (default minimum = 10ºC) / 50 – 90ºF (default minimum

= 50ºF)

22 Keypad lockout 0 = All keys available (default)
1 = All keys locked

REFERENCE:

DOWNLOAD MANUALS:

Honeywell T16812A1000 Digital Thermostat Operating Instructions

Honeywell logo

Honeywell T16812A1000 Digital Thermostat Operating Instructions

Leave a Reply

Your email address will not be published. Required fields are marked *

Your post must include a link to this post.

How does this work?
Write a response on your own website and include a link to this post. Then submit your response’s URL here. Your response may appear here after moderation. To update or remove it, edit or delete your original post and submit the same URL again. Learn more about Webmentions.