Honeywell Q7100A Thermostat Installation Instruction

Honeywell logoHoneywell Q7100A Thermostat

Honeywell-Q7100A-Thermostat-PRODUCT

APPLICATION

The Q7100 Thermostat Subbases provide electronic control of commercial 24 Vac single or multistage heat pumps or conventional heating and cooling systems. Select models have terminals for light-emitting diode LEDs, remote temperature sensors, and remote setback timers. The LED models have up to two field configurable LEDs and up to two factory-assigned LEDs. Refer to Table 1. All Q7100 Thermostat Subbases require a common wire to the supply power.
Table 1. Description of Q7100 Subbases.

 

Q7100

Use T7100  

System

Stages  

Figs.

Heat Cool
A D or F Conventional 1 or 2 1 or 2 8-9
C E or F Heat pump 1, 2 or 3 1 or 2 10-14
D E or F Heat pump 1 or 2  1 or 2 15

a Depends on the model.

RECYCLING NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.

INSTALLATION

When Installing this Product…

  1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
  2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
  3. Installer must be a trained, experienced service technician.
  4. After completing the installation, use these instructions to check out the product operation.

CAUTION
Disconnect power supply to prevent electrical shock or equipment damage.

Location

Subbase without Remote-Mounted Temperature Sensor Install the subbase about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
Do not install the subbase where it can be affected by:

  • drafts, or dead spots behind doors and in corners.
  • hot or cold air from ducts.
  • radiant heat from sun or appliances.
  • concealed pipes and chimneys.
  • unheated (uncooled) areas such as an outside wall behind the thermostat.

Subbase with Remote-Mounted Temperature Sensor(s)
Install the subbase in an area that is accessible for setting and adjusting the temperature and settings. Install the remote-mounted sensor(s) about 5 ft (1.5m) above the floor in an area with good air circulation at an average temperature. See Fig. 1.
Do not mount the sensor(s) where it can be affected by:

  • drafts, or dead spots behind doors and in corners.
  • hot or cold air from ducts.
  • radiant heat from the sun or appliances.
  • concealed pipes and chimneys.
  • unheated (uncooled) areas such as an outside wall behind the thermostat.

If more than one remote sensor is required, they must be arranged in a temperature-averaging network consisting of two, three, four, five, or nine sensors. See Fig. 2 through 6.

Honeywell-Q7100A-Thermostat-fig.1 Honeywell-Q7100A-Thermostat-fig.2 Honeywell-Q7100A-Thermostat-fig.3

Subbase Installation

The sub base can be mounted horizontally on the wall or in a 2 in. x 4 in. wiring box. Position the subbase horizontally on the wall or on a 2 in. x 4 in. wiring box.

  1. Position and level the subbase (for appearance only). The thermostat will function properly even when not level.
  2. Use a pencil to mark the mounting holes. See Fig. 7.Honeywell-Q7100A-Thermostat-fig.4
  3. Remove the subbase from the wall and drill two 3/16 inch holes in the wall (if drywall) as marked. For firmer material such as plaster or wood, drill two 7/32 inch holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
  4. Position the subbase over the holes, pulling wires through the wiring opening.
  5. Loosely insert the mounting screws into the holes.
  6. Tighten mounting screws.

WIRING

All wiring must comply with local electrical codes and ordinances. Refer to Fig. 9 through 15 for typical hookups. A letter code is located near each terminal for identification.
CAUTION
Disconnect power before wiring to prevent electrical shock or equipment damage.

  1. Loosen the terminal screws on the back of the thermostat and connect the system wires. See Fig. 8.
    IMPORTANT
    Use 18 gauge, color-coded thermostat cable for proper wiring.
  2. Securely tighten each terminal screw.
  3. Push excess wire back into the hole.
  4. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.

Honeywell-Q7100A-Thermostat-fig.5Honeywell-Q7100A-Thermostat-fig.6 Honeywell-Q7100A-Thermostat-fig.7 Honeywell-Q7100A-Thermostat-fig.8

  1. CAUTION: EQUIPMENT DAMAGE WILL OCCUR IF POWER IS CONNECTED TO THE D TERMINALS.
  2. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
  3. EM. THE HEAT RELAY DOES NOT CYCLE. TO TURN OFF THE EM. HEAT, GO TO SYSTEM SELECTION AND CHOOSE HEAT.
  4. SELECT MODELS HAVE LEDS.
  5. X2 AND X4 NEED TO BE JUMPERED TO TERMINAL X.

Fig. 14. Typical hookup of Q7100C1008 in a two-stage heat and two-stage cool heat pump system.
Includes remote temperature sensor and remote setback timer. Honeywell-Q7100A-Thermostat-fig.9

  1. CAUTION: EQUIPMENT DAMAGE WILL OCCUR IF POWER IS CONNECTED TO THE D TERMINALS.
  2. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
  3. SELECT MODELS HAVE LEDS.
  4. X4 NEEDS TO BE JUMPERED TO TERMINAL X.

Fig. 15. Typical hookup of Q7100C1073 in a three-stage heat and one-stage cool heat pump system.
Includes remote temperature sensor and remote setback timer. Honeywell-Q7100A-Thermostat-fig.10

Mounting Thermostat on Subbase

Mount the thermostat on the subbase after the subbase is installed.

  1. Engage tabs at the top of thermostat and subbase.
    See Fig. 16.Honeywell-Q7100A-Thermostat-fig.11
  2. Press lower edge of case to close and latch.
    NOTE: To remove the thermostat from the wall, first pull out at the bottom of the thermostat; remove top last.
    IMPORTANT
    Refer to the thermostat installation instructions for Installer Setup, Settings, Installer Self-Test and Troubleshooting information.

Home and Building Control
Honeywell Inc.
Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524

Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road North York, Ontario M2H 2C9

Reference

Download Manual:

Honeywell Q7100A Thermostat Installation Instruction

Honeywell logo

Honeywell Q7100A Thermostat Installation Instruction


Posted

in

by

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *