SPECIFICATION AND ACCESSORIES

  • Input Ratings:
    • Voltage: 18-30 VAC 50/60 Hz transformer of 40 VA or more.
  • Current Draw:
    • Zone Panel: 7.5 VA max.
    • All VA specifications at 24 VAC.
  • Wiring:
    • 18- or 20-gauge solid (not stranded) wire.
  • Humidity Ratings:
    • 5% to 90% RH non-condensing.
  • Temperature Ratings:
    • Shipping: -20° to 150°F (-29° to 66°C)
    • Operating: -40° to 165°F (-40° to 74°C)
  • Dimensions:
    • See below.
  • Emissions:
    • Complies with FCC Class B, part 15 requirements

HONEYWELL- HZ322- TrueZONE- THERMOSTAT- 1

Recommended Thermostats

System Non-

Programmable

Programmable
Single-

Stage

TH5110D, TH3110D,

T87N

TH8110U, TH6110D,

TH4110D

Multi-

Stage

TH5220D TH8320U, TH8321U,

TH6220D, YTH9421C

Heat-

Pump

TH5220D (2H/1C

only)

TH3210D (2H/1C

only)

TH8320U

TH8321U

TH6220D (2H/1C only) TH4210D (2H/1C only) YTH9421C

Wire- less* TH5320R TH6320R

Recommended Dampers

Type Honeywell

Damper

Round Rectangular
Zone Spring-open/

power-closed

ARD ZD
Zone Power-open/

power-closed

MARD/

RRD

For recommended

dampers call the Honeywell Zoning Hotline at

1-800-828-8367.

Bypass Static pres-

sure regulat- ing damper

SPRD/

MARD

SPRD

Maximum Dampers

Ambient Temp. Maximum Damper VA per Zone
100°F (38°C) 28.8
160°F (71°C) 16.8

Accessories.

Accessory Description
40 VA transformer* AT140A1042*
75 VA transformer AT175A1008
Discharge Air

Temperature Sensor *

DATS C7735A1000*
Wireless Outdoor Air Temperature Sensor C7089R1013
Wireless Adapter THM4000R1000
SDCR Slave Damper Control

Relay

Mounting

  • Mount the HZ322 TrueZONE panel near the HVAC equipment; locate it on a wall, stud, roof truss, or cold-air return.
  • NOTE: The HZ322 TrueZONE panel can be mounted in any orientation; level it for appearance only.
  • Please refer to TrueZONE Panel Frequently Asked Questions form 50-9694 for operating detailsHONEYWELL- HZ322- TrueZONE- THERMOSTAT- 2
  • Separate the zone panel cover from the base, and use the base as a template to drill mounting holes.
  • Attach the base to the wall, stud, roof truss, or duct with appropriate screws (not included).
  • HONEYWELL- HZ322- TrueZONE- THERMOSTAT- 3Install thermostats using instructions provided with thermostats.
  • Connect thermostat to zone panel. To connect wire to the panel, strip approximately 1/4 in. of insulation and push wire into terminal. To release wire, press the button on top of the terminal.
  • In retrofit applications, trim end of wire if not straightHONEYWELL- HZ322- TrueZONE- THERMOSTAT- 4
  • Install dampers using instructions provided with dampers. Connect dampers to zone panel.HONEYWELL- HZ322- TrueZONE- THERMOSTAT- 5

Wiring

  • Connect DATS as shown.HONEYWELL- HZ322- TrueZONE- THERMOSTAT- 6
  • Connect the equipment as shown.HONEYWELL- HZ322- TrueZONE- THERMOSTAT- 7
  • If using any wireless device, connect the ABCD terminals for the wireless interface moduleHONEYWELL- HZ322- TrueZONE- THERMOSTAT- 8
  • Connect the transformer as shown.HONEYWELL- HZ322- TrueZONE- THERMOSTAT- 9

The following diagram is an overall view of wiring for a conventional system as depicted in steps 3–8.HONEYWELL- HZ322- TrueZONE- THERMOSTAT- 10

Heat Pump

  • Fig. 12. Zone panel wiring—heat pump with electric auxiliary heat.
  • Use the following diagram for wiring a heat pump with electric auxiliary heat.
  • NOTE: You can use a conventional thermostat for a heat pump system; however, em heat can only be controlled by heat pump thermostats. The diagram below shows a heat pump thermostat used with a heat pump systemHONEYWELL- HZ322- TrueZONE- THERMOSTAT- 11

To enter Configuration

  • Press the Mode button (the Config LED will light up).HONEYWELL- HZ322- TrueZONE- THERMOSTAT- 12
  • Use the Back and Next buttons to navigate through the configuration menus. Pressing Next enters the selected option for that menu item and advances to the next menu. Adjust settings up or down by pressing the Adjust Setting button.
  • The flow chart below illustrates basic zone panel configuration. For additional configuration, see Advanced Configuration on page 8. The label on the inside cover of the HZ322 Zone Panel also contains configuration informationHONEYWELL- HZ322- TrueZONE- THERMOSTAT- 13

CONNECT WIRELESS DEVICES

  • Press the Mode button until the Wireless LED lights up. The TrueZONE must be configured for wireless devices to select Wireless mode
  • Press Next to add devices.
  • While the display alternates the Press Connect and Exit screens, push the Connect button(s) on the wireless device(s).
  • Follow the instructions that came with the wireless device(s).
  • Press Next to exit.HONEYWELL- HZ322- TrueZONE- THERMOSTAT- 14

ADVANCED CONFIGURATION

Menu Name Menu Title (LCD

top line)

Menu Options (LCD bottom

line; defaults in bold)

Menu option description Notes:
Heat Fan HEAT FAN

CONTROL

[HVAC] PANEL Fan control by HVAC In heat mode, fan controlled by HVAC or turned

on by panel in call for heat.

HVAC [PANEL] Fan control by Panel
Stage 2 Timer STAGE 2 TIMER [5 MIN]  > – < [60 MIN]

[5 MIN]  >

5 minutes–60 minutes Number of minutes to delay before engaging second stage.
Purge Timer PURGE TIME [2] 3.5 5 MIN 2.0 minutes Number of minutes panel will purge following call for heat or cool.
2 [3.5] 5 MIN 3.5 minutes
2 3.5 [5] MIN 5.0 minutes
Purge Fan FAN IN PURGE [HVAC] PANEL Fan control by HVAC Fan controlled by HVAC or panel during purge.
HVAC [PANEL] Fan control by Panel
Purge Dampers PURGE DAMPERS [UNCHANGD] OPEN Dampers Unchanged Damper position unchanged or all dampers open during purge.
UNCHANGD [OPEN] Dampers All Open
Auto Changeover Delay CHANGEOVER DELAY [15] 20 30 MIN 15 minutes auto changeover timer Number of minutes to delay auto changeover when one zone is calling for heat and another is calling for cooling.
15 [20] 30 MIN 20 minutes auto changeover timer
15 20 [30] MIN 30 minutes auto changeover timer
DATS Enabled DISCHARGE SENSOR [NO] YES Disabled Enables or disables DATS. If Disabled, the Multistage DATS Inhibit setting is Disabled.
NO [YES] Enabled
DATS High Limit DAT HIGH LIMIT [110 F]  > – < [180 F]

<  [160 F]  >

110 deg F–180 deg F High temperature limit.
DATS Low Limit DAT LOW LIMIT [30 F]  > – <  [60 F]

<  [40 F]  >

30 deg F–60 deg F Low temperature limit.
OT Temp Enabled OT SENSOR [NO] YES Disabled Enables or disables outdoor temperature sensor. If Disabled, the Multistage OT Temp Lockout setting is Disabled.
NO [YES] Enabled
OT Trip Point for

Multistage Lockout

OT LOCKOUT

TEMP

[0 F]  > – <  [50 F]

<  [50 F]  >

0 deg F–50 deg F Above this temperature 2nd stage heat is

locked out.

Multistage DATS Inhibit DAT MSTG INHIBIT NO [YES] Enabled Allow panel to downstage multistage equip- ment when near DATS high or low limit.
[NO] YES Disabled
LCD Contrast Adjust LCD CONTRAST [1]     > – <  [10]

<  [5]      >

Contrast value 1–10 Sets LCD display contrast for ease of viewing. Lowest contrast is 1, highest contrast is 10.
Save Changes SAVE CHANGES? [NO] YES Disabled Saves or rejects the configuration settings.
NO [YES] Enabled
Reload Defaults RELOAD DEFAULTS? [NO] YES Disabled Restores the panel’s default configuration settings.
NO [YES] Enabled

OPERATION

The HZ322 TrueZONE panel contains an LED display that communicates system and zone status. The LEDs indicate the following information Much of this information, as well as configuration information, is listed on the label on the inside of the HZ322 cover. For users who prefer French or Spanish labels, they are provided in form 69-2199FS. Cut them out and attach them to the inside of the HZ322 cover.

Table 6. LED Operation.
LED Description
HEAT 1 Solid when in heat stage 1. Blinking when DATS high limit mode has been reached.
HEAT 2 Solid when in heat stage 2. Blinking when stage 2 locked out due to

DATS or OT.

COOL 1 Solid when in cool stage 1. Blinking when DATS low limit mode has been reached.
COOL 2 Solid when in cool stage 2. Blinking when stage 2 locked out due to DATS.
PURGE Solid when in purge (at power-up and after a call for heat or cool). Blinking when the DATS sensor has failed, or the wires are shorted or open. Will blink for 3 minutes at power-up if DATS is not present.
FAN Solid with a call for fan.
EM HEAT Solid when in emergency heat mode. This light does not indicate a call for heat. Emergency heat will only run when both HEAT and EM HEAT are lit.
ZONE 1, 2, 3 Solid green when open or opening. Solid red when closed or closing. Blinking amber when there is a damper or thermostat short circuit (cir- cuit breaker trip).

HONEYWELL- HZ322- TrueZONE- THERMOSTAT- 15

CHECK OUT

To enter Checkout, with the zone panel cover off, press the Mode button until the Check out LED lights up. Use the Adjust Setting and Next buttons to work through the checkout menu as listed below. See the Configuration section on page 7 for instructions on using these buttons.
Steps 3–10 cycle through heating and cooling stages and open and close dampers to verify proper operation. Steps 11–14 verify thermostat operation and correct wiring. This is done by making the thermostats call for heat or cool and viewing the active wires as displayed on the LCD screen.

Table 7. Checkout.
Checkout Step Line 1 display Line 2 Display Notes:
1. Display shows OT OT SENSOR VAL current OT temp (dynamic) All zone dampers open, all other relays OFF.
2. Display shows DATS DAT SENSOR VAL current DATS (dynamic)
3. Heat stages test TEST HEAT [OFF] 1 2 Heat turns on (fan also turns on if configured for fan on in heat).
4. EM Heat stages test TEST EMERG HEAT [OFF] 1 2 Emergency heat turns on (fan also turns on).
5. Cool stages test TEST COOL [OFF] 1 2 Cooling turns on (fan also turns on).
6. Fan Test TEST FAN [OFF] ON Fan cycles on and off.
7. Damper 1 test TEST Z1 DAMPER [OPEN] CLOSED Cycles damper position with fan on.
8. Damper 2 test TEST Z2 DAMPER [OPEN] CLOSED Cycles damper position with fan on.
9. Damper 3 test TEST Z3 DAMPER [OPEN] CLOSED Cycles damper position with fan on.
10. View Tstat1 inputs ZONE1 STAT INPTS Displays active Tstat1 terminals or displays wire- less thermostat operation Tests thermostat wiring with HVAC off.
11. View Tstat2 inputs ZONE2 STAT INPTS Displays active Tstat2 terminals or displays wire- less thermostat operation Tests thermostat wiring with HVAC off.
12. View Tstat3 inputs ZONE3 STAT INPTS Displays active Tstat3 terminals or displays wire- less thermostat operation Tests thermostat wiring with HVAC off.
13. Exit checkout mode? EXIT CHECKOUT? (NEXT = EXIT)
14. Exiting checkout mode EXITING CHECKOUT

Warranty

Honeywell warrants the products in this catalog (except those parts designated on Honeywell’s price lists as not covered by this warranty) to be free from defects due to workmanship or materials, under normal use and service, for the following warranty periods. Honeywell VisionPRO®, Commercial VisionPROTM, FocusPRO®, PRO 4000, PRO 3000, LineVoltTM PRO, Digital RoundTM, and Modern RoundTM (T87K, N) Series Thermostats with a date code of 0501 or later: sixty (60) months from date of installation. CommercialPRO, PRO 2000, and PRO 1000 thermostats: twenty-four (24) months from the date of installation. All other Honeywell thermostats and thermostats with a date code of 0452 or earlier: twelve (12) months from the date of installation, unless specified otherwise. Honeywell Air Cleaners, Humidifiers, Ventilators, Ultraviolet Treatment, and Zoning Products with a date code of 0501 or later, excluding replacement maintenance parts: sixty (60) months from the date of installation. All other Honeywell indoor air quality and zoning products with a date code of 0452 or earlier: twenty-four (24) months from the date of installation, unless specified otherwise. Variable frequency drive devices (VFD) and accessories: new products for thirty-six (36) months and factory refurbished drives for twelve (12) months from the date of installation when start-up and commissioning is performed by Honeywell VFD Authorized and trained personnel. All VFD warranty return products must have prior authorization (Form No. 87-0284) and be returned only to the VFD Service Center in Chattanooga, TN. MS, MN, and Fact Acting 2-position Direct Coupled Actuators: sixty (60) months from date of installation. The warranty period for all other products is twelve (12) months from date of installation. If a product is defective due to workmanship or materials, is removed within the applicable warranty period, and is returned to Honeywell in accordance with the procedure described below, Honeywell will, at its option, either repair, replace or credit the customer for the purchase price of the product, in accordance with the procedure described below. This warranty extends only to persons or organizations who purchase products in this catalog for resale. The expressed warranty above constitutes the entire warranty of Honeywell with respect to the products in this catalog and IS instead of ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL HONEYWELL BE RESPONSIBLE FOR ANY CONSEQUENTIAL DAMAGES OF ANY NATURE WHATSOEVER.

Need Help?
For assistance with this product please visit http://yourhome.honeywell.com or call Honeywell Zoning Hotline toll-free at 1-800-828-8367

Automation and Control Solutions

Reference

Download Manual:

HONEYWELL HZ322 TrueZONE THERMOSTAT Installation Guide

Honeywell logo

HONEYWELL HZ322 TrueZONE THERMOSTAT Installation Guide


Posted

in

by

Tags:

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *