Honeywell FocusPro TH5320C Wireless Thermostat
Use With
Non-Programmable Digital Communicating Thermostat
To be used with up to 3 Heat 2 Cool conventional and heat pump systems with W8835 Zone Panel or W8635 or THM5241 Equipment Interface Modules (EIM).
- W8835 Zone Panel—up to 3H/2C conventional or heat pump system
- W8635A EIM—up to 2H/2C conventional system
- W8635B EIM—up to 2H/1C heat pump system
- THM5421 EIM—up to 3H/2C conventional or heat pump
System Types
- Gas, oil, or electric heat with air conditioning
- Warm air, hot water, high-efficiency furnaces, heat pumps, steam, gravity.
- Heat only — two-wire systems, three-wire zone valves (Series 20), and normally open zone valves
- Heat only with fan
- Cool only
Must be installed by a trained, experienced technician
Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.
Need Help?
For assistance with this product please visit http://yourhome.honeywell.com or call Honeywell Customer Care toll-free at 1-800-468-1502.
Wallplate installation
- Separate wallplate from thermostat.
- Mount wallplate as shown below.
Drill 3/16” holes for drywall. Drill 7/32” holes for plaster.
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.
Wiring
Terminal designations
Thermostat Terminals (connect to network zone panel or EIM):
- Data communication
- Power
- Common
This thermostat does not use batteries. Installing batteries could lead to corrosion of the batteries and damage the thermostat.
Thermostat mounting
Once wallplate is securely mounted on wall:
- Push excess wire back into the wall opening.
- Plug wall opening with non-flammable insulation.
- Align the 4 tabs on the wallplate with the slots on the back of the thermostat.
- Gently push the thermostat onto the wallplate; thermostat will snap into place.
Installer setup
Follow the procedure below to configure the thermostat to match the installed heating/cooling system, and customize feature operation as desired.
Setup function Settings & options (factory default in bold)
0 Zone Instance
- 0 Not Zoned
- 1-9 Zoned (default setting 2)
1 System type
- 0 1 heat/1 cool conventional
- 1 1 heat/1 cool heat pump (no aux. heat)
- 2 Heat only — 2-wire systems, 3-wire zone valves (Series 20), and normally open zone valves
- 3 Heat only with fan
- 4 Cool only
- 5 2 heat/1 cool heat pump (with aux. heat)
- 6 2 heat/2 cool conventional
- 7 2 heat/1 cool conventional
- 8 1 heat/2 cool conventional
- 9 2 heat/2 cool heat pump (no aux. heat)
- 10 3 heat/2 cool heat pump (with aux. heat)
- A Auto Discover
2 Changeover valve (O/B terminal)
- 0 Changeover valve (O/B terminal energized in cooling)
- 1 Changeover valve (O/B terminal energized in heating)
3 Fan control (heating)
- 0 Gas or oil furnace — equipment controls fan in heating
- 1 Electric furnace — thermostat controls fan in heating
5 Stage 1 heat cycle rate (CPH: cycles/hour)
- 5 For gas or oil furnaces of less than 90% efficiency
- 1 For steam or gravity systems
- 3 For hot water systems & furnaces of over 90% efficiency
- 9 For electric furnaces
6 Second Stage Heat Cycle Rate
- 5 Standard Gas or Oil Furnace
- 1 Steam or Gravity
- 3 90% + Efficient Furnace or Hot Water
- 9 Electric Furnace [Other options: 2, 4, 6, 7, 8, 10, 11, 12 for Special Applications]
- A Auto Discover
7 Third Stage Heat Cycle Rate
- 5 Standard Gas or Oil Furnace
- 1 Steam or Gravity
- 3 90% + Efficient Furnace or Hot Water
- 9 Electric Furnace [Other options: 2, 4, 6, 7, 8, 10, 11, 12 for Special Applications]
- A Auto Discover
8 Emergency Heat Cycle Rate
- 9 Electric Furnace [Other options: 1–8, 10, 11, 12 for Special Applications]
- A Auto Discover
9 Stage 1 compressor cycle rate (CPH)
- 3 Recommended for most compressors [Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
10 Second Stage Compressor Cycle Rate
- 3 Compressor Cycle Rate [Other options: 1, 2, 4, 5, 6 for Special Applications]
- A Auto Discover
12 Manual/Auto changeover
- 0 Manual changeover (Heat/Cool/Off)
- 1 Auto changeover (Heat/Cool/Auto/Off)
- 2 Auto changeover only (Auto)
14 Temperature display
- 0 Fahrenheit
- 1 Celsius
15 Compressor protection
- 5 Five-minute compressor off time [Other options: 0, 1, 2, 3 or 4-minute off time]
19 Service Indicator
- 00–199 Diagnostic Codes
- See Special function section on page 5.
23 Backlight Mode
- 0 Disabled
- 1 Enabled
26 Aux Control
- 0 Comfort
- 1 Economy
- See Special function section on page 5.
27 Heat temperature range stops
- 90 Max. heat temperature setting is 90 °F (32 °C) [Other options: 40 °F to 89 °F (4.5 °C to 31.5 °C)]
28 Cool temperature range stops
- 50 Min. cool temperature setting is 50 °F (10 °C)
- [Other options: 51 °F to 99 °F (10.5 °C to 37 °C)]
Installer system test
System test System status
10 Heating system
- 0 Heat and fan turn off.
- 1 Stage 1 heat turns on. Fan turns on if Setup Function 1 is set to 1, 5, 9 or 10 OR Setup Function 3 is set to 1.
- 2 Stage 2 heat turns on.
- 3 Stage 3 heat turns on.
20 Emergency heating system
- 0 Heat and fan turn off
- 1 Heat and fan turn on
30 Cooling system
- 0 Compressor and fan turn off
- 1 Compressor and fan turn on
- 2 Stage 2 compressor turns on
40 Fan system
- 0 Fan turns off
- 1 Fan turns on
70 Thermostat information (for reference only)
- 71 Software Revision Number (major revisions)
- 72 Software Revision Number (minor revisions)
- 73 Configuration Identification Number (major)
- 74 Configuration Identification Number (minor)
- 75 Production configuration date code (week)
- 76 Production configuration date code (year)
CAUTION: Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.
Special function
Auxiliary heat control (Setup Function 26):
- Comfort Setting: The thermostat will prioritize comfort over economy depending on heat pump performance, load conditions and whether the thermostat is calling for the heat pump. Raising the temperature just a few degrees will often activate the auxiliary heat.
- Economy Setting: The thermostat will attempt to reach the temperature setting without activating the auxiliary heat. The thermostat will wait to activate the auxiliary heat depending on heat pump performance, load conditions and how many degrees the temperature setting is changed.
Diagnostic Codes (Setup Function 19):
When Error Codes are present the home screen of the thermostat will display “SERVICE NEEDED” and scroll through all active error codes. Setup Function 19 will display a list of the 10 most recent error codes, both active and inactive. The number on the right of the thermostat will show the number of active and inactive error codes saved in the thermostat. To view the error codes press the up arrow. To clear the list, press and hold both the up and down arrow keys. Active errors can not be cleared; the source of the error must be resolved prior to clearing from the list.
Accessories & replacement parts
Please contact your distributor to order replacement parts.
Part Description Part Number
Small cover plate assembly: 50001137-001
Medium cover plate assembly: 50002883-001
12 pack of small cover plates: 50007297-001
12 pack of medium cover plates: 50007298-001
EnviraZONE Zone panel: W8835A1004
Equipment Interface Module for 2H/2C conventional systems: W8635A1006
Equipment Interface Module for 2H/2C heat pump systems: W8635B1004
Telephone Access Module: W8735B1003
2-Channel Telephone Access Module: W8735D1009
4-Channel Telephone Access Module: W8735D1017
Note: Use to cover marks left by old thermostats.
Specifications
- Temperature Ranges
- Heat: 40° to 90°F (4.5° to 32°C)
- Cool: 50° to 99°F (10° to 37°C)
- Operating Relative Humidity: 5% to 90% (non-condensing)
- Physical Dimensions
- TH5220D: 3-9/16” H x 5-13/16” W x 1-1/2” D 91 mm H x 147 mm W x 38 mm D
- TH5110D: 3-7/16” H x 4-1/2” W x 1-5/16” D 86 mm H x 114 mm W x 33 mm D
- Operating Ambient Temperature: 32° to 120°F (0° to 48.9°C)
- Shipping Temperature: -20° to 120°F (-28.9° to 48.9°C)
Automation and Control Solutions
Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée 35 Dynamic Drive
Toronto, Ontario M1V 4Z9
http://yourhome.honeywell.com
Printed in the U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
® U.S. Registered Trademark.
© 2008 Honeywell International Inc. 69-2019EFS—02 M.S. Rev. 01-08
Reference
Download manual: Honeywell FocusPro TH5320C Wireless Thermostat Installation Guide