Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Installation Instructions

Honeywell logo

Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat 

Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- PRO

Wallplate installation

  • Remove the wallplate from the thermostat, then follow directions below for mounting.
  • Remove battery holder.Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 1
  • Pull here to remove wallplate from new thermostat.
  • Pull wires through wire hole.
  • Position wallplate on wall, level and mark hole positions with pencil.
  • Drill holes at marked positions as shown below, then tap in supplied wall anchors.
  • Place wallplate over anchors, insert and tighten mounting screws.Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 2

Power optionsHoneywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 3

Wiring

Wiring terminal designations

Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.

Conventional Terminals:

  • Rc 24VAC power from cooling transformer
  • R 24VAC power from heating transformer
  • W Heat relay (stage 1)
  • W2 Heat relay (stage 2)
  • Y Compressor contactor (stage 1)
  • Y2 Compressor contactor (stage 2)
  • G Fan relay
  • C 24VAC common. For 2 transformer systems, use common wire from cooling transformer.Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 4

Heat Pump Terminals:

  • Rc 24VAC power from cooling transformer
  • R 24VAC power from heating transformer
  • O/B Changeover valve
  • Y Compressor contactor
  • Y2 Compressor contactor (stage 2) -TH5320U only
  • G Fan relay
  • Aux/E Auxiliary/Emergency heat relay
  • L Sends output when set to Em. Heat
  • C 24VAC commonHoneywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 5

Wiring conventional systems

1H/1C System (1 transformer)Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 6

  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • Y Compressor contactor
  • C 24VAC common [3]
  • W Heat relay
  • G Fan relay

Heat-only SystemHoneywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 7

  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • C 24VAC common [3]
  • W Heat relay

Heat-only System (Series 20) [5]Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 7

  • Rc [R+Rc joined by jumper]
  • R Series 20 valve terminal “R” [1]
  • Y Series 20 valve terminal “W”
  • C 24VAC common [3]
  • W Series 20 valve terminal “B”

Heat-only System (normally open zone valve) [5]Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 7

  • Rc [R+Rc joined by jumper]
  • R Power [1]
  • Y Normally open zone valve
  • C 24VAC common [3]

1H/1C System (2 transformers)Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 6

  • Rc Power (cooling transformer) [1, 2]
  • R Power (heating transformer) [1, 2]
  • Y Compressor contactor
  • C 24VAC common [3, 4]
  • W Heat relay
  • G Fan relay

Heat-only System with FanHoneywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 6

  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • C 24VAC common [3]
  • W Heat relay
  • G Fan relay

Cool-only SystemHoneywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 6

  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • Y Compressor contactor
  • C 24VAC common [3]
  • G Fan relay

2H/2C System (1 transformer) [6]Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 8

  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • Y Compressor contactor (stage 1)
  • C 24VAC common [3]
  • W Heat relay (stage 1)
  • G Fan relay
  • W2 Heat relay (stage 2)
  • Y2 Compressor contactor (stage 2)

2H/2C System (2 transformers) [6]Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 8

  • Rc Power (cooling transformer) [1, 2]
  • R Power (heating transformer) [1, 2]
  • Y Compressor contactor (stage 1)
  • C 24VAC common [3, 4]
  • W Heat relay (stage 1)
  • G Fan relay
  • W2 Heat relay (stage 2)
  • Y2 Compressor contactor (stage 2)

NOTES
Wire specifications:

  • Use 18- to 22-gauge thermostat wire. Shielded cable is not required.
  •  Power supply. Provide disconnect means and overload protection as required.
  •  Remove jumper for 2-transformer systems.
  •  Optional 24VAC common connection.
  •  Common connection must come from cooling transformer.
  •  In Installer Setup, set system type to Heat Only.
  • In Installer Setup, set system type to 2Heat/2Cool Conventional.
  •  In Installer Setup, set changeover valve to O or B.
  •  In Installer Setup, set system type to 2Heat/1Cool Heat Pump.
  •  In Installer Setup, set system type to 2Heat/2Cool Heat Pump.
  •  In Installer Setup, set system type to 3Heat/2Cool Heat Pump.
  •  L terminal sends a continuous output when thermostat is set to Em. Heat. Connect to Honeywell zoning panels to switch the panel to Emergency Heat.

Wiring heat pump systems

1H/1C Heat Pump SystemHoneywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 9

  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • Y Compressor contactor
  • C 24VAC common [3]
  • O/B Changeover valve [7]
  • G Fan relay

2H/1C Heat Pump System (TH5220D only) [8]Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 10

  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • Y Compressor contactor
  • C 24VAC common [3]
  • O/B Changeover valve [7]
  • G Fan relay
  • Aux/E Auxiliary/Emergency heat relay
  • L Sends output when set to Em. Heat [11]

2H/1C Heat Pump System (TH5320U only) [8]Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 10

  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • Y Compressor contactor
  • C 24VAC common [3]
  • O/B Changeover valve [7]
  • G Fan relay
  • Aux/E Auxiliary/Emergency heat relay
  • L Sends output when set to Em. Heat [11]

2H/2C Heat Pump System (TH5320U only) [9]Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 11

  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • Y Compressor contactor (stage 1)
  • C 24VAC common [3]
  • O/B Changeover valve [7]
  • G Fan relay
  • Y2 Compressor contactor (stage 2)
  • L Sends output when set to Em. Heat [11]

3H/2C Heat Pump System (TH5320U only) [10]Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 12

  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • Y Compressor contactor (stage 1)
  • C 24VAC common [3]
  • O/B Changeover valve [7]
  • G Fan relay
  • Aux/E Auxiliary/Emergency heat relay
  • Y2 Compressor contactor (stage 2)
  • L Sends output when set to Em. Heat [11]

Thermostat mounting

  • Push excess wire back into the wall opening.
  •  Plug the wall opening with non-flammable insulation.Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 13
  •  Align the 4 tabs on the wallplate with the corresponding slots on the back of the thermostat.
  •  Push gently until the thermostat snaps in place.

Installer setup

Follow the procedure below to configure the thermostat to match the installed heating/cooling system, and customize feature operation as desired.Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 14

  •  To begin, press and hold the Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 16 and FAN buttons until the display changes.
  •  Press Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 17 t to change settings.
  •  Press NEXT to advance to next function.
  •  Press DONE to exit and save settings.Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 15

Setup function Settings & options (factory default in bold)Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 18 Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 19

Special function

Auxiliary heat control (Setup Function 26):
Comfort Setting: The thermostat will prioritize comfort over economy depending on heat pump performance, load conditions and whether the thermostat is calling for the heat pump. Raising the temperature just a few degrees will often activate the auxiliary heat.
Economy Setting: The thermostat will attempt to reach the temperature setting without activating the auxiliary heat. The thermostat will wait to activate the auxiliary heat depending on heat pump performance, load conditions and how many degrees the temperature setting is changed.

Installer system test

  •  To begin, press and hold the Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 17 buttons until the display changes.
  •  Press Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 17 to turn system on/off.
  •  Press NEXT to advance to next test
  •  Press DONE to terminate system test.Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 20

Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 21

Specifications

Temperature Ranges

  • Heat: 40° to 90°F (4.5° to 32°C)
  • Cool: 50° to 99°F (10° to 37°C)
  • Operating Ambient Temperature
  • 32° to 120°F (0° to 48.9°C)

Shipping Temperature

  • -20° to 120°F (-28.9° to 48.9°C)
  • Operating Relative Humidity
  • 5% to 90% (non-condensing)

Physical Dimensions

  • TH5220D
  • 3-9/16” H x 5-13/16” W x 1-1/2” D
  • 91 mm H x 147 mm W x 38 mm D
  • TH5220D
  • 3-7/16” H x 4-1/2” W x 1-5/16” D
  • 86 mm H x 114 mm W x 33 mm D

Electrical RatingsHoneywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 22

Customer assistance

  • For assistance with this product, please visit customer.honeywell.com.
  • Or call Honeywell Customer Care tollfree
  • at 1-800-468-1502Honeywell- FocusPRO- 5000- Series -Non-Programmable- Digital- Thermostat- 23

EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.

ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.

MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal

Automation and Control Solutions

  • Honeywell International Inc.
  • 1985 Douglas Drive North
  • Golden Valley, MN 55422
  • Honeywell Ltd
  • J2X 5K8
  • customer.honeywell.com
  • ® U.S. Registered Trademark.
  • © 2013 Honeywell International Inc.
  • 69-2698EFS—03 M.S. Rev. 07-13
  • Printed in U.S.A.