HONEYWELL EVOTOUCH CONTROLLER THERMOSTAT
Preface
This extended evotouch Installation Guide provides information about the installer functions available from the main configuration menu.
For information about the other installer functions of evotouch please refer to the printed Installation Guide supplied with evotouch
System Configuration
The System Configuration menu provides access to the Installer configuration options.
To display the System Configuration menu:
- Press MENU on the home screen for ten seconds. The following warning will be displayed:
- Press YES to continue.
The System Configuration menu will then be displayed. This provides the following options:
These are described in greater detail in the following sections.
Guided Config
Leads you through the essential steps in setting up a system. For more information see the Installation Guide.
Edit System Config
See Edit System Configuration, page 4.
Factory Reset
Resets all settings to their factory defaults. The following prompt is displayed
Press YES to continue.
Note: After a factory reset the system configuration is also lost.
Edit Zone Config
Allows you to edit the name, application, and sensor assigned to each zone. See Edit Zone Configuration, page 4.
System Parameters
Allows you to set parameters affecting the operation of the whole system. See System Parameters, page 8.
Binding and RF Test
Allows you to bind or test sensors or actuators throughout the system. See Binding and RF Test, page 9.
Edit System Configuration
Allows you to edit aspects of the system configuration. It provides the following options:
Boiler demand
Allows you to specify whether the boiler is a heat demand device:
Outdoor sensor
Allows you to specify whether there is an outdoor temperature sensor:
- To specify an outdoor sensor press OUTDOOR SENSOR.
- You will then be prompted to bind the sensor:
- When a successful response has been received press DONE.
Edit Zone Configuration
Allows you to edit the name, application, and sensor assigned to each zone. You are first prompted to specify the zone you want to edit:
Press the zone you want to edit.
The following menu shows the zone name, application, and sensor currently assigned to the zone:
From this screen, you have the following options
- To do this Do this
- Edit the zone name Press the button opposite the Zone Name label
- Change the application Press the button opposite the Application label
- Change the sensor Press the button opposite the Sensor label
- Edit the application settings Press NEXT
These options are described in greater detail in the following sections.
To edit the zone name
- Press the button opposite the Zone Name label.
- Edit the name as required and press DONE
To change the application
- Press the button opposite the Application label.
The following menu allows you to choose the application
The currently selected application for the zone is shown highlighted.
- Press the appropriate application button.
The options are as follows:
Option Description
- Underfloor heating using an HCE80(R) or HCC80(R) controller.
- Radiator heating Radiator control using an HR80 radiator controller.
- Mixing valve control using an HM80.
- Zone valves Zone valve control using an HC60NG or BDR90
You will then be prompted to bind the appropriate actuator:
Once the actuator has been successfully bound you are returned to the Zoning Configuration screen.
To change the sensor for the zone
- Press the button opposite the Sensor label. The following screen shows the currently selected sensor type:
- Press the INTERNAL DEVICE SENSOR to use the internal temperature sensor in evotouch, in the zone where evotouch is situated, or EXTRA REMOTE SENSOR to use a remote sensor.
Note: Only one zone can be controlled by the internal sensor. Selecting the internal sensor automatically configures all other zones to use external sensors.
The following screen is then displayed
- Press DEVICE SENSOR INFORMATION to use the sensor for information only, or DISTRIBUTE SENSOR INFORMATION to distribute the information to all actuators in the zone.
- To edit the application settings
Press NEXT on the Zoning Configuration screen.
The following screen is then displayed:
- Press APPLICATION SETTING.
- The settings available for each of the applications are described on the following pages.
Underfloor heating setting
The following setting is available for the Underfloor Heating application:
Min. Max. Setpoint
This specifies the minimum and maximum temperature that can be requested for the zone:
- Min. Max. Setpoint
This specifies the minimum and maximum temperature that can be requested for the zone:
Radiator heating settings
The following settings are available for the Radiator Heating application:
Optimization setting
medication calculation locally using the desired set point, measured temperature, and comfort schedule:
Window function
Enables the function built into the HR80 that detects when a window is open (by measuring a drastic drop in temperature) and automatically closes the radiator valve for a certain time for energy saving:
Min. Max. Setpoint
See Min. Max. Setpoint, on this page.
Local override
Allows the setpoint to be changed at the HR80. This is valid until the next switching point:
Mixing valve settings
The following settings are available for the Mixing Valve application:
Pump run time
Pump Run time (or pump overrun) specifies how long the pump in the heat source needs to keep running to extract all the heat to avoid blocking the heat source:
Actuator running time
Specifies the amount of time to open/close the actuator, in the range 0 to 100%.
Min flow temp, Max flow temp
The min/max flow temperature limits to control the flow temperature to achieve the target room temperature setpoint and protect the heating system
Min. Max. Setpoint
See Min. Max. Setpoint, page 6.
Zone valves options
The following options are available for the Zone Valves application:
Fail-safe
Specifies that the HC60NG/BDR90 output relay should switch OFF if the RF communication is lost:
Min. Max. Setpoint
See Min. Max. Setpoint, page 6
System Parameters
Allows you to set parameters affecting the operation of the whole system:
Cycle rate
Specifies how often the boiler will switch on and off in any given hour. measured as cycles per hour. A typical cycle rate is 6 cycles per hour, giving a 10-minute cycle length.
Off temperature
Specifies the temperature that the system will revert to when the system is turned off, for frost protection
Holiday temperature
Specifies the temperature set throughout all zones when the user selects Holiday mode:
Internal sensor offset
Specifies the offset of the internal sensor temperature, when the unit is placed in a location where the measurement needs to be corrected:
Holiday temperature
Specifies the temperature set throughout all zones when the user selects Holiday mode:
Min. boiler on time
Specifies a minimum time for the heat source, to ensure all the heat is dissipated from the system before shutting off.
Binding and RF Test
Allows you to bind or test sensors or actuators throughout the system:
Binding will normally be performed with evotouch positioned beside the actuator or sensor, for convenience.
RF Test is then used to check the communication performance of all devices in their correct locations.
Heat Demand
Binds to the heat demand device:
Zone Binding
You are first prompted to specify the zone to bind:
You will then be prompted to bind one representative sensor and one or more actuators to the selected zone.
Outdoor Sensor
Binds to the outdoor sensor:
RF Test Heat Demand
Tests the boiler heat demand
RF Test Zones
You are first prompted to specify the zone to test:
You will then be prompted to perform an RF test to the selected zone.
RF Test Outdoor
Tests RF communication with the outdoor sensor.
Safety information
Approvals
Conforms to protection requirements of the following directives:
- EMC: 2004/108/EC
- LVD: 2006/95/EC
- R&TTE: 1995/5/EC
EMC compliance considerations
Refer to Code of Practice standards EN61000-5-1 and -2 for guidance.
Caution: Isolate the power supply and make it safe before wiring the unit to prevent electric shock and equipment damage. Installation should be carried out by a competent person.
Product handling
Care should be taken with the evotouch unit while it is out of its dock or table-top to stand as the unit, particularly the touchscreen the display may be damaged if the unit is dropped onto a hard surface.
Location of device
evotouch should be placed in an open space for best performance as it is a radio frequency device. Leave at least 30cm distance from any metal objects including wall boxes and at least 1 meter from any other electrical equipment eg. radio, TV, PC, etc. Do not mount onto metal wall boxes. For the best temperature control performance evotouch should not be placed near heat or cool sources (e.g. cooker, lamp, radiator, doorways, and windows).
Disclaimer
This product and its associated documentation and packaging are protected by various intellectual property rights belonging to Honeywell Inc and its subsidiaries existing under the laws of the UK and other countries. These intellectual property rights may include patent applications, registered designs, unregistered designs, registered trademarks, unregistered trade marks, and copyrights.
Honeywell reserves the right to modify this document, product, and functionality without notice. This document replaces any previously issued instructions and is only applicable to the product(s) described.
This product has been designed for applications as described within this document. For use outside of the scope as described herein, refer to Honeywell for guidance. Honeywell cannot be held responsible for the misapplication or the product(s) described within this document.
PLEASE RESPECT YOUR ENVIRONMENT!
Take care to dispose of this product and any packaging or
literature in an appropriate way
WEEE directive 2002/96/EC
Waste Electrical and Electronic
Equipment directive
- At the end of the product, life disposes of the packaging and product in a corresponding recycling center.
- Do not dispose of the unit with the usual domestic refuse.
- Do not burn the product.
- Remove the batteries.
- Dispose of the batteries according to the local statutory requirements and not with the usual domestic refuse. Manufactured for and on behalf of the
Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, ACS-ECC EMEA, Z.A. La Pièce 16, 1180 Rolle, Switzerland by its Authorised Representative Honeywell Inc.
Honeywell Control Systems Ltd. Arlington Business Park,
Bracknell, Berkshire RG12 1EB
Technical Help Desk: 08457 678999 50042752-001 B
© 2009 Honeywell International Inc.
www.honeywelluk.com
Reference
Download Manual:
HONEYWELL EVOTOUCH CONTROLLER THERMOSTAT Installation Manual
HONEYWELL EVOTOUCH CONTROLLER THERMOSTAT Installation Manual
Leave a Reply