Honeywell

Honeywell CT50A Thermostat

Honeywell-CT50A-Thermostat-User-Manual-PRODUCT

YOUR HONEYWELL THERMOSTAT

Your new Honeywell CT50A heating Thermostat will replace most 15 to 30 V, 2-wire heating system thermostats. The CT50A is suitable only for gas or oil heating systems (NOT for heating/cooling, heat pumps, or electric heating systems). Your new Honeywell CT51A heating/Cooling Thermostat will replace most 15 to 30 V, 4-wire, heating/cooling system thermostats. The CT51A is suitable only for gas or oil heating/cooling or electric cooling systems (NOT for heat pumps or electric heating systems). Your new Honeywell CT52A heating Thermostat will replace most 15 to 30 V. 4-wire electric heating system thermostats (NOT for cooling, heating cooling, heat pump, gas or oil systems). Your new Honeywell CT53A heating Thermostat is suitable for 250, 500, or 750 mV heating systems only.

THERMOSTAT FEATURES

Honeywell-CT50A-Thermostat-User-Manual-FIG-4

REMOVING OLD THERM0STAT

WIRE AND MOUNT THERMOSTAT

Honeywell-CT50A-Thermostat-User-Manual-FIG-6

CHECK OUT THE THERMOSTAT

THERMOSTAT SETTING

On CTS1A, place the system and fan switches at the desired settings for operation. On all models, move the temperature setting lever to the desired temperature comfort level.

TROUBLESHOOTING

Our Honeywell thermostat requires little or no attention. Most problems can generally be traced to the folowing:
NOTE f your system is heating-only or cooling-only, disregard sections not applicable to your system.

SYMPTOM PROBLEM CORRECTIVE ACTION
No heat System switch at OFF or

COOL Position.

Move switch to HEAT position.
Blown fuse or tripped circuit breaker. Replace fuse or reset circuit breaker.
Furnace power switch is on OFF. Switch to ON.
No pilot fla1T1e. Religtil pilot rlame per furnace manufacture r’s instructions.
Improper connections to thermostat. With Power to furnace OFF, tighten all mounting and terminal screws. Re­ pair broken wires.
Defective thermostat. (Here’s how you tell: Turn power to furnace OFF. Then remove the thermo­ stat from the wall. Dis­ connect wire from W termina\. Tum power to furnace ON. Touch W wire to R terminal. The thermostat is defective if the burner comes on.) Exchange the thermostat (see Warranty).
Other. Contact service technician for assistance .
Furnace turns on and ott Burner-on period is too sho Remove the thermostat cover and move the heat antici pator lever GOU N­ TERCLOCKWISE \ 7

one scale mark. Wait at least several hours to sta­ bilize.

Major swings in 1emp e rat u re (greater than 2 F [1.1 C] when out- side tern perature stable). Burner – on is too long. period Remove the thermostat cover and move the heat anticipator lever CLOCK­ WISE  1′:.  one scale mark. Wait several hours for the system to stabilize.
SYMPTOM PROBLEM CORRECTIVE ACTION
Thermostat setting and thermometer reading disagree, Thermostat is not level. Recheck the thermostat position on wall. Use a bubble level to make sure it’s level. See step 4,
Thermostat affected by drafis or radiant heat. Contact service technician to change u-,e location. The thermostat should be about

5 ft [1.5 m] above the floor and on an inside wall.

Thermostat is out of cali­ bration. Contact a qualified service technician to recalibrate tt,e thermostat.
Thermometer is out of calibration. Recalibrate. See step 8.
No cooling. System switch in in OFF or HEAT position. Move switch to C 00 L position .
Blown tu se or tripped circuit breaker. Replace fuse or reset circuit breaker.
Condenser switch (lo- cated outdoors) is turned OFF.

Improper connections to thermostat.

Move switch to ON posi­ tion.

 

VVith power to furnace OFF, tighten all mounting and terminal screws. Re­ pair broken wires .

Detective thermostat. (Here’s how you tell: Turn power to cooling system OFF. Then remove the thermostat from wall. Disconnect wire from Y terminal. Turn power to cooling system ON. Touch Y wire to terminal

R. The thermostat is de­ fective if the compressor starts Some systems have a ti me delay, so allow at least 2-3 minutes.)

Exchange the thermostat. See Warranty.
Other. Contact service techni­

cian for assistance.

RECALIBRATE THERMOMETER

Honeywell-CT50A-Thermostat-User-Manual-FIG-11

If the thermostat set point and the thermometer reading do not agree, the thermometer may need recalibration. Follow the procedure below.

Reference:

Download Manual:

Honeywell CT50A Thermostat User Manual

Honeywell

Honeywell CT50A Thermostat User Manual

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)