Honeywell logo

Honeywell PRO TH3210D PROGRAMMABLE THERMOSTAT

Honeywell PRO TH3210D PROGRAMMABLE THERMOSTAT

Product Application

This thermostat provides electronic control of 24 VAC heat pump systems with auxiliary heat (2 heat/1 cool).

Power Type

System Settings

Fan Settings

Must be installed by a trained, experienced technician

CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.

MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.

Installation tips

Hive SLT1 smart link Thermostat fig-1

Do not install in locations where the thermostat can be affected by:

Pre-installation checklist

Package contents
Check to make sure your package includes the following items:

Required tools & supplies

Wallplate installation

Hive SLT1 smart link Thermostat fig-2

Remove the wallplate from the thermostat as shown at the left, then follow the directions below for mounting.

  1. Pull wires through wire hole.
  2. Position the wallplate on the wall, level, and mark hole positions with a pencil.
  3. Drill holes at marked positions as shown below, then tap in supplied wall anchors.
  4. Place wallplate over anchors, insert and tighten mounting screws. Hive SLT1 smart link Thermostat fig-3

Wiring

CAUTION: ELECTRICAL HAZARD. Can cause electrical shock or equipment damage. Disconnect power before wiring. Hive SLT1 smart link Thermostat fig-4

Wiring

  1. Loosen screw terminals, insert wires into the terminal block, then re-tighten the screws.
  2. Push excess wire back into the wall opening. Keep wires in a shaded area as shown at left.
  3. Plug the wall opening with non-flammable insulation to prevent drafts from affecting thermostat operation.

NOTES

Terminal Designations

Wiring diagram

  1. Power supply. Provide disconnect means and overload protection as required.
  2. Optional 24 VAC common connection.
  3. Use either O or B terminals for the changeover valve.
  4. L terminal is powered continuously when the thermostat is set to Em Heat.
  5. Install field jumper between E and Aux if there is no emergency heat relay.

Hive SLT1 smart link Thermostat fig-5

Power options & mounting

AC Power
The thermostat can be powered by 24 VAC power, or by batteries.
To wire the thermostat for AC power, connect the common side of the transformer to the “C” terminal as shown at left. Hive SLT1 smart link Thermostat fig-6

Battery Power
The thermostat can be powered by batteries alone or, if used with AC power, can provide backup power to the display during power interruptions. Hive SLT1 smart link Thermostat fig-7

To Mount Thermostat
Align the 4 tabs on the wallplate with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place. Hive SLT1 smart link Thermostat fig-8

Installer setup

Follow the procedure below to configure the thermostat to match the installed heating/cooling system, and customize feature operation as desired.Hive SLT1 smart link Thermostat fig-9

Setup Function

Installer system test

After completing the installer setup above, pressHive SLT1 smart link Thermostat fig-16 the button again to begin a system test (see next page).

Follow the procedure below to test the heating and cooling system.Hive SLT1 smart link Thermostat fig-10

  1. Set SSYYSSTTEEMM switch to Heat.
  2. PressHive SLT1 smart link Thermostat fig-11 to turn on and check systems (see table, below).
  3. PressHive SLT1 smart link Thermostat fig-11 until the systems turn off.
  4. Set SSYYSSTTEEMM switch to Em Heat and repeat steps 2-3 above. 5 Set SSYYSSTTEEMM switch to Cool and repeat steps 2-3 above.
  5. Press and holdHive SLT1 smart link Thermostat fig-12 to terminate test at any time.
10 System Test

Heating system

0 System Status 

The compressor and fan turn off.

1 The compressor and fan turn on.
2 Auxiliary heat turns on.
20 Emergency heat 0 Heat and fan turn off.
1 Heat and fan turn on.
2 Auxiliary heat turns on.
30 Cooling system 0 The compressor and fan turn off.
1 The compressor and fan turn on.
70 Thermostat 71 Software revision number (major revisions)
information 72 Software revision number (minor revisions)
(for reference only) 73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)

CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection (minimum off time) is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.

A quick reference to controls

Digital display screen Hive SLT1 smart link Thermostat fig-13

Quick reference to display screen

Hive SLT1 smart link Thermostat fig-14

Built-in compressor protection (Setup Function 15)

Hive SLT1 smart link Thermostat fig-15

This feature helps prevent damage to the compressor.
Damage can occur if the compressor is re-started too soon after shutdown.This feature forces the compressor to wait for a few minutes before restarting.
During the wait time, the message Cool On or Heat On will flash on the display. When the safe wait time has elapsed, the message stops flashing and the compressor turns on.

In case of difficulty

If you have difficulty with your thermostat, please try the suggestions below. Most problems can be corrected quickly and easily.

Accessories

Please contact your distributor to order accessories.

Specifications

Electrical Ratings

Hive SLT1 smart link Thermostat fig-17

 

 

 

 

 

Hive SLT1 smart link Thermostat fig-17
Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée 35 Dynamic Drive
Scarborough, Ontario M1V 4Z9
http://yourhome.honeywell.com 

Reference

Download Manual:

Honeywell PRO TH3210D PROGRAMMABLE THERMOSTAT Operating Manual

 

Honeywell logo

Honeywell PRO TH3210D PROGRAMMABLE THERMOSTAT Operating Manual

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)