Honeywell logo

Honeywell Home TH6320ZW2003/U Z-Wave Digital Programmable Thermostat

 

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-product

Package Includes

Compatibility

Customer assistance
For assistance with this product, please visit customer.resideo.com.
Or call Resideo Customer Care toll-free at 1-800-468-1502.

Read and save these instructions.

Introduction

The T6 Pro Z-Wave Programmable Thermostat is a Z-Wave Plus certified thermostat capable of controlling up to three heat and two cool stages of heat pump, (incl. dual fuel heat pump systems) and up to two heat and two cool stages of the conventional system (3H/2C HP, 2H/2C Conv.) It also measures, displays, and reports % indoor relative humidity; however, this model does not control humidification equipment. It is one of the easiest smart thermostats to install and is controllable by all Z-Wave-compliant controllers that have the control capability for “Thermostat” devices. When integrated with the app that controls your Z-Wave controller, it lets you program and control your home’s HVAC system as well as control other Z-Wave
devices connected to the same Z-Wave controller. Because the thermostat is battery-powered, low-voltage integrators can easily connect the thermostat to most HVAC systems. Optional 24 VAC powering via “C” or a common wire is also available, if desired.

CAUTION

UWP Mounting System Installation

 

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-1

  1. Open the package to find the UWP. See Figure 1.
  2. Position the UWP on the wall. Level and mark hole positions. See Figure 2. Drill holes at marked positions, and then lightly tap supplied wall anchors into the wall using a hammer.
    ‒ If your box contains red anchors, drill 7/32” holes for drywall. If your box contains yellow anchors, drill 3/16” holes for drywall.
  3. Pull the door open and insert wires through the wiring hole of the UWP. See Figure 3.
  4. Place the UWP over the wall anchors. Insert and tighten mounting screws supplied with the UWP. Do not over-tighten. Tighten until the UWP no longer moves. Close the door. See Figure 4.

Optional Decorative Cover Plate Installation

 

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-2

Use the Optional Cover Plate when you need to cover the paint gap from the old thermostat. There are different cover plates depending on when the thermostat was manufactured. One plate is square, the other is rectangular.

  1. If the square mounting plate is used, separate the cover plate from the mounting plate. See Figure 1.
  2. Mount the mounting plate to the wall using any of the screw holes. Insert and tighten the mounting screws supplied with the cover plate. Do not over-tighten. Make sure the mounting plate is level. See Figure 2a (square) or 2b (rectangle).
  3. Attach the UWP by hanging it on the top hook of the mounting plate and then snapping the bottom of the UWP in place. See Figure 3.
  4. Snap the Cover Plate onto the mounting plate. See Figure 4.

For the rectangular cover plate

  1. Mount the cover plate on the wall using any of the 6 screw holes. Insert and tighten the mounting screws supplied with the Cover Plate. Do not over-tighten. See Figure 1. Make
    sure the Cover Plate is level. Attach the UWP by hanging it on the top hook of the Cover Plate and then snap the bottom of the UWP in place. See Figure 2.
  2. f there are no existing wall anchors:
    • Position the Cover Plate on the wall. Level and mark hole positions. See Figure 1.
    • Drill holes at marked positions, and then lightly tap supplied wall anchors into the wall using a hammer.
    • if your box contains red anchors, drill 7/32” (5.6 mm) holes.
    • if your box contains yellow anchors, drill 3/16” (4.8 mm) holes.
    • Use 2x supplied screws (#8 1 1/2” (38 mm) for red anchors and #6 1 1/2” (38 mm) for yellow anchors).

Power options

 

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-3

NOTES

Wiring UWP
Push down on the tabs to put the wires into the inner holes of their corresponding terminals on the UWP (one wire per terminal) until they are firmly in place. Gently tug on the wires to verify they are secure. If you need to release the wires again, push down the terminal tabs on the sides of the UWP.

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-4

Setting Slider Tabs

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-5

NOTE: Slider Tabs for U terminals should be left in place for other thermostat models. Setting Slider Tabs

Wiring terminal designations

 

S

 

Input for wired indoor or outdoor sensors

S
 

Y

Compressor contactor (stage 1)
Y2 Compressor contactor (stage 2)
G Fan Relay
 

C

24 VAC common.

For 2 transformer systems, use common wire from cooling transformer.

U  

Unused

U
L/A

– A

Heat Pump fault input (C wire required)
O/B Changeover valve
AUX – W2 Auxiliary heat relay Heat relay (stage 2)
E Emergency Heat relay
W Heat relay (stage 1)
 

K

 

Connect to K on C-wire adapter**

R 24 VAC power from heating transformer*
Rc 24 VAC power from cooling transformer*

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-6

Note: Not all terminals may be used, depending on the system type that is being wired. The most commonly used terminals are shaded.

A terminal can be jumped using Slider Tab. See “Setting Slider Tabs” above. The THP9045A1098 C-wire adapter is used on heat/cool systems when you only have four wires at the thermostat and you need a fifth wire for a common wire. Use the K terminal in place of the Y and G terminals on conventional or heat pump systems to provide control of the fan and the compressor through a single wire—the unused wire then becomes your common wire. See THP9045 instructions for more information.

Wiring conventional systems: forced air and Hydronics

1H/1C System (1 transformer)

Heat-only System

Heat-only  System  (Series  20) [5]

Heat-only System

1H/1C System (2 transformers)

Heat-only System with Fan

Cool-only System

2H/2C System (1 transformer) [6]

NOTES:

Wiring heat pump systems

2H/1C Heat Pump System [8]

Aux Auxiliary heat [4]

2H/2C Heat Pump System [6]

O/B Changeover valve [7] G      Fan relay

Aux Auxiliary heat [4]

Dual Fuel System

Aux Auxiliary heat [4]

NOTES:

Mounting thermostat

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-8

  1. Push excess wire back into the wall
  2. Close the UWP door. It should remain closed without
  3. Align the UWP with the thermostat, and push gently until the thermostat snaps in
  4. If needed, gently pull to remove the thermostat from the
  5. Turn the power on at the breaker.

Initial installer setup

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-9

NOTES

Z-Wave setup

 

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-12

After you finish the installer setup and set the date and time, you will be asked to set up a Z-Wave to include the thermostat in the Z-Wave network.

NOTES

Advanced Z-Wave temperature reporting

This thermostat may be configured to report the actual room temperature in a higher resolution than can be shown on the thermostat display. The default temperature reporting resolution is 1 °F or 0.5 °C. When configured to ADVANCED, the temperature reporting resolution will be 0.5 °F or 0.25 °C. To change default temperature reporting to a higher resolution, go to thermostat MENU/Z-WAVE SETUP/TEMP REPORT and set to ADVANCED. The temperature is reported by every displayed value change, and no later than 2 hours from the last report.
NOTE: When higher temperature resolution reporting is set, you may experience different resolutions of temperature displayed on the thermostat and Z-Wave controller.

Z-Wave connection status

The Z-Wave connection status is located in the upper-right corner of the screen.

System operation setting

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-16

  1. Press the Mode button to cycle to the next available System mode.
  2. Cycle through the modes until the required System mode is displayed and leave it to activate.

System modes

NOTES

Fan operation setting

  1. Press the Fan button to cycle to the next available Fan mode.
  2. Cycle through the modes until the required Fan mode is displayed and leaves it to activate.

NOTE: Available Fan modes vary with the system settings.
Fan modes:

Scheduling options

This thermostat may be configured to be programmable or nonprogrammable. The thermostat schedule is an optional menu item. It will only show up in the thermostat menu if enabled in the Installer setup – advanced menu. It provides the setting for local thermostat schedule control. Once the thermostat is included in the Z-Wave network, it assumes to be programmed from your Z-Wave controller and the program schedule on the thermostat is turned OFF by default. Use just the controller or associated app to program the schedule (automation scenes) for the thermostat.

See the table below with default, adjustable settings:

The thermostat schedule is turned OFF, the thermostat is included in Z-Wave network
Period Start Time Heat Cool
Away N/A* 62 ° 85 °
Home N/A* 72 ° 78 °

Triggered by Z-Wave controller

 

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-19

Enabling thermostat schedule when the thermostat is included in the Z-Wave network (optional):
Z-Wave controllers from various manufacturers may or may not support the Z-Wave Thermostat General V2 Device class used by the T6 pro-Z-Wave Thermostat. If your controller does not support full thermostat device class functions, it may still be able to control basic Home/ Away (Energy Saving) modes of the thermostat through BASIC_SET commands (ON/OFF) used by the controller for other Z-Wave devices (eg. lighting devices). When only basic commands are capable to receive from the controller, you can enable the local thermostat schedule to differentiate between temperatures when you are away and when you are at home to differentiate between home and sleep temperatures.

See table below with default 5+2 schedule (Mon-Fri; Sat-Sun), adjustable settings:

Thermostat schedule is turned ON, thermostat included in Z-Wave network
Period Start Time Heat (Mon-Fri) Cool (Mon-Fri) Heat (Sat-Sun) Cool (Sat-Sun)
Away N/A* 62 ° 85 ° 62 ° 85 °
Home 6:00 Am 70 ° 78 ° 70 ° 78 °
Sleep 10:00 Pm 62 ° 85 ° 62 ° 85 °

Triggered by Z-Wave controller

 

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-20

Program schedule on the thermostat when not included in the Z-Wave network (not operated by Z-Wave controller):
The T6 Pro Z-Wave thermostat will function as a fully programmable thermostat when not operated by your controller. Each day can be programmed for different heating and cooling setpoints in 4 unique periods (Wake, Away, Home, Sleep) in the thermostat MENU/SCHEDULE. Make sure that the thermostat schedule is enabled in INSTALLER SETUP – ADVANCED (see pages 14, 15), ISU 120 – Schedule type. See table below with default 5+2 schedule (Mon-Fri; Sat-Sun), adjustable settings:

Thermostat schedule is turned ON, thermostat excluded from Z-Wave network
Period Start Time Heat (Mon-Fri) Cool (Mon-Fri) Heat (Sat-Sun) Cool (Sat-Sun)
Wake 6:00 am 70 ° 78 ° 70 ° 78 °
Away 8:00 am 62 ° 85 ° 62 ° 85 °
Home 6:00 Pm 70 ° 78 ° 70 ° 78 °
Sleep 10:00 Pm 62 ° 85 ° 62 ° 85 °

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-21

Key features

 

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-22

The screen will wake up by pressing the center area of the displayed temperature. If powered by 24 VAC, the screen stays lit for 45 seconds after you complete changes. If powered by battery only, the screen stays lit for 8 seconds. The brightness of an inactive backlight can be if the thermostat is powered by 24 VAC.

Installer setup – advanced menu
To access the advanced menu, press and hold the Menu button for 5 seconds. Touch or to go through the options in the advanced menu.

 

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-23

Advanced menu options

Device Setup
This is used to access the device’s ISU setting.

Screen Lock
The thermostat touchscreen can be locked fully or partially.

System Test
Test the heating and cooling system.

Reset
Access all reset options on the thermostat. This is the only place to access factory reset.

Range Stop (Temperature)
Set the Minimum Cool and Maximum Heat temperature set points

Installer setup options (ISU) – advanced menu

# ISU ISU Name ISU Options (defaults in bold) Notes
120 Schedule Type No Schedule or Occupancy (when included in Z-Wave network) MO-SU = Every day the same

MO-FR, SA, SU = 5-1-1 schedule MO-FR, SA-SU = 5-2 schedule Each Day = Every day individual

You can change default MO-FR, SA-SU schedule here. To edit periods during days, temperature setpoints, or to turn Schedule On/Off, go to MENU/SCHEDULE (only available if schedule is set).
125 Temp Scale Fahrenheit, Celsius
130 Outdoor Temp No, Wired An outdoor temperature is required to set the following ISUs: ISU 355 Balance point (Compressor Lockout), ISU 356 Aux Heat Lockout. Use a wired outdoor sensor connected to the “S” terminals on the UWP and set this ISU to Wired. (“Wiring heat pump systems” on page 7.)
200 System Type Conventional Forced Air

Heat Pump Boiler

Cool Only

Basic selection of system your thermostat will control.
205 Equipment Type Conventional Forced Air Heat:

Standard Efficiency Gas (STD GAS), High Efficiency Gas (EFF GAS), Oil, Electric, Hot Water Fan Coil

This option selects the equipment type your thermostat will control. Note: This option is NOT displayed if ISU 200 is set to Cool Only.
Heat Pump:

Air To Air, Geothermal

Boiler:

Hot Water Radiant Heat, Steam

218 Reversing Valve 0/B on Cool, 0/B on Heat This ISU is only displayed if ISU 200 is set to Heat Pump. Select whether reversing valve O/B should energize on cool or on heat.
220 Cool Stages (#200=Conv./ 200=HP) 0, 1, 2
221 Heat Stages; Aux/E Stages (#200=Conv.; 200=HP) Heat Stages: 0, 1, 2

AUX/E Stages: 0, 1

Maximum of 2 Heat Stages for conventional systems. Maximum of 1 Aux/E stages for heat pump systems.
230 Fan Control Equipment, Thermostat This ISU is only displayed if ISU 205 is set to Electric Forced Air or Fan Coil.
253 Aux/E Control Both Aux/E, Either Aux/E Set “EITHER AUX/E” if you want to setup and control of Auxiliary and Emergency heating separately . This ISU is only displayed if ISU 200 is set to Heat Pump AND if ISU 221 Aux/E stages = 1.
255 Aux Heat Type Electric, Gas/Oil (or Fossil Forced Air) This ISU is displayed only if ISU 200 is set to heat pump AND if ISU 221 Aux/E heat stages = 1.
# ISU ISU Name ISU Options (defaults in bold) Notes
256 EM Heat Type Electric, Gas/Oil (or Fossil Forced Air) This ISU is displayed only if ISU 200 is set to Heat Pump AND if ISU 221 Aux/E heat stages = 1 AND if ISU 253 is set to run AUX/E heat separately.
260 Fossil Kit Control Thermostat, External (Fossil Fuel Kit Controls Backup Heat) This ISU is displayed only if ISU 200 is set to Heat Pump AND if ISU 221 Aux/E heat stages = 1, AND if ISU 256 is set to Gas/Oil.
300 Auto Changeover On, Off

Default setting varies depending on manufacture date

OFF: The user must select heating or cooling as needed to maintain the desired indoor temperature.

ON (Automatic): On (enabled) Allows user to select Auto Changeover as one of the system modes from the home screen. In auto mode, the thermostat control either heating or cooling automatically to maintain the desired indoor temperature.

303 Auto Differential 0 °F to 5 °F or 0.0 °C to 2.5 °C

Default setting varies depending on manufacture date

Differential is NOT deadband. Resideo uses an advanced algorithm that fixes deadband at 0 °F. The differential setting is the minimum number of degrees from set-point needed to switch from the last mode running (heat or cool) to the opposite mode when the thermostat is in auto-changeover. This is more advanced than previous thermostats.
305 High Cool Stage Finish Yes, No This ISU is only displayed when the thermostat is set to 2 cool stages. When set to YES, this feature keeps the higher stage of the cooling equipment running until the desired setpoint is reached.
306 High Heat Stage Finish Yes, No This ISU is only displayed when the thermostat is set to 2 or more heat stages. When set to YES, this feature keeps the higher stage of the heating equipment running until the desired setpoint is reached.
340 Aux Heat Droop 0 = Comfort; 2 °F to 15 °F from setpoint (in 1 °F increments) or 1.0 °C to 7.5 °C from setpoint (in 0.5 °C increments) Aux heat droop can be set on heat pump systems with an auxiliary heat stage. The Comfort setting is NOT available for Dual Fuel systems. Default setting is 0 °F (Comfort) for Electric while 2 °F for Gas/Oil. The indoor temperature must drop to the selected droop setting before the thermostat will turn Aux Heat on. For example, if Aux Heat is set to 2 °F (1.0 °C), the indoor temperature must be 2 ° F (1.0 ° C) away from the setpoint before Aux Heat turns on. When set to Comfort, the thermostat will use Aux Heat as needed to keep the indoor tem- perature within 1 °F (0.5 ° C) degree of the setpoint.
350 Up Stage Timer Aux Heat Off, 30, 45, 60, 75, 90 minutes

2, 3, 4, 5, 6, 8, 10, 12, 14, 16 hours

The Auxiliary Heat Upstage Timer starts when the highest stage of the previous heating equipment type turns on. Auxiliary heat will be used (if needed) when the timer expires. This ISU is only displayed when ISU 340 (AUX Heat Droop) is set to 2 °F or higher.
355 Balance Point (Compressor Lockout) Off, 5 °F to 60 °F (in 5 °F increments) or 15.0 °C to 15.5 °C (in 2.5 °C or 3.0 °C increments) Compressor Lockout requires an outdoor temperature. Set Compressor Lockout to the temperature below which it is inefficient to run the heat pump. When outside temperature is below this setting, thermostat will lockout the heat pump and run Aux Heat only. This ISU is only displayed if ISU 130 = Wired, ISU 200 is set to Heat Pump, ISU 221 Aux/E stages = 1. Default is 40 °F if ISU 205 Heating Equipment is Air to Air Heat Pump and ISU 255 Aux Heat Type is Gas/Oil. Default is Off if ISU 205 Heating Equipment is Air to Air Heat Pump and ISU 255 Aux Heat Type is Electric. Default is Off if ISU 205 Heating Equipment is Geothermal. Compressor Lockout is optional for any type of heat pump (Air to Air Heat Pump, Geothermal Heat Pump).
356 Aux Heat Lock Out (Aux Heat Outdoor Lockout) Off, 5 °F to 65 °F (in 5 °F increments) or

-15.0 °C to 18.5 °C (in 2.5 °C or 3.0 °C increments)

Aux Heat Lockout requires an outdoor temperature. Set Aux Heat Lockout to optimize energy bills and to not allow to run the more expensive Aux Heat source above certain outdoor temperature limit. This ISU is only displayed if ISU 130 = Wired, ISU 200 is set to Heat Pump, ISU 221 Aux/E stages = 1.
# ISU ISU Name ISU Options (defaults in bold) Notes
365 Cool 1 CPH (Cooling cycle rate stage 1) 1 – 6 CPH (3 CPH) This ISU is only displayed when Cool /Compressor Stages is set to 1 or more stages. Cycle rate limits the maxi- mum number of times the system can cycle in a 1 hour period measured at a 50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle 3 times per hour (10 minutes on, 10 minutes off). The system cycles less often when load conditions are less than or greater than a 50% load.
366 Cool 2 CPH (Cooling cycle rate stage 2) 1 – 6 CPH (3 CPH) This ISU is only displayed when Cool /Compressor Stages is set to 2.
370 Heat 1 CPH (Heating cycle rate stage 1) 1 – 12 CPH This ISU is only displayed when Heat Stages is set to 1 stage or more stages. Cycle rate limits the maximum number of times the system can cycle in a 1 hour period measured at a 50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is 3 times per hour (10 minutes on, 10 minutes off). The system cycles less often when load conditions are less than or greater than a 50% load. The recommended (default) cycle rate settings are below for each heating equipment type:

Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil Forced Air =

5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 3 CPH; Hot Water Radiant Heat = 3 CPH; Steam = 1 CPH.

371 Heat 2 CPH (Heating cycle rate stage 2) 1 – 12 CPH This ISU is only displayed when Heat Stages is set to 2 stages. The recommended (default) cycle rate settings are below for each heating equipment type:

Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil Forced Air =

5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 3 CPH; Hot Water Radiant Heat = 3 CPH; Steam = 1 CPH.

375 Aux Heat CPH (Heating cycle rate Auxiliary Heat) 1 – 12 CPH This ISU is only displayed when ISU 200 = Heat Pump and ISU 221=1. It is only displayed when Auxiliary Heat is configured. The recommended cycle rate settings are below for each heating equipment type:

Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH

378 EM Heat CPH (Heating cycle rate Emergency Heat) 1 – 12 CPH This ISU is only displayed when Emergency Heat is configured and ISU 253: Aux/E Terminal Control is set to control Aux and E heat Independently. The recommended cycle rate settings are below for each heating equip- ment type:

Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH.

387 Compressor Protection Off, 1 – 5 minutes The thermostat has a built in compressor protection (minimum off timer) that prevents the compressor from restarting too early after a shutdown. The minimum-off timer is activated after the compressor turns off. If there is a call during the minimum-off timer, the thermostat shows “Cool on” or “Heat On” (heat pump) status blinking on the thermostat home screen. This ISU is displayed if ISU 220 is set to at least 1 stage.
390 Ext Fan Run Time in Cool Off, 30, 60, 90 seconds

2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15 minutes

After the call for cooling ends, the thermostat keeps the fan on for the selected amount of time for increased efficiency. This may reintroduce humidity into the living space. This ISU is displayed if ISU 220 is set to at least 1 stage.
391 Ext Fan Run Time in Heat Off, 30, 60, 90 seconds

2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15 minutes

After the call for heating ends, the thermostat keeps the fan on for the selected amount of time for increased efficiency. This ISU is displayed if ISU 230 is set to Thermostat Controls Fan.
# ISU ISU Name ISU Options (defaults in bold) Notes
425 Adaptive Recovery On, Off Adaptive Intelligent Recovery (AIR) is a comfort setting. Heating or cooling equipment will turn on earlier, ensuring the indoor temperature will match the setpoint at the scheduled time.
430 Minimum Cool Setpoint 50 °F to 99 °F (50 °F); 10.0 °C to 37.0 °C (10.0 °C) The user cannot set the cooling temperature below this level.
431 Maximum Heat Setpoint 40 °F to 90 °F (90 °F); 4.5 °C to 32.0 °C (32.2 °C) The user cannot set the heating temperature above this level.
435 Lock Screen None, Partial, Full Unlocked: User has access to all thermostat settings.

Partially Locked: User can modify only temperature settings.

Fully Locked: User cannot modify any settings. Screen will be locked by default factory code and cannot be changed. This code is displayed for a short time, when you are about to lock the thermostat screen. Please note the code in safe place for future reference.

500 Indoor Sensor Yes, No Set this ISU when you want to wire a remote indoor sensor to the “S” terminals on the UWP – see “Wiring termi- nal designations” on page 5. This ISU is only displayed only if ISU 130 is set to NO wired outdoor sensor configured.
515 Sensor type 10k, 20k Choose resistance type of wired indoor sensor. This ISU is only displayed when indoor sensor is configured – ISU 500.
520 Temperature Control Thermostat, Wired, Average This ISU is only displayed when indoor sensor is configured – ISU 500. You can choose what temperature source to be used or you can ask thermostat to use both thermostat and remote sensors for higher accuracy of measurement.
702 Air Filters 0 – 2 This ISU refers to the number of air filters in the system.
711 Air Filter 1 Reminder Off

10, 20, 30, 45, 60, 90, 120, 150 Run Time Days

30, 45, 60, 75 Days

3, 4, 5, 6, 9, 12, 15 Months

Choose either calendar or equipment run time-based reminder.
712 Air Filter 2 Reminder Off

10, 20, 30, 45, 60, 90, 120, 150 Run Time Days

30, 45, 60, 75 Days

3, 4, 5, 6, 9, 12, 15 Months

Choose either calendar or equipment run time-based reminder.
810 Hum Pad Reminder Off

6, 12 Calendar Months

921 Dehum Filter Reminder Off

30, 60 Calendar Days

3 – 12 Calendar Months (in 1 month increments)

1018 Vent Filter Reminder Off, 3, 6, 9, 12 months
# ISU ISU Name ISU Options (defaults in bold) Notes
1100 UV Devices 0 – 2 Some systems may have two UV devices, one for the A-Coil and another for Air Treatment. A replacement reminder can be setup for each one separately.
1105 UV Bulb 1 Reminder Off, 6, 12, 24 months
1106 UV Bulb 2 Reminder Off, 6, 12, 24 months
1401 Idle Brightness 0= Off, 0 – 5 Adjust brightness of an inactive backlight (idle screen) from default 0 (backlight off) to 5 (maximum bright- ness). Brightness level higher that 0 will be applied and enabled for user to change in user menu only if ther- mostat is powered by 24 VAC (C-wire)
1410 Clock Format 12 hour, 24 hour
1415 Daylight Saving On, Off Set to Off in areas that do not follow Daylight Saving Time.
1420 Temperature Offset 0=Off, -3 °F to 3 °F (in 1 °F increments) or

-1.5 °C to 1.5 °C (in 0.5 °C increments)

0 °F – No difference in displayed temperature and the actual room temperature. The thermostat can display up to 3 °F (1.5 C) lower or higher than the actual measured temperature.
1425 Humidity Display Offset 0=Off, -12% to 12% (in 1% increments) 0% – No difference in displayed and actual room % relative humidity. The thermostat can display up to 12% lower or higher than the actual measured % relative humidity.

Z-Wave configuration parameters

If your gateway/hub/controller supports the configuration function, you may remotely configure or change the default thermostat configuration parameters. For detailed table with all available Z-Wave, configuration parameters go to  http://customer.resideo.com or search for T6 Pro Z-Wave Thermostat in the Z-Wave certified products section on http://Z-Wavealliance.org

Performing a system test

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-24
You can test the system setup in ADVANCED MENU under the SYSTEM TEST option.

  1. Press and hold Menu on the thermostat for 5 seconds to access ADVANCED MENU options.
  2. Touch or to go to SYSTEM TEST.
  3. Touch Select or touch the text area.
  4. Touch or to select the system test type. Touch Select or touch the text area.
  5. For the heat test and cool test, use or to activate each stage of the equipment. For the fan test, use or to turn the fan on and off.

NOTE: The clock is used as a timer while the stages are running. The Heat On and Cool On indicators are displayed when the system test is running.

Viewing equipment status

Honeywell-Home-TH6320ZW2003-U Z-Wave-Digital-Programmable-Thermostat-Installation-Guide-fig-25
You can see the status of thermostat-controlled equipment in the Menu under the EQMT STATUS option.

  1. Touch the Menu on your thermostat.
  2. Touch or to go to EQMT STATUS. Touch Select or touch the text area.
  3. Touch or to view the statuses of all the equipment the thermostat is controlling. Depending on what features the thermostat supports or how it was installed, The equipment Status screen reports data for the following systems:
    • Heating and cooling
    • Fan

Alerts and reminders

Alerts and reminders are displayed via the alert symbol and alert number in the clock area on the home screen. You can read more information about active alerts, snooze or dismiss non-critical alerts in Menu/Alerts.

Number Alert/Reminder Definition
54 Thermostat Humidity Sensor Error The sensor of the thermostat has encountered an error. Please contact dealer to replace the thermostat.
164 Heat Pump Needs Service Heat pump needs service. Contact dealer to diagnose and service heat pump.
170 Internal Memory Error The memory of the thermostat has encountered an error. Please contact dealer for assistance.
171 Set the Date and Time Set the date and time on your thermostat. The date and time are required for certain features to operate, like the program schedule.
173 Thermostat Temperature Sensor Error The sensor of the thermostat has encountered an error. Please contact dealer to replace the thermostat.
177 Indoor Temperature Sensor Error Wired indoor temperature sensor is not connected or there is a wiring short. Please contact dealer for assistance.
178 Outdoor Temperature Sensor Error Wired outdoor temperature sensor is not connected or there is a wiring short. Please contact dealer for assistance.
181 Replace Air Filter (1) Replace air filter (1). Reset the timer by touching  the “dismiss” button on thermostat screen after it is replaced.
182 Replace Air Filter (2) Replace air filter (2). Reset the timer by touching  the “dismiss” button on thermostat screen after it is replaced.
184 Replace Humidifier Pad Replace humidifier pad. Reset the timer by touching the “dismiss” button on the thermostat screen after it is replaced.
185 Replace Dehumidifier Filter Replace the dehumidifier filter. Reset the timer by touching “dismiss” button on thermostat screen after it is replaced.
187 Clean or Replace Ventilator Filter Clean or replace ventilator filter. Reset the timer by touching the “dismiss” button on thermostat screen after it is replaced.
188 Replace UV Bulb (1) Replace UV Bulb (1). Reset the timer by touching  the “dismiss” button on thermostat screen after it is replaced.
189 Replace UV Bulb (2) Replace UV Bulb (2). Reset the timer by touching  the “dismiss” button on thermostat screen after it is replaced.

Alerts and reminders

Number Alert/Reminder Definition
252 AC Power Lost If batteries used as backup power it would drain batteries quickly so Z-Wave communication needs to be turned off. The working power mode can only be changed when thermostat is NOT included in

a Z-Wave network. Either to exclude and include thermostat back in to Z-Wave network to change the power mode to LSS (power-save, sleep mode) or to resume AC power. You can check the actual power mode in the thermostat MENU/DEVICE INFO.

405 Battery Low Battery low. Please turn the system mode to off and replace the batteries.
407 Battery Critical Battery critical. Thermostat cannot control your system. Please replace the batteries immediately.
546 Z-Wave Not Configured Z-Wave has a not been configured yet to receive commands from your Z-Wave network. Please follow steps on how to include thermostat in to Z-Wave network.
547 Z-Wave Radio Error Z-Wave module is not operating. Thermostat cannot receive commands from your Z-Wave network. Please contact dealer to replace the thermostat.

Troubleshooting

Specifications

Electrical Ratings

Terminal Voltage

(50/60Hz)

Running

Current

W Heating 18-30 Vac 0.02-1.0 A
(Powerpile) 750 mV DC 100 mA DC
W2 (Aux) Heating 18-30 Vac 0.02-1.0 A
E Emergency Heat 18-30 Vac 0.02-0.5 A
Y Compressor Stage 1 18-30 Vac 0.02-1.0 A
Y2 Compressor Stage 2 18-30 Vac 0.02-1.0 A
G Fan 18-30 Vac 0.02-0.5 A
O/B Changeover 18-30 Vac 0.02-0.5 A
L/A Input 18-30 Vac 0.02-0.5 A

Z-Wave Radio

NOTES
Thermostat Mode V3

CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.

CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.

CAUTION: MERCURY NOTICE
This product should not be disposed of with other household waste. If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Check for the nearest authorized collection centers or authorized recyclers.

5-year limited warranty

For Warranty, information go to http://customer.resideo.com

Regulatory information

FCC REGULATIONS § 15.19 (a)(3)
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference, and
  2. This device must accept any interference received, including interference that may cause undesired operation.

IC REGULATIONS RSS-GEN
This device contains license-exempt transmitter(s)/ receiver(s) that comply with Innovation, Science and Economic Development Canada’s license-exempt RSS(s).

Operation is subject to the following two conditions:

  1. This device may not cause interference.
  2.  This device must accept any interference, including interference that may cause undesired operation of the device.

FCC Warning (Part 15.21) (USA only)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

FCC – 47 CFR § 15.105 (b)
See https://customer.resideo.com/en-US/support/ residential/codes-and-standards/FCC15105/Pages/ default.  for additional FCC information for this product. The operation of this equipment is subject to the following two conditions: (1) this equipment or device may not cause harmful interference, and (2) this equipment or device must accept any interference,
including interference that may cause undesired operation

Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-633-3991 33-00294—11 M.S. Rev. 04-20 | Printed in the United States © 2020 Resideo Technologies, Inc. All rights reserved. The Honeywell Home trademark is used under license from Honeywell International, Inc. This product is manufactured by Resideo Technologies, Inc. and its affiliates.

REFERENCE:

Download Manual

Honeywell Home TH6320ZW2003/U Z-Wave Digital Programmable Thermostat Installation Guide

Honeywell logo

Honeywell Home TH6320ZW2003/U Z-Wave Digital Programmable Thermostat Installation Guide

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)