Dear Customer, Thank you for choosing the Hi, Comfort T100 control. This control device for heating (and cooling) systems and boilers is easily installed and, if used correctly, offers better quality comfort as well as energy savings. This thermostat has been designed to support a maximum of 2 A at 30 VDC or 0.25 A at 230 VAC (specifications for internal relay to switch the boiler “room thermostat” connection). 9 If the device is installed by a third party, please ensure that this manual is given to the end user. 9 These instructions must be kept by the user.

COMPLIANCE
The Hi, Comfort T100 remote control panel complies with:

  • Electromagnetic Compatibility Directive 2014/30/EU
  • Low Voltage Directive 2014/35/EU

At the end of its life, the product should be not be disposed of as solid urban waste, but rather it should be handed over to a differentiated waste collection centre. The following symbols are used in some parts of the manual:

  • CAUTION= for tasks which require particular care and suitable preparation.
  • FORBIDDEN = for tasks which MUST NOT be performed.

GENERAL INFORMATION

General notices

Please read this manual before installing and using the device.

  • Risk of electric shock. This device should be installed by a qualified professional and in line with the standards in force for electrical installations. Always disconnect the power supply before installing.
  • Note to the installer:
    • Most of the product parameters are factory set. If the device is activated without a WiFi connection, the date and time should be set on the thermostat as a minimum (this information is wiped every time the batteries are removed and if not updated via the web). All other settings
    • such as linking the receiver and the transmitter (for the WiFi Box), usage mode and temperatures – are pre-configured.
  • These instructions must be read together with the sections of the boiler manual regarding the room thermostat/boiler remote control. It is recommended that the device be installed by qualified technicians.
  • The Hi, Comfort T100 should be installed in the most accessible room for you as regards controlling the room temperature (usually the living room).
  • As per the standards, the Hi, Comfort T100 should be positioned 1.5 m from the floor to make sure that you can easily read the display.
  • The Hi, Comfort T100 is powered by 2 x AA batteries.
  • The Hi, Comfort T100 must be kept away from sources of heat or air currents as these may affect the accuracy of the readings from the incorporated room sensor.
  • Do not open the Hi, Comfort T100 for any reason, unless to replace the batteries; it does not require any maintenance to operate.
  • Do not press on the liquid crystal display glass as this may damage the glass and cause problems with reading the display.
  • To clean the display, use a dry cloth only. Any seepage would damage the liquid crystal display.
  • With the WiFi Box connected in ON/ OFF mode to the boiler or another appliance via cable, should all of the thermostats be faulty or the batteries be flat, the Box switches OFF (after 12 minutes) if it was ON, or it remains OFF (no heating/ cooling heat request). From the app, you can manually force the WiFi Box relay on or off.
  • With the WiFi Box connected in OTBus mode to the boiler via cable, should all the thermostats be faulty or the batteries flat, the Box will remain in the last operating mode. The boiler (in heating mode) can be forced on and off manually using the APP.
  • With the Hi, Comfort T100 connected (ON/OFF) to the boiler or another device via cable, should all the thermostats be faulty or the batteries flat, the thermostat relay will remain in the last operating mode.
  • Should the power supply to the WiFi Box connected in ON/OFF mode fail, the Box remains in the last operating state. It does not maintain the OFF state.
  • With the WiFi Box connected in OTBus mode to the boiler via cable, should there be a power outage, the WiFi box remains in the last operating mode

What is the Hi, Comfort T100 for?
The Hi, Comfort T100 allows you to check the temperature in your house and the operation of your boiler without you needing to access it. For reasons of space optimisation, your boiler may be located outside (for example, on a terrace or balcony or in an outdoor space); the Hi, Comfort T100, on the other hand, is usually installed in the largest room in the house, where it can be easily checked and adjusted. Where installed in systems with a boiler which is not equipped with the specific communication bus, the Hi, Comfort T100 only allows you to check the temperature in your house and does not allow you to control the boiler remotely (domestic hot water temperature and boiler settings/ alarms cannot be managed). For both types of installation, the Hi, Comfort T100 system allows you to check the temperature in different zones in your house, where there are zone valves and each one of these is connected to a single additional Hi, Comfort T100 (multi-zone management). If the Hi, Comfort T100 is installed together with the WiFi Box and you have a WiFi internet connection in your home, the Hi, Comfort T100 system allows you to carry out the same functions available via the Hi, Comfort T100 itself remotely on a smartphone.

Modes of use
The Hi, Comfort T100 means you can manage your domestic heating in a more sophisticated way; you can decide how and when the boiler will come on to heat your living spaces. In addition, it allows you to set the domestic hot water temperature, without having to access the boiler panel (where connected to the boiler via OTBus or a specific communication bus). The purpose of this manual is to explain each of these ways of using the device and the related functions.

Glossary of technical terms

  • Heating water: the water in the radiators that has been heated by the boiler. Domestic hot water: the water heated by the boiler which is dispensed from the domestic taps.
  • Fault code: this code shows on the display to flag any boiler or Hi, Comfort T100 faults.
  • Original set-up: this is the control panel configuration after turning on the device for the first time or after a reset.
  • Display: this is the liquid crystal panel where each of the symbols corresponding to the various functions are shown.
  • Anti-freeze function: this function ensures that any drops in temperature do not cause the water inside the pipes to freeze and cause damage to the heating system. This function is activated when the room temperature drops below 5°C (this value can be changed by the qualified technical service).
    NOTE
    This function is active only if the boiler is in the correct operating condition (i.e. powered and not blocked).
  • Restore factory settings: this restores the control panel to its original set-up, resetting any user programming excluding the system clock.
  • Summer: the heating system is not active in this mode (for example, during the summer). The boiler can dispense domestic hot water. If correctly connected and configured (in cooling mode), the Hi, Comfort T100 can be used to manage a cooling system in the summer, turning the relay on in ON/OFF mode, in the opposite way to the winter operating mode. The relay keeps the user request connected (e.g. a zone valve) until the room temperature falls below a certain level. The cooling mode requires a specific system and generator for this purpose.
  • Winter: the Hi, Comfort T100 dispenses domestic hot water and hot water for heating in this mode.
  • T1 anti-freeze temperature: this is the temperature used when the rooms are not lived in.
  • T2 economy temperature: this is the temperature used when the rooms are not lived in during the day, at night or when you are on holiday.
  • T3 comfort temperature: this is the temperature at which you obtain ideal room heating during the day.
  • Room temperature: this is the temperature in the room where the Hi, Comfort T100 is installed (see “NOTE 1” to page 7). Room setpoint temperature: this is the desired room temperature.
  • External temperature: this is the temperature outside, read using an external probe connected to the boiler or read in another way (see “NOTE 2” to page 7).
  • Heating curve: this is the relationship between the external temperature and the heating flow temperature. Where external temperature data are available (via an external probe or other method), the heating flow temperature is automatically adjusted as the external temperature varies in order to maintain a constant temperature in the room. The heating curve must be set by the installer on the basis of the geographical location and type of system.
  • Connection via OTBus communication bus: this is a communication mode between the Hi, Comfort T100 and the boiler, where a series of information is exchanged between the two electronic systems. This proprietary connection can be used as opposed to the simple ON/OFF (open/closed contact) and is set by the boiler manufacturer specifically for the Hi, Comfort T100. Check the compatibility of your boiler with the OTBus connection first.
  • ON/OFF connection (boiler room thermostat): this is the simple communication method between the Hi, Comfort T100 and the boiler (or any other unit capable of receiving this command), where the relay on the Hi, Comfort T100 (or on the WiFi Box/receiver) sends an on/off request via the room thermostat (TA) contact on the boiler. The ON/OFF connection is also used when a request is made to another system component such as a zone valve or similar. The Hi, Comfort T100 ON/OFF contact always maintains the same technical characteristics (Hi, Comfort T100 relay, WiFi Box relay, boiler RF receiver relay) wherever it is positioned and these must be respected when connecting the relay and the components it controls via cable.
    NOTE: Never exceed the maximum electrical loads.

NOTE 1
The display range for the room temperature is between -7°C and +50°C.

NOTE 2
The display range for the external temperature is between -40°C and +60°C. Temperatures outside of these ranges are shown as three dashes “- – -”.

Hi, Comfort T100 control Class Declaration, according to the ErP Directive
With reference to Delegated Regulation (EU) No. 811/2013, the data in the table can be used to complete the product data sheets and energy labelling of space heaters, combination heaters, packages of space heater, temperature control devices and solar devices.

Manufacturer/Brand Model
RIELLO SpA / Hi, Comfort T100 Hi, Comfort T100

Possible Hi, Comfort T100 configurations, the relative configuration classes and the energy contribution to the system

Boiler characteristics  

Hi, Comfort T100 configuration

Class and contribu- tion
Boiler with fixed delivery tem- perature (ON/OFF control)  

Hi, Comfort T100 ON/OFF connection

 

I = 1%

Boiler with variable delivery temper- ature (controlled by communication bus) Connection via communication bus to the Hi, Comfort T100. Delivery temperature to the boiler calculated on the basis of one room temperature only  

 

V = 3%

 

Boiler with variable delivery temper- ature (controlled by communication bus)

Connection via communication bus to the Hi, Comfort T100. Delivery temperature to the boiler calculated on the basis of the room temperature and the external temperature (given by the external probe or via the web).  

 

VI = 4%

Boiler characteristics  

Hi, Comfort T100 configuration

Class and contribu- tion
 

Boiler with variable delivery temper- ature (controlled by communication bus)

Connection via communication bus to the Hi, Comfort T100. Delivery tempera- ture to the boiler calculated on the basis of at least 3 distinct room temperatures. At least 3 Hi, Comfort T100s (sensors) connected to at least 3 zone valves (ac- tuators) are required.  

 

 

VIII = 5%

Definition of classes

  • Class I – On/off room thermostat: a room thermostat that controls the on/off operation of a heater. Performance parameters, including switching differential and room temperature control accuracy are determined by the thermostat’s mechanical construction.
  • Class V – Modulating room thermostat, for use with modulating heaters: an electronic room thermostat that varies the flow temperature of the water leaving the heater dependent upon measured room temperature deviation from room thermostat set point. Control is achieved by modulating the output of the heater.
  • Class VI – Weather compensator and room sensor, for use with modulating heaters: a heater flow temperature control that varies the flow temperature of water leaving the heater dependent upon prevailing outside temperature and selected weather compensation curve. A room temperature sensor monitors room temperature and adjusts the compensation curve parallel displacement to improve room comfort. Control is achieved by modulating the output of the heater.
  • Class VIII – Multi-sensor room temperature control, for use with modulating heaters: an electronic control, equipped with 3 or more room sensors, that varies the flow temperature of the water leaving the heater dependent upon the aggregated measured room temperature deviation from room sensor set points. Control is achieved by modulating the output of the heater

INSTALLATION

Contents of the package

The WiFi Hi, Comfort T100 package contains the following components:

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-1 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-2

If installing additional Hi, Comfort T100s or boiler RF receivers, you must follow the procedure to link them to the WiFi Box (see “3.14 Linking function” to page 73). The Hi, Comfort T100 package contains the following components

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-3

If installing additional Hi, Comfort T100s or boiler RF receivers, you must follow the procedure to link them to the WiFi Box (see “3.14 Linking function” to page 73). The WiFi Box kit contains the following components

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-4

If installing additional Hi, Comfort T100 or boiler RF receivers, you must follow the procedure to link them to the WiFi Box (see “3.14 Linking function” to page 73).

The Boiler RF receiver kit contains the following components

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-5

If installing additional Hi, Comfort T100 or boiler RF receivers, you must follow the procedure to link them to the WiFi Box (see “3.14 Linking function” to page 73). In this manual, the descriptions related to “Kit (Thermostat + Wi-Fi Box)”, “Wi-Fi Box”, “RF Receiver” are related to the models below

Description Model
Kit (Thermostat + Wi-Fi Box) Hi, Comfort T100 Wi-Fi;
Wi-Fi Box Hi, Comfort G100-W
RF Receiver Hi, Comfort G100-R.

Practical installation diagrams

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-6

Diagram 1

ON/OFF programmable thermostat for heating (TA). Single heating zone in ON/OFF mode.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-7

Diagram 2
ON/OFF programmable thermostat for heating (TA). Multi-zone heating in ON/OFF mode

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-8

Up to 8 areas if WiFi Box is available. Up to 7 areas with boiler RF receiver connected to the boiler. For information on wireless management of the zone valves, please see “Diagram 16” – “Diagram 17”

Diagram 3

  • Modulating programmable thermostat/remote control.
  • Single heating zone in modulating thermoregulation mode.
  • OT: full control of boiler, heating, DHW, alarms and settings

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-9

Diagram 4

  • Modulating programmable thermostat/remote control and ON/OFF programmable thermostat for heating (TA).
  • Single zone in modulating thermoregulation mode.
  • OT: full control of boiler, heating, DHW, alarms and settings.
  • Multi-zone heating in ON/OFF mode.
  • Set the boiler to “zone valve” mode. For the procedure, contact the Technical Assistance Center

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-10Up to 8 areas if WiFi Box is available. Up to 7 areas with boiler RF receiver connected to the boiler. For information on wireless management of the zone valves, please see “Diagram 16” – “Diagram 17”

Diagram 5
ON/OFF programmable thermostat for heating (TA). Single heating zone in ON/OFF mode. Wireless installation. 9 Only one Hi, Comfort T100 can be connected to the boiler RF receiver

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-11

Diagram 6

  • Modulating programmable thermostat/remote control.
  • Single heating zone in modulating thermoregulation mode.
  • OT: full control of boiler, heating, DHW, alarms and settings.

Wireless installation.
Only one Hi, Comfort T100 can be connected to the boiler RF receiver.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-12

Diagram 7
ON/OFF programmable thermostat for heating (TA) with remote control via WiFi. Single heating zone in ON/OFF mode.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-13

Diagram 8

  • Modulating programmable thermostat/remote control with remote control via WiFi.
  • Single heating zone in modulating thermoregulation mode.
  • OT: full control of boiler, heating, DHW, alarms and settings.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-14

Diagram 9
ON/OFF programmable thermostat for heating (TA) with remote control via WiFi. Wireless installation.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-15

Diagram 10

  • Modulating programmable thermostat/remote control, , with remote control via WiFi.
  • Single heating zone in modulating thermoregulation mode.
  • OT: full control of boiler, heating, DHW, alarms and settings.

Wireless installation

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-16

Diagram 11
ON/OFF programmable thermostat for heating (TA) with remote control via WiFi. Single heating zone in ON/OFF mode. With boiler RF receiver to be inserted if the WiFi signal at the boiler is weak or lacking. Wireless installation. To extend the WiFi signal it is possible to use the WiFi EXTENDER accessory in alternative to the Boiler RF Receiver

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-17

Diagram 12
Modulating programmable thermostat/remote control with remote control via WiFi. Single heating zone in modulating thermoregulation mode. OT: full control of boiler, heating, DHW, alarms and settings. With boiler RF receiver to be inserted if the WiFi signal at the boiler is weak or lacking. Wireless installation. To extend the WiFi signal it is possible to use the WiFi EXTENDER accessory in alternative to the Boiler RF Receiver

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-18

Diagram 13
ON/OFF programmable thermostat for heating (TA) with remote control via WiFi. Multi-zone heating in ON/OFF mode

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-19

Up to 8 zones For information on wireless management of the zone valves, please see “Diagram 16” – “Diagram 17”

Diagram 14
Modulating programmable thermostat/remote control with remote control via WiFi. Multi-zone heating system in modulating thermoregulation mode. OT: full control of boiler, heating, DHW, alarms and settings. Thermoregulation for every zone with automatic selection of the maximum request temperature between the different zones. 9 Set the boiler to “zone valve” mode. For the procedure, contact the Technical Assistance Center.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-19

Up to 8 zones
For information on wireless management of the zone valves, please see “Diagram 16” – “Diagram 17”

Diagram 15
Modulating programmable thermostat/remote control with remote control via WiFi. Multi-zone heating system in modulating thermoregulation mode. OT: full control of boiler, heating, DHW, alarms and settings. Thermoregulation for every zone with automatic selection of the maximum request temperature between the different zones. With boiler RF receiver to be inserted if the WiFi signal at the boiler is weak or lacking. To extend the WiFi signal it is possible to use the WiFi EXTENDER accessory in alternative to the Boiler RF Receiver Set the boiler to “zone valve” mode. For the procedure, contact the Technical Assistance Center

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-21

Up to 8 zones
For information on wireless management of the zone valves, please see “Diagram 16” – “Diagram 17”

Diagram 15
Modulating programmable thermostat/remote control with remote control via WiFi. Multi-zone heating system in modulating thermoregulation mode. OT: full control of boiler, heating, DHW, alarms and settings. Thermoregulation for every zone with automatic selection of the maximum request temperature between the different zones. With boiler RF receiver to be inserted if the WiFi signal at the boiler is weak or lacking. To extend the WiFi signal it is possible to use the WiFi EXTENDER accessory in alternative to the Boiler RF Receiver Set the boiler to “zone valve” mode. For the procedure, contact the Technical Assistance Center.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-21

Up to 7 zones with “Boiler RF Receiver”. For information on wireless management of the zone valves, please see “Diagram 16” – “Diagram 17”

Diagram 16
Wireless management of the zone valves via RF zone receiver. Generic use both in system ON/OFF mode and in OT mode, with or without WiFi.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-22

Up to 8 areas if WiFi Box is available. Up to 7 areas with boiler RF receiver connected to the boiler. Set the RF receiver to the RF zone receiver mode (see paragraph 3.13 “Configuring the RF receiver”).

Diagram 17
Wireless management of various devices controlled by just one Hi, Comfort T100 and of zone valves via RF zone receiver

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-23Set the RF receiver to the RF zone receiver mode (see paragraph 3.13 “Configuring the RF receiver”).

Diagram 18
Management of the area with alternative power source separate from the boiler. Modulating programmable thermostat/remote control with remote control via WiFi and ON/OFF programmable thermostat (TA), with remote control via WiFi. Multi-zone heating system in modulating thermoregulation mode. OT: full control of boiler, heating, DHW, alarms and settings. Thermoregulation for every zone with automatic selection of the maximum request temperature between the different zones. Multi-zone heating in ON/OFF mode

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-24

Set the boiler to “zone valve” mode. Up to 8 zones For information on wireless management of the zone valves, please see “Diagram 16” – “Diagram 17” Set parameter 29 of the alternative power source area to OFF.

Diagram 19
Management of the area with alternative power source separate from the boiler. Modulating programmable thermostat/remote control with remote control via WiFi and ON/OFF programmable thermostat (TA). Multi-zone heating system in modulating thermoregulation mode. OT: full control of boiler, heating, DHW, alarms and settings. Thermoregulation for every zone with automatic selection of the maximum request temperature between the different zones. With boiler RF receiver to be inserted if the WiFi signal at the boiler is weak or lacking. Multi-zone heating in ON/OFF mode. To extend the WiFi signal it is possible to use the WiFi EXTENDER accessory in alternative to the Boiler RF Receiver.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-25

Set the boiler to “zone valve” mode. Up to 7 zones For information on wireless management of the zone valves, please see “Diagram 16” – “Diagram 17” Set parameter 29 of the alternative power source area to OFF.

Diagram 20
Modulating programmable thermostat/remote control with remote control via WiFi. Multi-zone heating system in modulating thermoregulation mode. OT: full control of boiler, heating, DHW, alarms and settings. Thermoregulation for every zone with automatic selection of the maximum request temperature between the different zones

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-25

Up to 8 zones
Set parameter 32 according to zone valve opening time. There cannot be any RF zone receivers where parameter 32 is a value other than 0.

Diagram 21
Modulating programmable thermostat/remote control with remote control via WiFi. Multi-zone heating system in modulating thermoregulation mode. OT: full control of boiler, heating, DHW, alarms and settings. Thermoregulation for every zone with automatic selection of the maximum request temperature between the different zones. With boiler RF receiver to be inserted if the WiFi signal at the boiler is weak or lacking. To extend the WiFi signal it is possible to use the WiFi EXTENDER accessory in alternative to the Boiler RF Receiver

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-27

Up to 7 zones with “Boiler RF Receiver”. Set parameter 32 according to zone valve opening time. There cannot be any RF zone receivers where parameter 32 is a value other than 0.

Diagram 22
Management of the area with alternative power source separate from the boiler. Modulating programmable thermostat/remote control with remote control via WiFi and ON/OFF programmable thermostat (TA), with remote control via WiFi. Multi-zone heating system in modulating thermoregulation mode. OT: full control of boiler, heating, DHW, alarms and settings. Thermoregulation for every zone with automatic selection of the maximum request temperature between the different zones. Multi-zone heating in ON/OFF mode.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-28

Up to 8 zones
Set parameter 29 of the alternative power source area to OFF. Set parameter 32 according to zone valve opening time. There cannot be any RF zone receivers where parameter 32 is a value other than 0.

Diagram 23
Management of the area with alternative power source separate from the boiler. Modulating programmable thermostat/remote control with remote control via WiFi and ON/OFF programmable thermostat (TA). Multi-zone heating system in modulating thermoregulation mode. OT: full control of boiler, heating, DHW, alarms and settings. Thermoregulation for every zone with automatic selection of the maximum request temperature between the different zones. With boiler RF receiver to be inserted if the WiFi signal at the boiler is weak or lacking. Multi-zone heating in ON/OFF mode. To extend the WiFi signal it is possible to use the WiFi EXTENDER accessory in alternative to the Boiler RF Receiver

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-29

Up to 7 zones
Set parameter 29 of the alternative power source area to OFF. Set parameter 32 according to zone valve opening time. There cannot be any RF zone receivers where parameter 32 is a value other than 0.

  • If installing additional Hi, Comfort T100s, follow the procedure to link these Hi, Comfort T100s to the WiFi Box (see “3.14 Linking function” to page 73).
  • When installing a boiler RF Receiver connected to the boiler, it is necessary to perform the connecting procedure to the WiFi Box (see “3.14 Linking function” to page 73).
  • When installing one or more boiler RF Receivers connected to one or more Hi, Comfort T100 it is necessary to perform the connecting procedure to the Hi, Comfort T100 thermostat (see “3.14 Linking function” to page 73).

Technical Data

Description Thermostat Hi, Comfort T100 Units
Battery power supply 2 x 1.5 – AA V
Battery life 18 months (normal use)
Dry contact relay output electrical power (room thermostat) at 30 VCC/VDC min 1 mA
max 2 A
at 230 VAC/VAC max 0.25 A
Radio frequency band (RF) 864-869.6 MHz
Radiofrequency power < 20 mW
Room temperature setting 1 – 35

Resolution 0.2

°C
Room temperature display -9.9 – 50

Resolution 0.2

°C
Factory set temperatures T3 = Comfort 21 °C
T2 = Economy 16 °C
T1 = Anti-freeze 5 °C
Description Thermostat Hi, Comfort T100 Units
Maximum cable length between the WiFi Box and the boiler OTBus terminal or the Hi, Comfort T100 and the boiler OTBus terminal  

30

 

m

Maximum open-field distance between the WiFi Box and the

Hi, Comfort T100 or between the WiFi Box and the boiler RF receiver (RF connection)

 

 

40

 

 

m

Size (W x H x D) 135 x 89 x 28 mm
Distance between holes for wall con- nection electrical box 503 83.5 mm
electrical box DIN 60.3 mm
Description WiFi Box Units
Transformer power supply Input 100-240 / 0.1 VAC/A
Output 5 – 1 VCC-VDC/A
Dry contact relay output electrical power (room thermostat)  

at 30 VCC/VDC

min. 1 mA
max 2 A
Radio frequency band (RF) 864-869.6 MHz
Radiofrequency power < 20 mW
 

WiFi band

EEE 802.11 b/g/n
2.4-2.5 GHz
WiFi Power < 100 mW
Monthly data traffic (30 days) 16.95 MB
Maximum consumption 0.5 W
Maximum length of WiFi Box cables – boiler connection via cables 30 m
Minimum operating room temperature -15 °C
WiFi signal percentage to guarantee cor- rect Hi, Comfort T100 system operation 40 %
Description Boiler RF receiver Units
Transformer power supply Input 100-240 / 0,1 VAC/A
Output 5 – 1 VCC-VDC/A
Dry contact relay output electrical power (room thermostat) at 30 VCC/VDC min. 1 mA
max 2 A
Maximum consumption 1,2 W
Maximum length of WiFi Box cables – boiler connection via cables 30 m
Minimum operating room temperature -15 °C
Radio frequency band (RF) 864-869,6 MHz
Radiofrequency power < 20 mW

Dimensions

Units
W – Width 135 mm
H – Height 89 mm
D – Depth 28 mm

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-30

Three-phase installation

Preparation
Before installing the device Check that the thermostat is compatible with the boiler (see boiler installer manual). The wireless Hi, Comfort T100 thermostat can be installed anywhere, however the most suitable place should be chosen taking into account the following:

  • Avoid draughts (A).
  • Do not install above sources of heat (B).
  • Avoid direct sunlight (C).
  •  Position at the appropriate height (D).

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-31

The following tools are required:

  • Phillips screwdriver
  • Small slotted screwdriver
  • Pliers and wire strippers

Installing the Hi, Comfort T100
Remove the Hi, Comfort T100 from its base;

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-32

Fix the Hi, Comfort T100 base to the wall or electrical box using the screws provided. Using screws other than those PROVIDED may compromise the correct closure of the plastic. Make sure that the screw head is correctly inserted in the hole.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-33

The Hi, Comfort T100 can be installed in one of the following ways:
Wireless
No wiring is required. Please check the maximum openfield distances shown in the Hi, Comfort T100 thermostat technical data. Loss of radio frequency communication is flagged with alarm E82. Distances which exceed the maximum may occasionally generate an E82 alarm, causing incorrect system operation.

Wired in ON/OFF mode (room thermostat contact on Hi, Comfort T100 base) When replacing old thermostats or as a new wired ON/OFF installation. The Hi, Comfort T100 can be connected to a boiler, zone valve or other device. The electrical load on the Hi, Comfort T100 room thermostat contact must not exceed the specifications for the relay itself (see “2.3 Technical Data” to page 33). Should the electrical load not be compatible with the technical characteristics indicated in the Hi, Comfort T100 thermostat technical data, it is recommended that you use an additional separation relay. Connect the cables from the boiler room thermostat terminal or the power supply for any zone valves to the Hi, Comfort T100 room thermostat terminal.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-34

Wired in OTBus mode (OTBus contact on Hi, Comfort T100 base). Direct connection via two wires to the boiler equipped with the same communication protocol. We recommend checking the maximum cable length between the WiFi Box and the boiler OTBus terminal or Hi, Comfort T100 and the boiler OTBus terminal (see “2.3 Technical Data” to page 33). For the electrical connection to the boiler, please see the boiler manual. A wired connection via OTBus between the Hi, Comfort T100 and the boiler is recommended in the absence of a WiFi Box. With the above connection and a WiFi Box, only one zone can be controlled and operation via the APP is not guaranteed.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-35

Insert the 2 x AA batteries provided, with correct polarity

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-36

Fit the Hi, Comfort T100 onto the base

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-37

Installing the WiFi Box

Description of the WiFi Box
The WiFi Box communicates with the Hi, Comfort T100 thermostat or with the boiler RF receiver only via radio frequency (wireless).

OUTPUTS
The WiFi Box contains a relay (see “2.3 Technical Data” to page 33) which replicates the Hi, Comfort T100 thermostat relays linked to it. It is ON if at least 1 of the Hi, Comfort T100 relays is ON, and OFF if all of the Hi, Comfort T100 relays are OFF. The WiFi Box can be wired to the boiler OTBus connection. This transforms the WiFi Box into a wireless receiver of anOTBus command. All of the information available in the Hi, Comfort T100 via the OTBus connection is repeated to the receiver which wires it to the boiler; it is therefore an example of complex radio frequency communication. The relay and OTBus outputs are identified on the WiFi Box by the term OUTPUTS and are available via a USB plug . The position and distinction between the 2 outputs on the USB plug are given below.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-38

USB Outputs/Boiler:

  • Dry contact TA
  • ON/OFF relay
  • max 2 A at 30 VDC
  • OTBus protocol contact
  • Never 230 V

Power supply:

  • USB mini B 5V – 1A
  • WiFi: IEEE 802.11 b/g/n – 2.4 GHz
  • Radio frequency: 868 MHz
  • Power consumption: 0.5 W

Two USB cables are also supplied, one to provide power via the USB power adapter and the other to connect the WiFi Box to the boiler. The cable to connect it to the electrical power supply is a USB mini.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-39

The USB cable to connect the device o the boiler has an end with 4 terminals.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-40

The black terminals are for the ON/OFF connection and are to be connected to the “boiler room thermostat” output. The red terminals are for the connection via OTBus and are to be connected to the “OTBus” output on the boiler.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-41

If there is a Boiler RF receiver installed in the system, these do nothing other than repeat everything that happens in the WiFi Box on a RF receiver with the same outputs (ON/OFF and OTBus) which use the same wiring colours: Red = OTBus, Black = ON/OFF Following you find information on the boiler RF receiver and a description of its electric connection (6 wires)

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-42

WiFi Box connection via OTBus (only for boilers equipped with a compatible OTBus protocol) Connect the red wires of the USB cable to the boiler OTBus terminal (please consult the boiler installer manual). Should the boiler not be equipped with an OTBus terminal, you can use an OTBus connector provided in the WiFi Hi, Comfort T100 package (only for boilers without one). 9 Only one of the Hi, Comfort T100 system components (Hi, Comfort T100, WiFi Box or boiler RF receiver) must be connected to the boiler via cable via OTBus.

ON/OFF WiFi Box connection
Connect the black wires of the USB cable to the boiler room thermostat terminal (it is recommended that you consult the  boiler installer manual). In the case of Hi, Comfort T100 thermostats wired in ON/OFF mode, or zone valve microswitches, it is recommended that you connect these to the boiler room thermostat terminal and wire the WiFi Box to the boiler via OTBus only (only for boilers equipped with a compatible OTBus protocol).

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-43

  • Black cables = TA (ON/OFF)
  • Red cables = OTBus communication protocol

Attach the WiFi Box to the boiler casing using the magnet on the back;

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-44

Connect the USB connector on the previously connected cable to the WiFi Box OUTPUTS/BOILER output;

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-45

Power the WiFi Box via the relevant cable and power adapter provided.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-46

Resetting the OTBus connection autoconfiguration function
The Hi, Comfort T100 is configured to function in ON/OFF mode. Should it be connected to an OTBus communication bus (wired or wireless/ radio frequency), the Hi, Comfort T100 auto-configures to the “Boiler remote control” operating mode. To restore the thermostat to its original operating mode (ON/OFF), remove and then reinsert the batteries. The alarm E82 may be triggered by a change of operating mode from OTBus to ON/OFF or vice versa.

Installing and configuring the smartphone APP
Download the APP on your smartphone or tablet;

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-47

Create a user account;

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-48

Match the WiFi ID of the WiFi Box to the user account. If you need to link other thermostats and/or boiler RF receivers to the WiFi Box via radio frequency, press the clear button on the WiFi Box for 5 seconds until the LEDs flash at the same time and set the device to be linked to the same operating mode (see “3.14 Linking function” to page 73). After making these links, the system automatically resumes normal operation

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-49

Link you home modem password to the WiFi Box via one of the following methods. Smartphones or tablets must be connected to the WiFI network that will be matched to the WiFi Box.

Smart Link

  • Press the Smart Link button on the WiFi Box once with an appropriate implement.
  • The green and red LEDs start flashing frequently.
  • Select the “Configure WiFi” field from the drop-down menu in the APP, insert your home modem password and press the “Connect” button.

The process is complete if the APP displays the message “Connection complete”. Once online, the system requires up to 4 minutes to auto-configure.

WPS (only for modems with this function)

  • Set your home modem to WPS mode.
  • Press the WPS button on the WiFi

Box using an appropriate implement and hold for 5 seconds until the red and green LEDs flash frequently. The link has been made if the red LED on the WiFi Box flashes frequently after a few seconds. Once online, the system requires up to 4 minutes to auto-configure

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-50

Restart the WiFi router at the end of the operation.

NOTE
For further information, please see the Hi, Comfort T100 APP manual.

COMMISSIONING

User interface

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-51

  1. BACK button = allows you to select the desired field, reset an alarm or activate the ONE HOUR BOOSTER function
  2. SET/PROG button = allows you to access the menus or selected field and save
  3. FORWARD button = allows you to select the desired field or activate the special ADVANCE function
  4. UP button = increases the field selected or displays the room temperature for the current time period
  5. ESC/MODE button = allows you to select the operating mode, exit programming, activate the link function or activate the special SEMI-AUTOMATIC FILLING function
  6. ESC = escape
  7. MODE = select the operating mode

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-52

  • AUTO
  • MANUAL
  • HOLIDAY
  • PARTY
  • SUMMER (if OTBus available)
  • OFF

DOWN button = decreases the field selected or displays the room temperature for the current time period

Display

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-53

  1. Date and time
  2. Operating mode
  3. Time program for heating/DHW
  4. Room setpoint temperature desired, in relation to the heating program. If the summer/domestic hot water mode is set, it displays the domestic hot water setpoint temperature (available with OTBus connection between the WiFi Box and the boiler or the RF receiver and the boiler or the Hi, Comfort T100 and the boiler, if provided for by the OTBus protocol).
  5. Batteries running low
  6. Room temperature read by the Hi, Comfort T100 thermostat
  7. Flame detection (available with OTBus connection between the WiFi Box and the boiler or the RF receiver and the boiler or the Hi, Comfort T100 and the boiler, if provided for by the OTBus protocol) or heating request if the Hi, Comfort T100 system is in ON/OFF mode
  8. Unit of measure (°C/°F)
  9. Heating or DHW mode active
  10. Radio frequency communication active with the WiFi Box or with the boiler RF receiver
  11. Cooling mode active

Setting the date and time
From the HOME screen, press the SET/ PROGRAM button twice.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-54

Select the desired field (hours, minutes or day) using the FORWARD or BACK button (time, minutes, day, month and year).

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-57

When day is selected, the corresponding number flashes and the message dAY is displayed

V

When month is selected, the corresponding number flashes and the message Non is displayed.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-59

When year is selected, the corresponding number flashes and the message YEA is displayed

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-60

Change the value using the UP or DOWN buttons

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-63

Press the SET/PROG button to save and return to the programming menu, press ESC/MODE to save and exit the programming menu, or wait 30 seconds to automatically save the value and return to the home screen.

Setting the heating/ cooling mode
The Hi, Comfort T100 is default set to heating mode. In heating mode, the Hi, Comfort T100 activates a request for heat when the room temperature is below the set temperature. In cooling mode, the Hi, Comfort T100 activates an ON request (where there is a cooling system) when the room temperature is above the set temperature. From the HOME screen, press the SET/ PROGRAM button to open the user menu.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-64

Press the FORWARD or BACK button to select the field HEATING/COOLING

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-65

Press the SET/PROG button to set.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-66

Press the UP or DOWN button to select the desired mode.

IN=WINTER
Heating mode

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-67

SU=SUMMER
Cooling mode.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-68

Press the SET/PROG button to save and return to the programming menu, press ESC/MODE to save and exit the programming menu, or wait 30 seconds to automatically save the value and return to the HOME screen. If at least one Hi, Comfort T100 thermostat is in cooling mode, the heating request via OTBus is not considered.

Setting the operating mode
From the HOME screen, press ESC/MODE repeatedly to select one of the following modes:

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-69

OFF mode HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-70

In OFF mode, the Hi, Comfort T100 guarantees the minimum room temperature set at parameter 01 from the PL technical menu only.

NOTE
Only if the boiler is in the correct operating condition (i.e. powered and not blocked). In case of an OTBus connection between the WiFi Box and the boiler (including other types of connection via OTBus), the boiler remains OFF if all the Hi, Comfort T100 thermostats in the system are OFF. When the boiler is OFF it does not provide any heating or domestic hot water

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-71

SUMMER/DHW mode HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-72

Hi, Comfort T100 in SUMMER/DOMESTIC HOT WATER mode. In this mode, the boiler provides domestic hot water where requested (instant boiler). If the parameter 24 CLOC is set to ON; the Hi, Comfort T100 follows the time periods set in the user-programming menu for DHW, pre-heating the water in the storage tank (only for boilers with integrated tank). The minimum room temperature set at parameter 01 from the PL technical menu is, however, guaranteed. In case of an OTBus connection between the WiFi Box and the boiler (including other types of connection via OTBus), the boiler remains in SUMMER mode if at least one of the thermostats is in summer mode and the others are OFF

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-73

WINTER/AUTOMATIC mode
In Winter/AUTOMATIC mode, the Hi, Comfort T100 follows the time program set in the user-programming menu for heating. In case of an OTBus connection between the WiFi Box and the boiler (including other types of connection via OTBus), the boiler remains in Winter/AUTOMATIC mode if at least one of the thermostats is in heating mode.  For installations with multiple Hi, Comfort T100 thermostats connected via OTBus, if one of these devices is in cooling mode, the heating request to the boiler is not considered

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-74

WINTER/MANUAL modeHI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-75
Hi, Comfort T100 in Winter/MANUAL mode, the Hi, Comfort T100 programmable thermostat takes the T3 room setpoint temperature (comfort), ignoring the heating time program. In case of an OTBus connection between the WiFi Box and the boiler (including other types of connection via OTBus), the boiler remains in Winter/MANUAL mode if at least one of the thermostats is in heating mode. For installations with multiple Hi, Comfort T100 thermostats connected via OTBus, if one of these devices is in cooling mode, the heating request to the boiler is not considered.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-76

WINTER/HOLIDAY modeHI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-77

In HOLIDAY mode, the Hi, Comfort T100 takes the T2 room setpoint temperature (economy), ignoring the heating time program, for the days set with the FORWARD or BACK buttons. The Hi, Comfort T100 returns to AUTO modeHI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-78 once the days set in HOLIDAY mode have lapsed. In case of an OTBus connection between the WiFi Box and the boiler (including other types of connection via OTBus), the boiler remains in Winter/HOLIDAY mode if at least one of the thermostats is in heating mode. For installations with multiple Hi, Comfort T100 thermostats connected via OTBus, if one of these devices is in cooling mode, the heating request to the boiler is not considered

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-79

WINTER/PARTY modeHI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-80

takes the T3 room setpoint temperature (comfort), ignoring the heating time program, until midnight of the current day, and then automatically switches back to AUTO modeHI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-81 . In case of an OTBus connection between the WiFi Box and the boiler (including other types of connection via OTBus), the boiler remains in Winter/PARTY mode if at least one of the thermostats is in heating mode.  For installations with multiple Hi, Comfort T100 thermostats connected via OTBus, if one of these devices is in cooling mode, the heating request to the boiler is not considered.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-82

Setting the extra functions

ADVANCE function for AUTOMATIC operating mode
The ADVANCE function allows you to bring forward the next heating/cooling time period and the relative room setpoint temperature desired, or to disable the heating time period if it is already running. To activate/deactivate the ADVANCE function, from the HOME screen press the FORWARD button (if active, the MAN icon is displayed).

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-83

ONE HOUR BOOSTER function for AUTOMATIC operating mode
The ONE HOUR BOOSTER function allows you to activate the heating/ cooling time period and the relative T3 room temperature (comfort) for 60 minutes, if it is not already in operation.  If the heating time period relative to the T3 room setpoint temperature (comfort) is already running, by activating the function the time period is extended by one hour, but not beyond midnight of the current day. To activate/deactivate the ONE HOUR BOOSTER function, from the HOME screen press the BACK button (if active, the MAN icon is displayed).

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-84

SEMI-AUTOMATIC FILLING function
The SEMI-AUTOMATIC FILLING function allows the correct system pressure to be restored and is only available for boilers equipped with the relevant function (if OTBus connection available between the WiFi Box and the boiler or the RF receiver and the boiler or the Hi, Comfort T100 and the boiler, if provided for by the OTBus protocol). If the rIE alarm is quick flash (0,5 sec.) on the HOME screen in the room temperature field,

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-85

press the ESC/MODE button and hold for 5 seconds to start semi-automatic filling (the message rIE will stop flashing and remain on). When releasing the button ESC/MODE the rIE message starts flashing slowly (2 secs) until the end of the function.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-86

Once the system pressure has been restored, the Hi, Comfort T100 automatically returns to the normal HOME screen display.  If the SEMI-AUTOMATIC FILLING function is not carried out within 90 seconds, the rIE alarm flashes quickly (1sec.) and is displayed on the HOME page again.

KEY-LOCK function
In the main menu press the FORWARD and UP buttons for 5 seconds simultaneously to display the request for password entry

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-87

If the password has never been set, the symbols “–” are displayed; set the new password using the UP and DOWN buttons and press SET to confirm and return to the main menu with the buttons disabled. The new password is then saved. The password value must be between “0” and “99”. The default value is not set “–“. If the password has already been set, “00” is displayed; enter the password using the UP and DOWN buttons and press SET to confirm.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-88

If the password entry is correct and the button function is enabled, the text “LOC” is displayed for 5 seconds in place of the ambient temperature, and the functions of all individual buttons are disabled.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-89

If the password entry is incorrect, the display returns to the main menu. When the keypad is blocked and any button is pressed, the text “LOC” is displayed for 5 seconds. To re-enable button functions, press the buttons FORWARD and UP simultaneously for 5 seconds, after which the password is requested. If the password entry is correct, the text “UnL” is displayed for 5 seconds in place of the ambient temperature, and the functions of all buttons are re-enabled. If the password entry is incorrect, the text “LOC” is displayed for 5 seconds in place of the ambient temperature, and the functions of all individual buttons remain disabled.

Reset password – key lock
To reset the password press the FORWARD and UP buttons at the same time and hold for 5 seconds; you are then asked to enter the password and “00” is displayed. Press the BACK and DOWN buttons at the same time and hold for 5 seconds to reset the old password and “–” is displayed. Press SET/PROG to return to the home screen without entering the password (with the buttons unlocked) or set a new password using the UP and DOWN buttons and confirm using SET/PROG, returning to the main screen either with the buttons disabled, “LOC” (where the last status was “UnL”) or with the buttons enabled, “UnL” (where the last status was “LOC”). When the power is turned ON, the buttons show the same status as when the power was switched off. If the password is not entered after 2 minutes, the device returns to the main screen.

Setting the heating/ cooling time program in automatic operating mode
From the HOME screen, press the SET/ PROGRAM button to open the user menu.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-90

Press the FORWARD or BACK button to select the field HEATING/COOLING TIME PROGRAM

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-91

Press the SET/PROG button to set.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-92

Press the FORWARD or BACK button to select the day or period of the week to be changed

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-93 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-94 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-95

Press the SET/PROGRAM button to confirm the day or period of the week to be changed. Press the FORWARD or BACK button to select the time segment to be changed. Press the ESC/MODE button to select the desired room setpoint temperature (T1, T2, T3). Press the UP button to copy the previous setting to the following time segment (the DOWN button can be  used to go back or copy the setting tothe previous time segment). Press the SET/PROG button to save and return to the programming menu, press ESC/MODE to save and exit the programming menu, or wait 30 seconds to automatically save the value and return to the HOME screen.

Setting the DHW time program
This function is available only if the parameter 24 CLOC is set to ON. The time periods are default set to ON (domestic hot water function active). From the HOME screen, press the SET/ PROGRAM button to open the user menu.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-96

Press the FORWARD or BACK button to select the field DHW TIME PROGRAMHI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-72

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-97

Press the SET/PROG button to set. Press the FORWARD or BACK button to select the day or period of the week to be changed.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-98 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-99 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-100

Press the SET/PROGRAM button to confirm the day or period of the week to be changed. Press the FORWARD or BACK button to select the time segment to be changed. Press the ESC/MODE button to activate or deactivate the domestic hot water function. Press the UP button to copy the previous setting to the following time segment (the DOWN button can be used to go back or copy the setting to the previous time segment). Press the SET/PROG button to save and return to the programming menu, press ESC/MODE to save and exit the programming menu, or wait 30 seconds to automatically save the value and return to the HOME screen.

Setting the heating/ cooling room setpoint temperature
To change the T1/T2/T3 room setpoint temperature, press the SET/PROGRAM button from the HOME screen to enter the user menu. Press the FORWARD or BACK button to select the field HEATING/COOLING TEMPERATURE

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-101

Press the SET/PROG button to set.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-102

Press the FORWARD or BACK button to select the temperature to be changed.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-103

Press the UP or DOWN button to modify the selected room setpoint temperature. 9 The T3 temperature (comfort) cannot be higher than 35°C or less than or equal to T2 (economy). 9 The T2 temperature (economy) cannot be higher than or equal to T3 (comfort) or less than or equal to T1 (anti-freeze The T1 temperature (anti-freeze) cannot be higher than or equal to T2 (economy) or less than 1°C. Press the SET/PROG button to save and return to the programming menu, press ESC/MODE to save and exit the programming menu, or wait 30 seconds to automatically save the value and return to the HOME screen. The room setpoint temperatures can also be modified instantly if the Hi, Comfort T100 is in the operating mode corresponding to the room setpoint temperature to be modified.

Setting the temperature in MANUAL mode
From the HOME screen, press the UP or DOWN button to set the desired T3 (comfort) room setpoint temperature.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-104

The room setpoint temperature set cannot be less than or equal to the T2 temperature (economy). Press the SET/PROG button to save and return to the HOME screen, press ESC/ MODE to save and return to the HOME screen, or wait 5 seconds to automatically save the value and return to the HOME screen.

Setting the temperature in AUTOMATIC mode
From the HOME screen, press the UP or DOWN button to set the desired room setpoint temperature for the current time period.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-105

Press the SET/PROG button to save and return to the HOME screen, press ESC/ MODE to save and return to the HOME screen, or wait 5 seconds to automatically save the value and return to the HOME screen

Setting the temperature in HOLIDAY mode
From the HOME screen, press the UP or DOWN button to set the desired T2 (economy) room setpoint temperature

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-106

The room setpoint temperature set cannot be higher than or equal to T3 (comfort) or less than or equal to T1 (anti-freeze). Press the SET/PROG button to save and return to the HOME screen, press ESC/ MODE to save and return to the HOME screen, or wait 5 seconds to automatically save the value and return to the HOME screen.

Setting the temperature in PARTY mode
Press the UP or DOWN button on the HOME screen to set the desired room setpoint temperature.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-107

The room temperature set cannot be less than or equal to the desired T3 (comfort) room setpoint temperature. 9 The room setpoint temperature set cannot be less than or equal to the T2 temperature (economy). Press the SET/PROG button to save and return to the HOME screen, press ESC/ MODE to save and return to the HOME screen, or wait 5 seconds to automatically save the value and return to the HOME screen

Setting the DHW setpoint temperature
From the HOME screen, press the SET/ PROGRAM button to open the user menu. Press the FORWARD or BACK button to select the field DOMESTIC HOT WATER TEMPERATURE.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-108

Press the SET/PROG button to set.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-109

Press the UP or DOWN button to modify the domestic hot water setpoint temperature. Press the SET/PROG button to save and return to the programming menu, press ESC/MODE to save and exit the programming menu, or wait 30 seconds to automatically save the value and return to the HOME screen.

Displaying operating information
This function (available with OTBus connection between the WiFi Box and the boiler or the RF receiver and the boiler or the Hi, Comfort T100 and the boiler, if provided for by the OTBus protocol) allows you to display the boiler probe values and some boiler operating statuses. From the HOME screen, press the SET/ PROGRAM button to open the user menu.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-110

Press the FORWARD or BACK button to select the field InFO

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-111

Press the SET/PROGRAM button to display this field.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-112

Press the UP or DOWN button to select the desired parameter and wait until it is displayed

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-113 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-114 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-115

Press the SET/PROG button to save and return to the programming menu, press ESC/ MODE to save and exit the programming menu, or wait 180 seconds to automatically save the value and return to the HOME screen

Technical menu – Advanced programming
From the HOME screen, press the SET/ PROGRAM button to open the user menu.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-116

Press the FORWARD or BACK button to select the field PL.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-117

Press the SET/PROG button to set

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-118

Press the UP or DOWN button to insert the installer password (password = 18).

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-119

Press the SET/PROG button to set.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-120

Press the FORWARD or BACK button to select the desired parameter. Press the SET/PROGRAM button to set the selected parameter. For parameters 08 to 19, use the FORWARD or BACK button to select the 2 sub-parameters. Press the UP or DOWN button to modify the selected parameter. Press the SET/PROG button to save and return to the technical menu, press ESC/ MODE to save and exit the technical menu, or wait 120 seconds to automatically save the value and return to the HOME screen.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-122 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-123 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-124 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-125 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-126 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-127 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-129 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-130 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-131 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-132

CH Re-

quest

Par. 29 Hi,ComfortT100 Wifi box RF boiler receiver RF zone receiver
OT Relay OT Relay OT Relay OT Relay
ON OFF off on off off off off (*)
ON OF0 off on off on off on ON
ON ON on on on on on on ON
Cool Request Par. 29 Hi,ComfortT100 Wifi box RF boiler receiver RF zone receiver
OT Relay OT Relay OT Relay OT Relay
ON OFF off on off off off off (*)
ON OF0 off on off on off on ON
ON ON off on off on off on ON
  • off= request in progress not met
  • on= request in progress met

(*) = not supported. To ensure the relay-controlled zone valve operates, use a Hi, Comfort T100 wired to the zone valve.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-133

RF receiver configuration
The RF receiver can be configured to be used as a boiler RF receiver or as an RF receiver for the zone valve. The receiver is factory set as the boiler RF receiver. To configure the RF receiver proceed as follows:

  • Power up the receiver
  • Press button B once during the two seconds in which the green and red leds remain lit.

The operating mode of the RF receiver switches from boiler RF receiver to zone valve RF receiver and vice versa.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-135

The change in configuration is identifiable by the different flashing mode of the green led.

Configured as boiler RF receiver
Green LED Red LED
Relay Off 0.5 sec. on

0.5 sec. off

Relay On 0.2 sec. on

0.2 sec. off

Configured as zone receiver
Green LED Red LED
Relay Off 2 sec. on

2 sec. off

Relay On 1 sec. on

1 sec. off

NOTE
If the receiver is configured as a boiler RF receiver, the Opentherm connection to the boiler should be detached to enable display of the flashing green led.

Linking function
Hi, Comfort T100 linking with the WiFi Box The Hi, Comfort T100 and the WiFi Box in the WiFi Hi, Comfort T100 package are already linked.If installing an additional Hi, Comfort T100, follow the procedure below. Ensure that the Hi, Comfort T100 and the WiFi Box are connected to a power source and there are no alarms. Press the prismatic dome clear LED button (A) and hold for 5 seconds until the green and red LEDs slow flashing (1 seconds) at the same time (once linked the flash will return to normal).

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-136

From the Hi, Comfort T100 HOME screen, press the ESC/MODE button and hold for 5 seconds to display the following (alternating) information.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-137

EXAMPLE OF LINKED Hi, Comfort T100

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-138

  1. Radio frequency channel
  2. Receiver (WiFi Box) number
  3. Radio frequency address
  4. number of the thermostat assigned by the WiFi Box (in the event of several linked thermostats) – identifying the zone
    EXAMPLE OF LINKED Hi, Comfort T100HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-139
  5. number of the transmitter (Hi, Comfort T100)

To complete the link, press the SET/PROGRAM button or wait for Hi, Comfort T100 to return to the HOME screen. 9 This may take up to 2 minutes, after which the Hi, Comfort T100 automatically returns to the HOME screen. Should the link not be successful, please contact the Authorised Service Centre.

NOTE
When replacing the WiFi Box it is necessary to repeat the linking again between the WiFi Box and Hi, Comfort T100.

Linking the boiler RF receiver to the WiFi Box
If installing a boiler RF receiver, please follow the procedure below. Press the prismatic dome clear LED button (A) on the WiFi Box and hold for 5 seconds until the green and red LEDs slow flash at the same time (1 sec). Press and hold again for 5 seconds until the green and red LEDs momentarily switch off and then flash slowly (every 2 seconds).

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-140

Press the prismatic dome clear LED button (B) on the boiler RF receiver and hold for 5 seconds. The green and red LEDs of the WiFi Box flash quickly (0.5 sec) and at the same time to indicate the successful connection. Press the button on the WiFi Box again to confirm. The boiler RF receiver auto-configures to normal operating mode The light indicators on the boiler RF receivers could differ from what is indicated in section “4 Alarms and operating statuses” to page 77 9 This may take up to 2 minutes, after which the Hi, Comfort T100 automatically returns to the HOME screen. Should the link not be successful, please contact the Authorised Service Centre

NOTE
When replacing the WiFi Box it is necessary to repeat the linking again between the boiler RF receiver and the WiFi box.

Linking the RF receiver to the Hi, Comfort T100
The Hi, Comfort T100 programmable thermostat can be linked to a wireless receiver if you want to replicate the relay functionality on the thermostat in a remote zone (e.g. zone valve), which is not accessible with a cable (wireless access). Follow the procedure below to link them: Press the prismatic dome clear LED button on the boiler RF receiver and hold for 5 seconds until the green and red LEDs slow flash (1 seconds) at the same time (once linked the flash returns to normal). The light indicators on the boiler RF receivers could differ from what is indicated in section “4 Alarms and operating statuses” to page 77 From the Hi, Comfort T100 HOME screen, press the ESC/MODE button and hold for 5 seconds to display the following (alternating) information

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-141

EXAMPLE OF LINKED Hi, Comfort T100

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-142

  1. Channel (usually 11)
  2. Address (usually 00)
  3. Thermostat ID (unequivocal, also shown on the app/server)
  4. number of the thermostat assigned by the WiFi Box (in the event of several linked thermostats) – identifying the zoneHI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-143
  5. number of the transmitter (Hi, Comfort T100)

Checking the number assigned to the thermostat in the vent of a multizone (several thermostats )paired with a WiFi Box Put the thermostat in RF pairing mode by pressing the MODE button for 5 seconds. Press the FORWARD button once: the number that appears in the position under address (2) indicates the number assigned to the thermostat (or identifying the zone served by the thermostat). Press PROG to exit. To complete the link, press the SET/PROGRAM button or wait for Hi, Comfort T100 to return to the .HOME screen 9 This may take up to 2 minutes, after which the Hi, Comfort T100 automatically returns to the HOME screen. Should the link not be successful, please contact the Authorised Service Centre.

NOTE
When replacing the WiFi Box it is necessary to repeat the linking between the zone RF receiver and Hi, Comfort T100

Resetting the WiFi Box
To perform a full reset of the WiFi Box, deleting the full list of coupled devices (thermostats and receivers):

  • press the clear prismatic round LED button (A) on the WiFi Box and hold for 5 seconds until the green and red LEDs both start to flash slowly (1 sec).
  • press the Smart Link button on the WiFi Box once using a suitable instrument

The clear LED remains off for 1 second to confirm the operation was successful. At the end of this operation the linking should be carried out again between:

  • WiFi Box and thermostats
  • Zone RF thermostats and receivers.

ALARMS AND OPERATING STATUSES

LED notification lights for the WiFi Box and boiler RF receiver **

LED

Green

LED

Red

Status
 

F05

Relay = closed (only for ON/OFF connections)
 

F1

Relay = open (only for ON/OFF connections)
 

ON

OTBus connection

= OK

(for OTBus con- nection)

 

ON

 

F01

Boiler alarm (only for OTBus connection)
F05 F1

ON (OT

Bus)

 

ON

 

Network or RF error

 

F05

 

F05

WPS mode active

– Wait for WPS signal from the router*

F05 WPS signal ac- cepted*
F05 F05 Smartlink mode active*
F1 F1 Encoded RF mode active

Only for WiFi Box ** The notification lights on Boiler RF receivers may differ with respect to the table.

LED

  • ON = remains on
  • F05 = quick flash (every 0.5 seconds)
  • F1 = slow flash (every 1 second)

Operation of the prismatic dome clear LED button on the WiFi Box and boiler RF receiver

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-136

In case of a boiler alarm (available with OTBus connection between the WiFi Box and the boiler or the RF receiver and the boiler or the Hi, Comfort T100 and the boiler, if provided for by the OTBus protocol), the alarm can be reset by pressing the prismatic dome clear LED button (A) (for alarm A99, reset from the boiler). 9 The reset performed by the boiler RF receiver could differ from what has been described. With an ON/OFF connection, the relay can be activated or deactivated by pressing the prismatic dome clear LED button (A).

Boiler and Hi, Comfort T100 alarms
The alarm is shown in alternation with the room temperature detected by the Hi, Comfort T100 on the display.

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-145

In case of a boiler alarm (available with OTBus connection between the WiFi Box and the boiler, if provided for by the OTBus protocol), the alarm can be reset by pressing the BACK/RESET button (for alarm A99, reset from the boiler). 9 The Hi, Comfort T100 alarms (rIE, E82, E83) and the temporary boiler alarms may be automatically reset once the fault has been resolved

HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-146 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-147 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-148 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-149 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-150 HI-COMFORT-T100-Wi-Fi-THERMOSTAT-INSTALLER-FIG-151

Alarm Description
A01-A10 Burner ignition/detection failure after numerous attempts
A02-A20 Limit thermostat tripped
A03-A30 Flue gas thermostat and/or safety thermostat and/or air pressure switch and/or fan fault
A04-A40 Primary circuit pressure insufficient
A06-A60 DHW NTC probe anomaly
A07-A70 Alarm relating to heating NTC probe and/or delivery NTC probe and/ or excessive differential between the delivery and return NTC probes
A08-A80 NTC return probe alarm and/or excessive differential between the combustion probes
A09-A90 NTC smoke probe alarm or exchanger dirty and combustion non coherent
A77 Low external temperature limit thermostat tripped
A99 Too many resets performed via remote control

The alarm history can be viewed under the parameter ALL from the advanced programming menu. For details of boiler alarms, please see the boiler installer manual.

RIELLO S.p.A. 37045 Legnago (VR)

As part of the company’s ongoing commitment to perfecting its range of products, the appearance, dimensions, technical data, equipment and accessories may be subject to variation.

Reference

Download Manual:

HI, COMFORT T100 Wi-Fi THERMOSTAT INSTALLER Manuals

HI-LOGO

HI, COMFORT T100 Wi-Fi THERMOSTAT INSTALLER Manuals

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post’s permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post’s URL again. (Find out more about Webmentions.)