Hailin HL116 Digital Room Thermostat
Introduction
HL116 Series thermostats are available for individual room temperature control in residential, industrial and business premises. Suitable for 2-pipe or 4-pipe Fan Coil configuration. HL116 adopt digital control technology with LCD display, It shows the following items: working states (cool, heat, auto or ventilation), the room temperature, and set-point. There are following keys on the panel: Exchange mode (cool, heat, auto or ventilation) “M”, set-point temperature “and ”; switch: Power On/Off, and Select fan speed (high, medium or low).
MODEL DENOMINATIONS
- DA/DA2: Control Motorized Valve (DA: Control 2-wire N.C. FCU valve; DA2: Control 3-wire FCU valve) and 3-speed fan; When the temperature reaches the set-point, it will close the Motorized Valve with the fan still running.
- (A)FCV2: Control 4 pipe fan coil units, Control two Motorized Valves and 3-speed fan, when the temperature reaches the set-point, it will close the Motorized Valves with the fan still running.
- P: Control the 3-wire FCU valve (Floating Arithmetic) and 3-speed fan; when the temperature reaches the set-point, it will close the Motorized Valve with the fan still running.
BASIC FEATURES
- Room temperature setting
- Manual 3-speed changeover
- Defrost (low-temperature protection)
- Blue Backlight
SPECIFICATIONS
- Sensing element: NTC
- Accuracy : ± 1℃
- Set-point range: 5℃ to 35℃
- Display range: 0~50℃
- Operation environment: 0~45℃
- Operating Humidity: 5~95%RH (non-condensing)
- Power supply: AC 220V ± 10%, 50/60Hz
- Switch current rating: Resistive: 2A, Inductive: 1A
STATUS DISPLAY
- Working Status: Cool, Heat, Auto and Ventilation
- Room temperature display
- Temperature setting display
- Rated Power: < 2 W
- Wirings: Screw-in terminals, each terminal capable of accepting 2 x 1.5 mm2 or 1 x 2.5 mm2 wires
- Housing: ABS + PC Flame Retardant
- Dimensions: 86 × 86 × 23.5 mm ( W × H × D )
- Hole pitch: 60 mm ( Standard )
- Protection Class: IP30
- Display: LCD
OPERATION
- On/Off: Slide the switch to “LOW”, “MED” or “HIGH” turn on; Slide the switch to “OFF”, to turn off thermostat and its output.
- Setting temperature: Press “” to reduce set-point, press “” to raise set-point, and 1℃ changed once.
Mode Selection
- HL116DA/DA2/P: When turn on, Press “M ” to change system working in cooling “ ”, heating “ ” or ventilation “ ” mode, the related icon will flash, and a continuous switch can be performed among three models hereinbefore while “M ” key is pressed without release.
- HL116(A)FCV2: When turn on, Press “M” to change the system working in cooling “ ”, heating “ ”, Auto “ ” or ventilation
- “ ” mode in turn, the related icon will flash, and a continuous switch can be performed among four models hereinbefore while
- “ M” key is pressed without release. Thermostat auto-switch to cooling or heating mode in accordance with the result set point compared to environment temperature under AUTO “ ” mode (This mode is called AFCV2 mode).
- Fan speed selection: If the switch on the panel is slipped to position LOW、MED or HIGH, namely, the corresponding Fan speed of representation LOW、MED、HIGH symbol is selected
- Control of motorized-valve (L116DA/DA2/P): If the difference between room temperature and set-point exceed (or under) 1℃, FCU valve will be open; if room temperature are equal to set-point, the FCU valve will close with the fan still running.
- Control cooling-heating FCU Valve under 4-pipe configuration (HL116FCV2): In cooling Mode, when the room temperature is higher than the set-point, the cooling valve will be opened. Otherwise it will be closed. Heating valve is always closed In heating, in heating Mode When the room temperature is lower than the set-point, the heating valve will be opened. Otherwise, it will be closed. Cooling valve is always closed.
LOW-TEMPERATURE PROTECTION
If the thermostat is at shut state, and when room temperature is lower than 5℃, the thermostat will start valve for heating, HL116DA/DA2/P for electric motorized valve and HL116FCV2 for heating water valve respectively, when the temperature returns to 7℃ or above, it will close valve.
SET LOW-TEMPERATURE PROTECTION
urn off the thermostat, press “ ” until the backlight is on and the parameter setting is displayed with icon “ ” and “00”, “01”, press “” or “” key to adjust. “00” indicates low-temperature protection is invalid, “01” indicates the low-temperature protection function is valid. The default is “00”.
Caution: test Mode modification is prohibited while “F” is displayed in the middle of the LCD screen
WIRING DIAGRAM
MOUNTING