gewiss logo

Gewiss GW21853 ELECTRONIC THERMOSTAT 

Gewiss-GW21853-ELECTRONIC-THERMOSTAT-PRODUCT

Electronic thermostat for Fan-Coil

ATTENTION – IMPORTANT

GENERAL PRODUCT DESCRIPTION

Functions

opEratINg Data

Technical Data

INSTALLATION INSTRUCTIONS

loCatIoN a DVICE

Gewiss-GW21853-ELECTRONIC-THERMOSTAT-FIG.1

recommendations on positioning:
Install the thermostat at a height of from 1.50 to 1.70 m from the floor, far away from sources of heat, air ducts, doors or windows

Gewiss-GW21853-ELECTRONIC-THERMOSTAT-FIG.2

Example of installation with the thermostat controlling the fan and solenoid valve.
Example of installation with the thermostat controlling only the fan.
N.B.: The examples shown in the following documentation are for illustration purposes only.

Electrical Connections

Important: electrical wiring installation of the devices and appliances should be carried out by qualified technicians in accordance with the regulations and laws in force. The manufacturer will not assume any responsibility for the use of products that must comply with special environmental and/or installation regulations; this obligation is the responsibility of and to charge of the installer.
Warning: before installing the product, disconnect the power supply.
Important: the thermostat control outputs are polarized; pay close attention to Line and Neutral connections.

Wiring: as indicated in the figure.
Disconnect the power supply (main breaker).
Connect the supply line to terminals n° 2 (Neutral) and n° 3 (Line).
Connect the fluid interception solenoid valve to terminal n° 4.
Based on the type of installation, connect the wires for speed control coming from the fan to terminals n° 5-6-7:

N.B.:

Gewiss-GW21853-ELECTRONIC-THERMOSTAT-FIG.3

The setting wire must always be connected to terminal n° 3 or terminal n° 4. setting the fan-coil control mode
N.B.: the solenoid valve is always thermostat controlled.

  1.  thermostat-controlled fan operation
    Connect the wire that comes out of the first hole of the thermostat terminal board (hole 1) to terminal n° 4.
    Wiring diagram for solenoid valve control and fan control with the thermostat-controlled operationGewiss-GW21853-ELECTRONIC-THERMOSTAT-FIG.4
  2. Continuous fan operation
    Connect the wire that comes out of the first hole of the thermostat terminal board (hole 1) to terminal n° 3.Gewiss-GW21853-ELECTRONIC-THERMOSTAT-FIG.5

OPERATING INSTRUCTIONS

CommaNDsaND s IgNals:

Gewiss-GW21853-ELECTRONIC-THERMOSTAT-FIG.6

OPERATING mode

Based on the devices connected (fan and/or solenoid valve) and the terminal (n° 3 or n° 4) to which the wire for the fan operating mode setting is connected, the thermostat can operate in the following modes:

  1. thermostat-controlled solenoid valve and continuous fan operation (fig. a)
  2. thermostat-controlled solenoid valve and fan operation (fig. a)Gewiss-GW21853-ELECTRONIC-THERMOSTAT-FIG.7
  3. thermostat-controlled fan operation only and solenoid valve not connected (fig. B)
    In all cases, 3 different fan speeds can be selected by a switch on the front panel.
    Heating or cooling mode can also be selected by a switch on the front panel.

The thermostat operates with proportional temperature control, within a 1°C-band width, as shown in the figure.
Regulation is carried out by switching the load on and off for variable time intervals, depending on the difference between the temperature setpoint and the temperature reading.

Gewiss-GW21853-ELECTRONIC-THERMOSTAT-FIG.8

References

Download Manual

Gewiss GW21853 ELECTRONIC THERMOSTAT Instruction Manual

gewiss logo

Gewiss GW21853 ELECTRONIC THERMOSTAT Instruction Manual

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)