Fujitsu UTY-RNRUZ5 Wired Remote Thermostat

Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat

SAFETY PRECAUTIONS

WARNING Indicates a potentially or imminently hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION Indicates a potentially hazardous situation that may result in minor or moderate injury or damage to property.

Do not install the unit in the following areas:

MAIN UNIT AND ACCESSORIES

The following installation parts are supplied. Use them as required.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-1

ELECTRICAL REQUIREMENT

When connecting the remote controller use the following wiring.

Cable size Wire type Remarks
22 to 16 AWG

(0.33 to 1.25 mm²)

Non polar 2 core Use sheathed twisted pair cable
18AWG Thermostat cable 2 core Use sheathed non twisted pair cable

Select a fl exible cable that can be bound using cable ties from over the cable sheath inside this unit. Maximum connectable number of remote controllers by cable size and the length.

Cable size Max. connectable number of remote controllers
 

 

AWG

 

 

mm²

 

L* ≤ 328 ft (L* ≤ 100 m)

328 ft < L*

≤ 820 ft (101 m < L*

≤ 250 m)

820 ft < L*

≤ 1,640 ft (251 m < L*

≤ 500 m)

VRF RAC VRF RAC VRF RAC
16 1.25 4 2 4 2 4 2
18 0.75 (1.25 > S* ≥ 0.75) 4 2 4 2 2 2
20 0.5 (0.75 > S* ≥ 0.5) 4 2 2 2 2 2
22 0.3 (0.5 > S* ≥ 0.3) 4 2 1 1 1 1

L: Total cable length, *S: Cable size

SELECTING AN INSTALLATION LOCATION

Dimensions and Name of parts

Remote controller unit

Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-2

All Fujitsu General products are manufactured to metric units and tolerances. United States customary units are provided for reference only.
In cases where exact dimensions and tolerances are required, always refer to metric units.

Monitor mode screen
The home screen of this unit. Except for in the following cases, the screen will return to this screen if there is no operation for over 10 min. (Unsaved settings will be cancelled.)

Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-3

For the screen display, this product uses a Bitmap font made and developed by Ricoh Company, Ltd.

Setting the room temperature detection location

CAUTION As the temperature sensor of remote controller detects the temperature near the wall, when there is a certain difference between the room temperature and the wall temperature, the sensor will not detect the room temperature correctly sometimes. Especially when the outer side of the wall on which the sensor is positioned is exposed to the open air, it is recommended to use the temperature sensor of the indoor unit to detect the room temperature when the indoor and outdoor temperature difference is significant.

The detection location of the room temperature can be selected from the following 2 methods. Choose the detection location that is best for the installation location.
The temperature sensor of the indoor unit or the remote controller can be used to detect the room temperature.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-4

When the remote controller is not used, the following functions cannot be used.

Installation space

INSTALLING THE REMOTE CONTROLLER

WARNING

CAUTION

Wiring types

Single controlFujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-6

Group control
With a single remote controller, up to 16 units can be simultaneously operated.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-7

Multiple remote control
Number of connectable remote controllers. VRF: 4, RAC: 2
Multiple installation method described above is prohibited to combine 3 Wired type with 2 Wired Type.
In multiple installations, the following functions are restricted. Functions that can only be used with a Master Remote Controller:

Group control and multiple remote control can be used together.

Preparing for Installation

Strip of the remote controller cableFujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-9

Remove the front case
When opening the remote controller, remove the connector from the front case. The cables may break if the connector is not removed and the front case hangs down. When installing the front case, connect the connector to the front case. When removing and connecting the connector, be careful not to break the cables.
Release the claws (2 places) with a fl at-blade screwdriver, and separate the front case and rear case.

Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-10

Disconnect the connection cable connector from the connector of the front case PC board (printed circuit board).

Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-11

Setting the DIP switch

CAUTION Use an insulated screwdriver to set the DIP switches. Do not touch the DIP switch with your hands.

Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-12

Before using this product, always set DIP switch to “ON”. If not set, when the main power is turned on again, the set data by menu operation will be erased and cause erroneous operation.

[DIP Switch]

Installation

CAUTION Perform wiring so that water does not enter this unit along the external wiring. Always install a trap to the wiring or take other countermeasures. Otherwise it will cause trouble or electric shock or fire.

Install the rear case

A. When attaching to switch box:

Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-13

B. When attaching to the wall directly:

Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-14

C. When routing the cable on-wall:

Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-15

Connecting the remote controller cable

CAUTION When connecting a remote controller cable to the remote controller terminal block, use the specifi ed torque to tighten screws. If you over-tighten screws, they will break the terminal unit.
Be careful to avoid breaking the cable by over-tightening the cable tie.

Fasten the outside covering of the connection cable with the cable tie. Tighten the cable tie firmly so that pulling force does not propagate to the terminal connection even if force of 30 N is applied to the cable.
Select a flexible cable that can be bound using cable ties from over the cable sheath inside this unit.

Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-16

Attach the front case

Connect the remote controller cable connector to the connector of the front case PC board. Insert after adjusting upper part of front case. Otherwise, there is a risk of damage to the internal parts of this unit. When you attach the front case, make sure that the cables are not being pinched by front case.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-17

Connecting to the indoor unit

CAUTION When connecting the remote controller cable to the indoor unit, do not connect it to the outdoor unit or the power terminal block. It may cause a failure. When switching the DIP switch (SW1) on the indoor unit PC board, be sure to turn off the power supply to the indoor unit. Otherwise, the PC board of the indoor unit may be damaged.
There are 2 methods to connect the remote controller cable to the indoor unit. One is the connection using connecting cable (Included in the indoor unit), and the other is the connection the remote controller cable is connected to the exclusive terminal block of the indoor unit.
(For the details, refer to the installation manual of the indoor unit to be used.)

When connecting to the connector

  1. Use a tool to cut off the terminal on the end of the remote controller cable, and then remove the insulation from the cut end of the cable as shown in Fig. 1. Connect the remote controller cable and connecting cable as shown in Fig. 2. Be sure to insulate the connection between the cables.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-18
  2. Connect the remote controller cable to the connecting cable, and insert it to the connector. Set to “2WIRE” the DIP switch (SW1) on the PC board of the indoor unit.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-19

When connecting to exclusive terminal block

  1. Connect the end of remote controller cable directly to the exclusive terminal block. Set to “2WIRE” the DIP switch (SW1) on the PCB (printed circuit board) of the indoor unit.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-20
Tightening torque
M3 screw

(Remote controller / Y1, Y2)

4.4 to 5.3 lbf·in (0.5 to 0.6 N·m)

For “Group control” or “Multiple remote control”, refer to the following figure on how to connect to the indoor unit terminal.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-21

SETTING THE REMOTE CONTROLLER

Initialization procedure

After remote controller installation work is complete, perform initialization using the following procedures before starting to use the system.
(*: Items that indoor unit does not support are not displayed.)Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-22 Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-23

After installing this unit, perform the test run to confirm that the unit is operating properly. Then, explain the operation of this unit to the customer.

Setting of first time start

Turn on the power

CAUTION: Recheck the wiring. Incorrect wiring will cause trouble. When initially starting up this unit, the following setting screen will be displayed. Settings confi gured at this stage can be changed afterwards.

Language Setting

  1. The “Language Setting” screen has two pages. You can switch be-tween the pages by touching [Next Page] or [Previous Page]. Touch the language to be used.
    Touch [OK] to Language Setting Page 1/ 2 Language Setting Page 2/ 2 display the “R.C. English Français Deutsch Italiano Português Türkçe Master/ Slave Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-26

R.C. Master/Slave Setting

  1. (a) If the remote controller is a single connection, this setting is omitted. Proceed to “6.2.4. Data and Time Setting”.
    (b) If a remote controller has multiple connections, and if “Master” is initially set, all other units will be set to “Slave”.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-27Set only one Master remote controller. Units other than Master are set to Slave automatically.
    When remote controllers are set to “Slave”, setting items will be restricted.
    Touch [OK] to display the “Date and Time Setting” screen.

Date and Time Setting

  1. Touch the [Date] on the “Date and Time Setting” screen. The “Date” screen is displayed.
  2. Touch Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-28 to set the year, month, and date. Touch [OK] to return to the “Date and Time Setting” screen.
  3. Touch the [Time] on the “Date and Time Setting” screen. The “Time” screen is displayed.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-29
  4. Touch [ ] or [ ] to set hours, minutes, and AM/PM. Touch [OK] to return to the “Date and Time Setting” screen.
  5. Touch [OK] on the “Date and Time Setting” screen to display the “Temp. Unit Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-30

Temp. Unit Setting

  1. Select and touch [°F] or [°C] and touch [OK].
  2. Touch [OK] on the “Temp. Unit Setting” screen to display the “Password Default Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-31

Password Default Setting

  1. Select and touch [Enable] or [Disable] and touch [OK].
    The initial value at “Change Setting” of “6.3.7 Password Setting” is diff erent depending on the selection of commercial use or residential use. Refer to the table below.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-32
    Function

    (*: Items that indoor unit does not support are not displayed.)

    Enable (Commercial) Disable (Residential)
    Auto Off Timer On Off
    Weekly Timer On Off
    Set Temp. Auto Return On Off
    Set Temp. Range Setting On Off
    Anti Freeze* On Off
    Away Setting On Off
    Human Sensor Setting* On Off
    Fan Control for Energy Saving* On Off
    Initial Setting On Off
    Maintenance On Off
  2. When initial start-up setting is complete, the screen on the right will be displayed. This screen is the “Monitor mode screen”, which is the home screen of this unit.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-33

Initial setting

Configure settings required at the time of installation. This unit has two kinds of passwords; pass-word for administrators and password for installers. Password for administrators cannot be used for the settings related to the installation of this unit. Installer password can be used to configure all of setting for this unit.
When “Password (Installer Password) Verifi cation” screen is displayed, enter the password (installer password) and touch [OK]. The default password is “0000” (4 digits).Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-34

  1. Touch the [Menu] on the “Monitor Mode screen”. The “Main Menu” screen is displayed.
  2. The “Main Menu” screen has two pages. Touch [Next Page] or [Previous Page] to switch between screens. Touch the [Initial Setting].(Items that indoor unit does not support are not displayed.)Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-35
  3. The “Initial Setting” screen has three pages. Touch [Next Page] or [Previous Page] to switch between screens. Touch the items you wish to configure.
    (Items that indoor unit does not support are not displayed.)Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-36If “Lead Lag Setting” is not displayed, refer to “Lead Lag Setting” in the operation manual.

Language Setting
Touch the [Language Setting] on the “Initial Setting” screen. The “Language Setting” screen is displayed.
For the method of setting language, refer to 6.2.2. Language Setting. Select the language to be used, and touch [OK] on “Language Setting” to return to the “Initial Setting” screen.

Date Setting

  1. Touch the [Date Setting] on the “Initial Setting” screen. The “Date Setting” screen is displayed.
    Select and touch “Date and Time Setting” or “Display Format Setting”.
    When settings for all items are complete, the screen will return to the home screen. Touch [Back] to return to the “Initial Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-37

Date and Time Setting 
Touch the [Date and Time Setting] on the “Date Setting” screen. The “Date and Time Setting” screen is displayed.
For the method of confi guration, refer to 6.2.4. Date and Time Setting. Set all required items, and touch [OK] on the “Date and Time Setting” screen to return to the “Date Setting” screen.

Display Format Setting

  1. Touch the [Date Format] on the “Display Format Setting” screen. The “Date Format” screen is displayed.
  2. Select and touch the data display format. Touch [OK] on the “Date Format” screen to return to the “Display Format Setting” screen.
  3. Touch the [Time Format] on the “Display Format Setting” screen. The “Time Format” screen is displayed.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-38
  4. Select and touch the data display format. Touch [OK] on the “Time Format” to return to the “Display Format Setting” screen.
  5. Touch [OK] on the “Display Format Setting” screen to return to the “Date Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-39

Temp. Unit Setting
Touch the [Temp. Unit Setting] on the “Initial Setting” screen. The “Temp. Unit Setting” screen is displayed.
For how to confi gure, refer to 6.2.5. Temp. Unit Setting. Set temperature units and touch [OK] on the “Temp. Unit Setting” to return to the “Initial Setting” screen.

R.C. Group Name Setting
Touch the [R.C. Group Name Setting] on the “Initial Setting” screen. The “R.C. Group Name Setting” screen is displayed.

About the “R.C. Group Name Setting” screen
Touch the relevant key and enter a name. Touch [OK] to return to the “Initial Setting” screen after dis-playing the “Confi rmation screen”.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-40

RC Sensor Setting

  1. Touch the [RC Sensor Setting] on the “Initial Setting” screen. The “RC Sensor Setting” screen is displayed.
    If a remote-control sensor is used, touch [Used]. Touch [OK] to return to the “Initial Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-41

When set to [Not Used] by this setting, the following functions cannot be used: (Refer to the operation manual on the accessory CD-ROM.)

Master Indoor Unit Setting

  1. Touch the [Master Indoor Unit Setting] on the “Initial Setting” screen. The “Master Indoor Unit Setting” screen is displayed.
    To set a unit as the Master Indoor Unit, touch [Set].
  2. Touch [Yes] when the confi rmation screen is displayed to return to the “Master Indoor Unit Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-42

When changing the Master Indoor Unit, another indoor unit cannot be made the master indoor unit unless the settings of the current master indoor unit are cancelled beforehand.
(“Reset” cannot be performed while the indoor unit is operating.)

Password Setting (administrator password)
Set or change the administrator password.

  1. Touch the [Password Setting] on the “Initial Setting” screen. The “Password Setting” screen is displayed. Then touch the [Change Password] on the “Password Setting” screen. The “Change Password” screen is displayed.
  2. Enter the current password, then touch the [OK]. The default password is “0000” (4 digits).
  3. Enter the new password, then touch the [OK]. It returns to the “Password Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-43
  4. Touch the [Change Setting] on the “Password Setting” screen. The “Change Setting” screen is displayed.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-44
  5. The “Change Setting” screen is 3 or 4 pages, they can be switched by the [Previ-ous Page] or [Next Page]. Items set to be [On] require the administrator password to open the setting screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-45
    Items that indoor unit does not support are not displayed.
  6. Touch the relevant item to display the setting screen. Touch [OK] after touching [On] to return to the “Change Setting” screen. Touch [OK] on the “Change Setting” screen after setting relevant items to return to the password setting screen.
  7. Touch the [Back] on the “Password Setting”. It returns to the “Initial Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-46

Display Item Setting

Filter Sign Set to “Visible” to display icons on the “Monitor mode screen” during the indoor unit filter cleaning period.

  1. Touch the [Display Item Setting] on the “Initial Setting” screen. The “Display Item Setting” screen is displayed.
  2. Then touch the [Filter Sign] on the “Display Item Setting” screen. The “Filter Sign” screen is displayed. Touch [OK] after touching [Visible] or [Invisible] to return to the “Display Item Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-47
    Room Temp.
    Set to “Visible” to display the room temperature detected by this unit on the monitor screen.
  3. Touch the [Room Temp.] on the “Display Item Setting” screen. The “Room Temp.” screen is displayed.
  4. Touch [OK] after touching [Visible] or [Invisible] to return to the “Display Item Setting” screen.
  5. Touch the [OK] on the “Display Item Setting”. It returns to the “Initial Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-48

RC Master/Slave Setting
If multiple remote controllers are set for a remote-control group or for a single indoor unit, it is necessary to set the remote-controller master. This setting will be required at the time of initial start-up during installation. However, this setting can be changed afterwards. No master remote controllers will be automatically set to be slaves. The following functions can be used with slave remote controllers.
For the method of configuration, refer to 6.2.3. RC Master Slave Setting. Setting. Touch [OK] on the “RC Master/Slave Setting” screen after setting the temperature units to return to the “Initial setting” screen.
Do not perform “RC Master/Slave Setting” during setting or operating from the Master unit.

Deadband Setting

  1. Touch the [Deadband Setting] on the “Initial Setting” screen. The “Deadband Setting” screen is displayed. “Deadband Setting” screen is displayed. Adjust the deadband with the Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-28.
    When the [OK] is touched, the display returns to the “Initial Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-49

When the “Auto mode type” (No. 68) of the function setting on the indoor unit is set to “Dual set point”, deadband can not be set on this unit. (The Deadband Setting is not displayed.) Please set in the “Deadband value” (No. 69) of the function setting on the indoor unit.

Optimum Start Setting

  1. Touch the [Optimum Start Setting] on the “Initial Setting” screen. “Optimum Start Setting” screen is displayed. Select the [On] or [Off ].
    When the [OK] is touched, the display returns to the “Initial Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-50

I.U. Display Number Setting
At initial starting, the display numbers (Unit X) of the indoor units displayed at the “Individual VT Hold” setting of this remote controller are automatically allocated in ascending order of address value. (For the indoor unit display number (Unit X), refer to “3-2-3 Individual VT Hold” of the operation manual on the accessory CD-ROM )
The indoor units (corresponding addresses) can be rearranged in arbitrary order in which you want to correspond to the display number (Unit X) at this setting. Decide the indoor unit (address) corresponding to the display number (Unit X) by consulting the user.

  1. Touch the [I.U. Display Number Setting] on the “Initial Setting” screen.
  2. “I.U. Display Number Setting” screen is displayed. When the screen has multiple pages, they can be switched by touching the [Next Page] or [Previous Page]. The address (System-Unit) allocated to the current display number (Unit X) is displayed. The refrigeration system address (Ref.-in.) is displayed only when this remote controller is connected to a VRF system. Touch the display numbers (Unit X) whose address you want to interchange.
  3. The address selection screen is displayed. Select the address of the indoor unit you want to match to the display number selected at step 2 with Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-28.
    When [OK] is touched, the display returns to the screen of 2 and the address is interchanged with the selected display number (Unit X). Repeat steps 2 and 3 up to the desired order.
    When [Back] of the screen of 2 is touched, the display returns to the “Initial Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-51

Lead Lag Setting

NOTE:
Be sure to read the operation manual of this product for detailed operating procedures and precautions. When enabling the rotation operation, the indoor units in the RC Group take turns stopping 1 or 2 at a time.

  1. Touch the [Lead Lag Setting] on the “Initial Setting” screen. The “Lead Lag Setting” screen is displayed.
  2. The screen has 2 pages which are switched by touching the [Next page] or [Previous Page].Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-52
    Cycle Setting3.
  3. Touch the [Cycle] on the “Lead Lag Setting” screen.
  4. “Cycle” screen is displayed. Set the day by touching [ ] or [ ]. The day can be set “TEST” or from 1 day to 7 days in 1-day increments. Touch the [OK] to return to the “Lead Lag Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-53NOTE:
    When TEST is set and “Lead Lag Operation Enable/Disable” is set to “Enable”, the indoor units switch the operation/stop following the lead lag operation setting each time you press the [On/Off ] button.
    Overlap Time Setting
  5. Touch the [Over Lap Time] on the “Lead Lag Setting” screen.
  6. “Over Lap Time” screen is displayed. Set the overlap time by touching [ ] or [ ]. The overlap time can be set “None” or from 10 minutes to 30 minutes in 10 minutes increments. When selecting “None”, the Rotation operation has no overlap time. Touch the [OK] to return to the “Lead Lag Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-54
    Backup Units Setting
    Select the number of indoor units which stop simultaneously.
  7. Touch the [Backup Units] on the “Lead Lag Setting” screen.
  8. “Backup Units” screen is displayed. Touch the [2 Units] or [1 Unit]. Touch the [OK] to return to the “Lead Lag Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-55
    NOTES:
    If there are 2 connected indoor units, it is possible to set “1 Unit” only. When written as a fraction, the numerator (top) indicates the number of backups, and the denominator (bottom) indicates the total number.
    Lag Operation Setting 
    If the room temperature remains high while after starting the lead lag operation, the stopped indoor unit will start the operation.
  9. Touch the [Lag Operation] on the “Lead Lag Setting” screen.
  10. “Lag Operation” screen is displayed. Touch the [Enable] or [Disable]. Touch the [OK] to return to the “Lead Lag Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-56
    Lead Lag Operation Enable/Disable
  11. Touch the [Enable/Disable] on the “Lead Lag Setting” screen. “Enable/Disable” screen is displayed. Touch the [Enable] or [Disable].
  12. When the [OK] is touched, the lead lag operation starts or stops. The display returns to the “Lead Lag Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-57

Quit the Lead Lag Setting 
Press [Back]. If set to “Enable”, the screen will return to Monitor mode screen (Lead Lag display). If set to “Disable”, the screen will return to “Initial Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-58

Room Temp. Off set Setting

NOTES:
The following situations where uniform correction is not possible are not covered under the warranty for room temperature correction.

  1. Hold the power button for 5 seconds or more on the “Initial Setting” screen. The “Room Temp. Off set” screen is displayed. Set the correction temperature by touching Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-28. The correction temperature can be set from -8 °F to 8 °F in 1 °F increments. Touch the [OK] to return to the “Initial Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-59

Maintenance (Other Settings)

Carry out the following setting and confirmation, as required.

  1. Touch the [Menu] on the “Monitor mode screen”. The “Main Menu” screen is displayed.
  2. The “Main Menu” screen has two pages. Touch [Next Page] or [Pre-vious Page] to switch between screens. Then touch the [Maintenance]. (Items that indoor unit does not support are not displayed.)Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-60
  3. The “Maintenance” screen is displayed. The “Maintenance” screen has 3 pages. Touch [Next Page] or [Previous Page] to switch be-tween screens.
    (Items that indoor unit does not support are not displayed.)Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-61

Error History

  1. Touch the [Error History] on the “Maintenance” screen. The “Error History” screen is displayed.
    If there are 7 or more errors, you can switch between pages by touching [Next Page] or [Previous Page] Up to a maximum of 32 er-rors can be saved. Once there are more than 32 errors, the oldest one will be deleted. Touch [Back] to return to the “Maintenance” screen.
  2.  To delete the error history, touch [Erase All] and then [Yes] on the confi rmation screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-62

Setting Status List

  1. Touch the [Setting Status List] on the “Maintenance” screen. The “Setting Status List” screen is displayed.
    Touch [Next Page] or [Previous Page] to switch between screens. Touch [Back] to return to the “Maintenance” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-63

Filter Sign Reset

  1. Touch the [Filter Sign Reset] on the “Maintenance” screen. The “Filter Sign Reset” screen is displayed.
    Touch [OK] to reset the fi lter sign, and return to the “Maintenance” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-64

Version

  1. Touch the [Version] on the “Maintenance” screen. The “Version” screen is displayed. Touch [Back] to return to the “Maintenance” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-65

Test Run
Carry out a test run after completing configuration.

  1. Touch the [Test Run] on the “Maintenance” screen. The “Test Run” screen is dis-played.
    Touch [OK] to return to the “Maintenance” screen, and start the test run. The test run will automatically end in approximately 60 min.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-66

When test run is ended midway, return to the “Monitor Mode” screen and check the occupied state. When “Occupied” is displayed, press the operation button to set to “Unoccupied”. Then test run is ended. When “Unoccupied” is displayed, press the operation button once to set to “Occupied” and press it again to set to “Unoccupied”. Then test run is ended.

R.C. Address Setting

[Setting the remote controller address at the side of the indoor unit]

Checking the remote controller address

  1. Touch the [R.C. Address Setting] on the R. “Maintenance” screen. The “R.C. Address Setting” screen is displayed.
    The “Current Address” is displayed as [System-Unit]. The value for “Unit” refers to the remote controller address. Touch [Back] to return to the “Maintenance” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-67Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-68

Manual Address Setting 
Remote controller address can be manually set to any number.
[Setting the remote controller address at the side of the indoor unit]

  1. Touch the [RC Address Setting] on the “Maintenance” screen. The “R.C. Address Setting” screen is displayed.
    Touch the [Manual Addressing]. The “Manual Addressing” screen is displayed.
  2. Touch Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-28 to set the addresses of this unit. Touch [OK] to display the confi rmation screen, and touch [Yes] to return to the RC Address setting screen.
    If you wish to carry out confi guration again, touch [Address Reset] on the “R.C. Address Setting”.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-69

The address for this unit can be set from 1 to 32. However, do not set the same number as that for the remote controller address of an indoor unit connected using the same remote controller cable.

I.U. Address Verifi cation
Check the address and position of the indoor unit.

  1. Touch the [I.U. Address Verifi cation] on the “Maintenance” screen. The “I.U. Address Verifi cation” screen is displayed.
    If there are multiple pages, you can switch between them by touching [Next Page] or [Previous Page]. Touch [Check] to display the indoor unit address checking start screen.
  2. Touch [Yes] to display the confirmation screen.
  3. Select the indoor unit to be checked. If there are multiple pages, you can switch between them by touching [Next Page] or [Previ-ous Page]. The selected indoor unit will start to blow air and fl ash a LED*. (*Only when the indoor unit has the relevant functions) Touch [Back] on the confirmation screen to return to the previous screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-70
  4. Touch [Back] on the “IU Address Verification” Screen to return to the “Maintenance” Screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-71

Function Setting

This procedure changes the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit to malfunction. Perform the “Function Setting” according to the installation conditions using the remote controller.
Refer to the indoor unit installation manual for details on the function numbers and setting numbers, before the start of function setting.

  1. Touch the [Function Setting] on the “Maintenance” screen. The “Function Setting” screen is displayed.
    Touch the [Address] on the “Function Setting” screen. The “Address” screen is displayed.
  2. TouchFujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-28to select the address of the indoor units to be configured. (To set all indoor units at the same time, touch [All].) Touch [OK] to return to the Function Setting screen.
  3. Touch the [Function No.] on the “Function Setting” screen. The “Function No.” screen is displayed.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-72
  4. TouchFujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-28to set the function number. Touch [OK] to return to the “Function Setting” screen.
  5. Touch the [Setting No.] on the “Function Setting” screen. The “Set-ting No.” screen is displayed.
  6. Touch Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-28to set the setting number. Touch [OK] to return to the “Function Setting” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-73
  7. Touch [Back] to return to the “Maintenance” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-74

Display Sensor Values

  1. Touch the [Display Sensor Values] on the “Maintenance” screen. “Unit Selection” screen is displayed.
    Select the air conditioner which you want to monitor. If 4 or more air conditioners are registered, this screen has multiple pages. To switch the page, touch the [Next Page] or [Previous Page].
  2. Select the category about which you want to monitor.
  3. If you select [Sensor ID], input the ID of the monitoring item on the next screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-75
  4. Information on the selected category is displayed. When the screen has multiple pages, they can be switched by touching the [Next Page] or [Previous Page].
    When the [End] is touched, the display returns to the “Monitor Type Selection” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-76

Installer Password Change
Change the Installer password.

  1. Touch the [Installer Password Change] on the “Maintenance” screen. The “Installer Password Verifi cation” screen is displayed. Enter the current password, then touch the [OK].
    The default password is “0000” (4 digits).
  2. The “Installer Password Change” screen is displayed. Enter the new password, then touch the [OK]. It returns to the “Maintenance” screen.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-77

Initialization
Require an Installer password.

  1. Touch the [Initialization] on the “Maintenance” screen. Enter the Installer password. The “Initialization” screen is displayed.
    When the [OK] is touched, this unit restarts automatically after initialization. Perform each setting.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-78

When relocating the set remote controller, initialize it.

NOTE: If you switch to a new (diff erent) remote controller when “Lead Lag Operation” is in the “Enable” state, you must hold the power button for 5 seconds or more when the “Initialization” screen is displayed. If you do not perform this operation, the “Lead Lag Setting” menu will not be displayed. When you perform this operation, “Lead Lag Operation” will be forcibly set to “Disable”.

TEST RUN

Refer to the indoor unit installation manual.
For how to carry out a test run, refer to 6. 4. Maintenance (Other Settings) 6.4.5. Test Run.

ERROR CODES

Check the error

  1. If an error occurs, an error icon appears on the “Monitor mode screen”.
    Touch the [Status] on the “Monitor mode screen”. The “Status” screen is displayed.
  2. Touch the [Error Information] on the “Status” screen. The “Error Information” screen is displayed. (If there are no errors, the [Error Information] will not be displayed.)
  3. 2-digit numbers correspond to the error code in the table below. Touch the [Next page] (or [Previous page]) to switch to other connected indoor units.Fujitsu-UTY-RNRUZ5-Wired-Remote-Thermostat-fig-79

For the details of the indoor unit or outdoor unit error, refer to the error codes in each installation manual.

Error code Contents
CC.1 Sensor error
C2.1 Transmission PCB error
12.1 Wired remote controller communication error
12.3 Number excess of device in wired remote controller system
12.4 Wired remote controller system start-up error
26.4 Address duplication in wired remote controller system
26.5 Address setting error in wired remote controller system
15.4 Data acquisition error

Reference

Download Manual:

Fujitsu UTY-RNRUZ5 Wired Remote Thermostat Installational Manual

OTHER MANUALS

Fujitsu UTY-RNRUZ5 Wired Remote Thermostat Operational Manual

Fujitsu UTY-RNRUZ5 Wired Remote Thermostat Product Specifications Guide

Fujitsu UTY-RNRUZ5 Wired Remote Thermostat Installational Manual

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)