Emerson

EMERSON White Rodgers 1C20 Heating Only Thermostat

EMERSON-White-Rodgers-1C20-Heating Only-Thermostat

YOUR THERMOSTAT REPLACES

Description 1C20 1C26
Standard Heating & Cooling Systems – 4 or 5 wires No Yes
Standard Heat Only Systems Yes Yes
Millivolt Heat Only Systems – Floor or Wall Furnaces Yes Yes
Standard Central Air Conditioning No Yes
Gas or Oil Heat Yes Yes
Electric Furnace Yes Yes
Hydronic (Hot Water) Zone Heat – 2 Wires Yes Yes
Hydronic (Hot Water) Zone Heat – 3 Wires No No
Heat Pump (No Aux or Emergency Heat) No Yes
Heat Pump (with Aux or Emergency Heat) No No
Baseboard Electric Heating or Line Voltage (120 or 240 Volt) No No

PREPARATIONS

Assemble tools required as shown below.

EMERSON-White-Rodgers-1C20-Heating Only-Thermostat-1

Failure to follow and read all instructions carefully before installing or operating this control could cause personal injury and/or property damage

THERMOSTAT FEATURESEMERSON-White-Rodgers-1C20-Heating Only-Thermostat-2

REMOVING OLD THERMOSTAT

CAUTION
To prevent electrical shock and/or equipment damage, disconnect electrical power to the system at the main fuse or circuit breaker until installation is complete. Before removing wires from old thermostat’s switching subbase, label each wire with the terminal designation it was removed from. Some models also include an adaptor plate to cover unpainted surfaces. Thermostat wires pass through the adaptor plate center opening.

  1. Remove Old Thermostat: A standard heat/cool thermostat consists of three basic parts:
    • The cover, which may be either a snap-on or hinge type.
    • The base, which is removed by loosening all captive screws.
    • The switching subbase, which is removed by unscrewing the mounting screws that hold it on the wall or adaptor plate.
  2. Make a note here .__ ____ __, of the anticipator setting on the old thermostat for future reference and use in step 5. The heat anticipator pointer, if adjustable, will be set at one of a series of numbers representing the current rating of the primary control in your furnace. The number will be one of the following: .2, .4, .8, etc. or 0.2, 0.4, 0.8, etc.
    If no heat anticipator/indication is showing, do not be concerned; move on to the next step.

A REMOVING OLD THERMOSTAT

ATTENTION! This product does not contain mercury. Howev­er, this product may replace a unit which contains mercury.
Do not open mercury cells. If a cell becomes damaged, do not touch any spilled mercury. Wearing non-absorbent gloves, take up the spilled mercury and place into a container which can be sealed. If a cell becomes damaged, the unit should be discarded.
Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place in a suitable container. Refer to www.thermostat-recycle.org for location to send the product containing mercury.

MOUNTING AND WIRING

WARNING

1 C20 (Heat Only Two Wire): 

1 C26 (Heating and Cooling): 

WARNING For California Residents: This product contains a chemical known to the state of California to cause cancer and birth defects and other reproductive harm.
CAUTION
Take care when securing and routing wires so they do not short to adjacent terminals or rear of thermostat. Personal injury and/or property damage may occur.EMERSON-White-Rodgers-1C20-Heating Only-Thermostat-3

SET HEAT ANTICIPATOR

Set anticipator to match the setting of your old thermostat you noted in Step 3, or, the anticipator should be set to match the current rating stamped on your main heating control. The heat anticipator is adjustable from 0.15 to 1.2 amps. Adjust the anticipator by rotating the contact arm (see fig. 5). The anticipator setting is indicated by the numbers on the base that the pointer points to. If you are unsure where to set the anticipator contact the heater manufacturer for a recommended setting.EMERSON-White-Rodgers-1C20-Heating Only-Thermostat-6
Move the pointer counterclockwise to lengthen heating system cycles; move clockwise to shorten heating cycles. Adjustments should not be greater than 1 /2 marking at a time.
Snap on Cover: Carefully align the cover with the base and snap the cover onto the base.EMERSON-White-Rodgers-1C20-Heating Only-Thermostat-5

NEW THERMOSTAT OPERATION

1 C20 Heat Only – After power is turned on, slide temperature lever to desired setting. To turn heat off, slide lever all the way to the left until it clicks.
1 C26 – This thermostat is easy to operate. Fig. 6 shows how the heating/cooling system and fan operate when the switches are in various positions. After power is turned on, use the system switch to select either heating or cooling, or to turn the heating/ cooling system off. Use the fan switch to control fan operation. When the fan switch is in the AUTO position, the fan will cycle with the heating or cooling system (the fan will not run if the system switch is in the OFF position and the fan switch is in the AUTO position). When the fan switch is in the ON position, the fan will run continuously, regardless of system switch position (even if the system switch is set to OFF, the fan will run if the fan switch is in the ON position).EMERSON-White-Rodgers-1C20-Heating Only-Thermostat-7

SPECIFICATIONS

ELECTRICAL DATA

Anticipator Rating: 

THERMAL DATA: 

TROUBLESHOOTING

Symptom Possible Cause Corrective Action
No Heat/No Cool/No Fan

(common problems)

1. Blown fuse or tripped circuit breaker.

2. Furnace power switch to OFF.

3. Furnace blower compartment door or panel loose or not properly installed.

Replace fuse or reset breaker.

Turn switch to ON.

Replace door panel in proper position to engage safety interlock or door switch.

No Heat 1. Pilot light not lit.

2. Broken or melted anticipator wire.

 

 

3. Loose connection to thermostat or system.

 

4. Thermostat or heating system requires replacement or service.

 

 

 

5. System Switch not set to Heat.

Re-light pilot.

Excessive current or dead short in system. Have a qualified service person check the system before replacing thermostat.

Verify thermostat and system wires are securely attached.

Your furnace manufacturer or service person can describe how to test the heating system to verify it is operating correctly. If the heating system is capable of operation and the no heat condition persists, replace the thermostat.

Set System Switch to Heat and raise temp above room temp.

Intermittent Heat 1. Furnace Lock-Out Condition Many furnaces have safety devices that shut the system

down when a lock-out condition occurs. If the heat works intermittently contact the furnace manufacturer or local service person for assistance.

No Cool 1. Loose connection to thermostat or system.

 

2. Thermostat or cooling system requires replacement or service.

 

 

 

3. System Switch not set to Cool.

Verify thermostat and system wires are securely

attached.

Your cooling system manufacturer or service person can describe how to test the cooling system to verify it is operating correctly. If the cooling system is capable of operation and the no cooling condition persists, replace the thermostat.

Set System Switch to Cool and lower temp below room temp.

Heat, Cool or Fan Runs

Constantly

1. Possible short in wiring.

2. Possible short in thermostat

3. Possible short in heat/cool/fan system.

Check each wire connection to the thermostat to verify

it is neatly looped under the terminals.No extra wire should stick out from under the terminals.

Furnace Cycles Too Fast or

Too Slow Narrow or wide temperature swing

See Step 5, Adjusting the Anticipator. The anticipation setting is the only adjustment that

effects the heating cycle rate. If an acceptable cycle rate is not achieved using the anticipator contact a local service person for additional suggestions.The location of the thermostat, size of the Heat/Cool System and current draw can influence the cycle rate.

Cooling Cycles Too Fast or Too Slow (narrow or wide temperature swing) 1. Poor thermostat location for sensing room temperature.

2. Cooling system over or undersized.

3. Excessive Current draw influencing thermostat.

The cycle rate for cooling can not be adjusted.The location of the thermostat, size of the Cool system and current draw can influence the cycle rate. Contact a local service person for suggestions.
Thermostat Setting and

Thermostat Thermometer Disagree

1. Thermostat thermometer setting requires adjustment.

2. Thermostat setting lever requires calibration.

The thermometer can be adjusted by using a standard slotted screwdriver.Turn the thermometer pointer screw located inside the front cover to change the setting. For calibrating the setting lever contact a local heating and

cooling service person.

Adjusting Thermometer 1.Thermostat thermometer disagrees with other room thermometers. The thermometer on the thermostat is accurately calibrated at our factory but you can adjust it by using a standard slotted screwdriver.Turn the thermometer pointer screw located inside the front cover to change

the setting.

White-Rodgers is a business of Emerson Electric Co. The Emerson logo is a trademark and service mark of Emerson Electric Co.
white-rodgers.com
emersonclimate.com

Reference

Download manual: EMERSON White Rodgers 1C20 Heating Only Thermostat Installation Instructions

Emerson

EMERSON White Rodgers 1C20 Heating Only Thermostat Installation Instructions

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)