Emerson- 1F95-0680 -Non-Programmable- Thermostat -FEA

Emerson 1F95-0680 Non-Programmable Thermostat Installation Guide

Emerson logo

Emerson 1F95-0680 Non-Programmable Thermostat

Emerson- 1F95-0680 -Non-Programmable- Thermostat -PRO

SPECIFICATIONS

Electrical Rating:

  • Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . . mV to 30 VAC, NEC Class II, 50/60 Hz or DC
  • Input-Hardwire . . . . . . . . . . . . . . . . . . . . . . . . . . 20 to 30 VAC
  • Terminal Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5A per terminal, 2.5A maximum all terminals combined
  • Setpoint Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 to 99°F (7 to 32°C)
  • Differential (Single Stage) . . . . . . . . . . . . . . . . . . . . . Heat 0.6°F; Cool 1.2°F
  • Differential (Multi-Stage) . . . . . . . . . . . . . . . . . . . . . . Heat 0.6°F; Cool 1.2°F
  • Differential (Heat Pump) . . . . . . . . . . . . . . . . . . . . . . Heat 1.2°F; Cool 1.2°F
  • Operating Ambient . . . . . . . . . . . . . . . . . . . . . . . . . . 32°F to +105°F (0 to +41°C)
  • Operating Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . 90% non-condensing max.
  • Shipping Temperature Range . . . . . . . . . . . . . . . . . . -40 to +150°F (-40 to +65°C)
  • Dimensions Thermostat . . . . . . . . . . . . . . . . . . . . . . 4.2″H x 6.4″W x 1.7″D

ATTENTION: MERCURY NOTICE This product does not contain mercury. However, this product may replace a product that contains mercury. Mercury and products containing mercury must not be discarded in household trash. Do not touch any spilled mercury. Wearing non-absorbent gloves, clean up any spilled mercury and place in a sealed container. For proper disposal of a product containing mercury or a sealed container of spilled mercury, place it in a suitable shipping container. Refer to www.thermostat-recycle.org for location to send product containing mercury.

THERMOSTAT APPLICATION GUIDE

Description
Heat Pump (No Aux. or Emergency Heat) Yes
Heat Pump (with Aux. or Emergency Heat) Yes
Systems with up to 4 Stages Heat, 2 Stages Cool Yes
Heat Only Systems Yes
Millivolt Heat Only Systems – Floor or Wall Furnaces Yes
Cool Only Systems Yes
Gas or Oil Heat Yes
Electric Furnace Yes
Hydronic (Hot Water) Zone Heat – 2 Wires Yes
Hydronic (Hot Water) Zone Heat – 3 Wires Yes
Wired Remote Temperature Sensor (Indoor or Outdoor) Yes
Dual Fuel Feature (Heat Pump Mode, Outdoor Remote Required) or Damper Control Feature Yes

INSTALLATION

Remove Old Thermostat
Before removing wires from old thermostat, mark wires for terminal identification so the proper connections will be made to the new thermostat.

Installing New Thermostat

  •  Pull the thermostat body off the thermostat base. Forcing or prying on the thermostat will cause damage to the unit.
  •  Place base over hole in wall and mark mounting hole locations on wall using base as a template.
  •  Move base out of the way. Drill mounting holes. If you are using existing mounting holes and the holes drilled are too large and do not allow you to tighten base snugly, use plastic screw anchors to secure the base.
  •  Fasten base snugly to wall using mounting holes shown in Figure 1 and two mounting screws.
  •  Leveling is for appearance only and will not affect thermostat operation.
    Connect wires to terminal block on base using appropriate wiring schematic.
  •  Push excess wire into wall and plug hole with a fire resistant material (such as fiberglass insulation) to prevent drafts from affecting thermostat operation.
  •  Carefully line the thermostat up with the base and snap into place.

Battery Location
2 “AA” alkaline batteries are included in the thermostat at the factory with a battery tag to prevent power drainage. Remove the battery tag to engage the batteries. To replace batteries, set system to OFF, remove thermostat from wall and install the batteries in the rear along the top of the thermostat (see Figure 1). For best results, use a premium brand “AA” alkaline battery such as Duracell® or Energizer ®. If the home is going to be unoccupied for an extended period (over 3 months) and is displayed, the batteries should be replaced before leaving.

Power Stealing Switch

Thermostat Power Method Switch Position/Description
Battery Powered, no 24 Volt system power available. Switches “On”, thermostat runs on batteries.
Hardwired with Battery Back-up, for 24 Volt systems with common connection from transformer to “C” terminal on thermostat. Switches “On”, thermostat runs on power directly from transformer with battery back- up.
*Battery Powered with Power Stealing Assist, for 24 Volt systems with no common connection from transformer to “C” terminal on thermostat. Switches “On”, thermostat runs on batteries and supplemental power drawn through the heat or cool circuit.

The Power Stealing Switches (Figure 1, rear view) should be left in the “On” position for most systems. The information in the following table details the thermostat power method and switch options.Emerson 1F95-0680 Non-Programmable Thermostat 1

WIRING DIAGRAMS

Refer to equipment manufacturers’ instructions for specific system wiring information. After wiring, see the CONFIGURATION section for proper thermostat configuration. The wiring diagrams shown are for typical systems and describe the thermostat terminal functions.

TERMINAL DESIGNATION DESCRIPTIONS

Single Stage and Multi-Stage Connections
Refer to equipment manufacturers’ instructions for specific system wiring information. This thermostat is designed to operate a single-transformer or two-transformer system. You can configure the thermostat for use with the following systems:

  • Single stage (SS 1) gas, oil or electric.
  • Multi-stage (MS 2) gas, oil or electric.Emerson 1F95-0680 Non-Programmable Thermostat 2

Emerson 1F95-0680 Non-Programmable Thermostat 3

Heat Pump Connections
Refer to equipment manufacturers’ instructions for specific system wiring information. This thermostat is designed to operate a single-transformer or two-transformer system. You can configure the thermostat for use with the following systems:

  • HEAT PUMP TYPE 1 (HP 1). Single stage compressor system; gas or electric backup.
  • HEAT PUMP TYPE 2 (HP 2). Multi-stage compressor or two compressor system with gas or electric backup. After wiring, see INSTALLER CONFIGURATION section for proper thermostat configurationEmerson 1F95-0680 Non-Programmable Thermostat 4

THERMOSTAT QUICK REFERENCE

Home Screen Description

Battery Level Indicator Indicating the current power level of the 2 “AA” batteries: Full power remaining. Half power remaining Change The batteries should be replaced at this time with 2 new premium brand “AA” Alkaline batteries. (See page 2 for more detailsEmerson 1F95-0680 Non-Programmable Thermostat 6

Programming and Configuration Items

  • “System On” indicates when heating or cooling stage is energized. “System On +2” indicates when a second stage is energized.
  • The word “Hold” is displayed when the thermostat is in the HOLD mode. “Temp” is displayed when the thermostat is in a Temporary HOLD mode. 3 Displays “Change Filter” when the system has run for the programmed filter time period as a reminder to change or clean your filter.
  • Displays “Set” for setpoint when in Run Program mode.
  • Displays System Mode (Heat, Em, Auto, Cool, Off) or Time in menu mode.
  • Displays Fan mode (On, Auto) “Prog FAN On” or “Run Sched” in Menu mode. Displays “Run Schedule”, “Schedule”, or “Menu”. 8 Displays “Save” when Cool SavingsTM is working.
  • Displays “Heat Pump” when system is configured as Heat Pump thermostat.
  • Displays “Hold” in programmable mode when not in Hold mode. Displays Light Bulb in non-programmable mode.
  • Initially displays “Auto Sched”. If Auto Schedule had been used or disabled, then it displays “Cool Savings” when in the Cool Mode. Displays “Copy” in Schedule mode and “Fan” in Fan Schedule mode.
  • “Call For Service” indicates a diagnostic fault in the heating/cooling system, it does not indicate a fault in the thermostat.
  • “Keypad Lockout” in Menu mode when selecting keypad Lockout or in RUN when a keypad Lockout is active.

INSTALLER/CONFIGURATION MENU

INSTALLER/CONFIGURATION MENU
Menu Ref. HP SS Press Button Displayed (Factory Default) Press  or  to select from listed options Comments
1 1 1 MENU (MS 2) HP 1, HP 2, SS 1 Selects Multi-Stage (MS 2 No Heat Pump), Heat Pump 1 (HP 1, 1 compressor),

Heat Pump 2 (HP 2, 2 compressor or 2 speed compressor), or Single Stage (SS 1)

2 2 2 MENU (GAS) for SS or MS ELE GAS setting: furnace controls the blower ELE setting: thermostat controls the blower
3 3 3 MENU CS (3) 0, 1, 2, 4, 5, 6 Selects Cool Savings Value 1 (low) to 6 (high), Value 0 disables feature
4 4 4 MENU E (On) OFF Selects Energy Management Recovery (EMR) On or OFF.
5 5 MENU CR Heat (ME) SL, FA Selects Adjustable Anticipation, cycle rate, Heat (This item only appears when MS 2 or SS 1 is selected above)
6 5 MENU CR Heat Pump (ME) SL, FA Selects Adjustable Compressor Anticipation (Heat Pump) This item only appears when HP 1, HP 2 is selected above
7 6 6 MENU CR Cool (ME) or

CR AU (FA)

SL, FA SL Selects Adjustable Anticipation, cycle rate, cool (when MS 2 or SS 1 is selected above.) or Selects the cycle rate for Auxiliary stage (when HP 1 or HP 2 is selected above)
8 7 7 MENU CL (OFF) CL On Compressor Lockout Time
9 8 8 MENU Em Heat, Cool Off Heat Auto Cool Off, Heat Off with Fan icon, Heat Off without Fan icon Cool Off, Auto Off System Mode Configuration

with Automatic Changeover capability

10 9 9 MENU dL (On) dL OFF Selects Display Light On or OFF
11 10 10 MENU 0

(current temperature)

1 HI, 2 HI, 3HI, 4 HI,

1 LO, 2 LO, 3 LO, 4 LO

Adjustable Ambient Temperature Display
12 11 11 MENU °F °C Selects Fahrenheit/Celsius Temperature Display
13 12 12 MENU (On) b OFF Select Beeper OFF to stop audible

key feedback (not applicable on all models)

14 13 13 MENU P (7) 3, 0 Defaults 7-day programming (P7) but non- programmable (0) or 5/1/1 programming (P3) is available on most models.
15 14 14 MENU PS (2) 4 Selects Program periods per day: 4 = Morn, Day, Eve, Night

2 = Day, Night

16 15 15 MENU Heat AS (On) OFF Automatic Schedule for heat mode
17 16 16 MENU Cool AS (On) OFF Automatic Schedule for cool mode
18 17 MENU Heat FA (On) OFF Fast Heat option may be disabled by selecting OFF. NA to SS or HP1 config.
19 18 MENU Cool FA (On) OFF Fast Cool option may be disabled by selecting OFF. NA to SS or HP1 config.
20 19 17 MENU Remote (OFF) On Selects Remote Sensor On/OFF
MENU Remote (In) Outdoor Selects Remote Sensor to outdoor NA is Remote Sensor OFF
MENU Indoor Loc (On) OFF Selects Local Sensor (in thermostat) to OFF. N/A if Remote is selected to Outdoor
21 20 18 MENU dS (On) Off Selects Automatic Daylight Saving Time option
22 21 19 MENU (OFF)

Keypad Lockout

L, P, Limit Selects one of 3 Keypad Lockout configurations L – Total Keypad Lockout

P – Partial Keypad Lockout (Up and Keys still work)

Limit – Limited Temperature Range

MENU (000)

Keypad Lockout

1-999 Selects personal lockout code. 000 is NOT A VALID CODE.
23 22 20 MENU L Heat (99) L 62 to L 98 Select Limited HEAT Range Temperature
24 23 21 MENU L Cool (45) L 46 to L 82 Select Limited COOL Range Temperature
25 24 MENU CO (05) 06-50 Selects outdoor Compressor OFF temperature (Balance Point temperature). 05 disables fea- ture. Outdoor Remote required
MENU (dF) EA Selects between dF (dual Fuel) or EA (Electric Aux) only available if CO is greater than 05
MENU Cd (60) Selects Compressor delay OFF time in seconds (only if dF is selected)
26 25 MENU AO (80) Selects AO (Auxiliary OFF) temperature. Fea- ture disabled if 80 is selected. Outdoor Remote required
27 26 22 MENU (OFF) EC On Selects Economizer On/OFF
28 27 23 MENU (O) PP 1-3 Selects number of hours of pre-occupancy purge time (hours the Fan runs with A1 ener- gized prior to occupied period)
29 28 24 MENU Change Filter (OFF) On Selects Filter Change-out Indicator On or OFF.
MENU Change Filter (200 h) 25-1975 h Change Filter time in 25 hour increments. This menu only appears if On is selected in above.
30 29 25 MENU (OFF)

Change UV Lamp

On Selects UV Lamp Timer: On/OFF
MENU (350)

Change UV Lamp

25-1975 Selects number of Days between changing UV Lamp
31 30 26 MENU Cool On (o) Heat On (b) Selects operation of the reversing valve terminal (O/B) output as an O or B terminal
32 31 27 MENU RUN SCHED Returns to Normal Operation
  • This control can be configured for:
    • MS 2 – Multi-Stage System (no heat pump)
    • HP 1 – Heat Pump with one stage of the compressor
    • HP 2 – Heat Pump with two stage compressor or two-compressor system, Gas or Electric backup
    • SS 1 – Single Stage System 2)
  • Select Cool Savings™ value – Selects the amount of adjustment for the Cool Savings™ feature in Cool mode with 1 (1°) being the least amount of adjustment and 6 (6°) being the most amount of adjustment. Default value is 3. Cool Savings is an optional energy saving feature that can reduce your cooling costs. It is based on the principal that lower indoor humidity makes a slightly higher temperature feel more comfortable. Cool Savings operates during periods of high demand which normally occur on the hottest summer days when a cooling system may run for hours to reach the thermostat setting. Long cooling run times also lower indoor humidity. Cool Savings, very slowly, adjusts the setpoint temperature to make the setpoint closer to the displayed room temperature, to a maximum of the number of degrees you select. Adjusting the setpoint temperature over a long cooling run time allows the system to reach your set temperature and turn off. The room temperature will actually be higher than the thermostat displays but the reduction in humidity will allow comfort at the slightly higher temperature. To turn this feature on in the Cool mode press Cool Savings. The display will show “Save” next to the setpoint temperature. When Cool Savings is making adjustments to the room temperature display “Save” will be flashing and the displayed room temperature may vary within the adjustment range you selected. If “Save” is not displayed and this feature is OFF, no change will occur when the cooling system is continuously running during periods of high demand.
  • Energy Management Recovery: (this step is skipped if configured to be non-programmable). Energy Management Recovery (E) On enables the thermostat to start heating or cooling early to make the building temperature reach the program setpoint at the time you specify. Heating will start 5 minutes early for every 1° of temperature required to reach setpoint.
    Example: E On is selected and your heating is programmed to 65° at night and 70° at 7 AM. If the building
    temperature is 65°, the difference between 65° and 70° is 5°. Allowing 5 minutes per degree, the thermostat setpoint will change to 70° at 6:35 AM. Cooling allows more time per degree, because it takes longer to reach set temperature.
  • Cycle Rate Selection – The factory default setting for Heat and Cool modes, SS1, MS2, is medium cycle (ME). For Heat Pump, HP1, HP2, the default setting is medium (ME). For Emer (Aux) the default setting is fast cycle (FA). To change cycle rate, press the Emerson 1F95-0680 Non-Programmable Thermostat 9button. Cycle rate differentials for different settings are:
    • MODE Fast Medium Slow
      • FA ME SL
      • Heat (SS1, MS2) 0.4°F 0.6°F 1.7°F
      • Cool (SS1, MS2) 0.9°F 1.2°F 1.7°F
      • Heat Pump (HP1, HP2) 0.9°F 1.2°F 1.7°F
      • Emer (HP1, HP2) 0.6°F – 1.7°F
  • Select Compressor Lockout CL OFF or ON – Selecting CL ON will cause the thermostat to wait 5 minutes between cooling cycles. This is intended to help protect the compressor from short cycling. Some newer compressors already have a time delay built in and do not require this feature. Your compressor manufacturer can tell you if the lockout feature is already present in their system. When the thermostat compressor time delay occurs, it will flash the setpoint for up to five minutes.
  • System Mode Configuration – This thermostat is configured for Heat and Cool (SYSTEM switch with Cool Off Heat) default. It can also be configured for Heat and Cool with Auto changeover (Heat, Auto, Cool, Off), Heat only with fan (Off Heat), Heat only without fan, Auto only (Auto Off), and Cool only (Cool Off).
  • Select Backlight Display – The display backlight improves display contrast in low lighting conditions. When the “C” terminal is powered, selecting backlight CdL ON will keep the light on continuously. Select backlight OFF will turn the light on momentarily after any button is pressed. When the “C” terminal is not powered, the light will be on momentarily after any button is pressed no matter whether the backlight is selected ON or OFF.
  • Select Temperature Display Adjustment 4 LO to 4 HI – Allows you to adjust the room temperature display up to 4° higher or lower. Your thermostat was accurately calibrated at the factory, but you have the option to change the display temperature to match your previous thermostat. The current or adjusted room temperature will be displayed.
  • Select F° or C° Readout – Changes the display readout to Celsius or Fahrenheit as required.
  • Select Audio Prompting (Beeper) On or Off – Factory default setting is on (b, On). To turn off the beeper, select OFF. Some models do not have a beeper. This setting has no effect on models without a beeper.
  • Program Options: Selects configuration for 7 day (7) or 5/1/1 day (3) programming or non-programming (0) mode. The default setting is 7, indicating 7 day programming. The programs per week can be changed to 3 or 0 by pressing the or buttons. A selection of 0 days for non-programmable will eliminate the need for EMR, and that step in the menu will be skipped
  • Program Steps per day – This control can be configured for 4 or 2 program steps per day. Default is “2 PS” and can be toggled between 4 PS and 2 PS.
  • Select Automatic Schedule – With just one touch of the Auto Schedule key this feature allows you to program a desired comfort temperature into all the program periods along with a 6° set back for night periods of both Heat and Cool programs. Factory default is “On” for both. When Heat AS On and Cool AS On are activated while in Heat or Cool mode, select desired setpoint temperature and press Auto Schedule. This value will be copied into all the morning, day and evening program periods. The night program periods will have a 6°F setback.
  • Select Fast Second Stage ON or OFF – Heat pump or Multi-stage only, in the run mode, with the fast Heat feature enabled (FA Heat On), if the Heat setpoint temperature is manually raised by 3°F (2°C) or more above the actual temperature using the second stage will energize immediately. With FA OFF, second stage will not energize until the setpoint temperature is 1°F or more above actual temperature for more than ten minutes. The Fast Cool feature (FA Cool) provides the same controls when the setpoint temperature is lowered.
  • Select Remote Temperature Sensor – This control allows one wired remote temperature sensor (indoor, F145-1328, or outdoor, F145-1378) be connected to it and indicates the measured temperature in clock digits. This menu enables you to select the remote sensor and also configure it as indoor or outdoor temperature sensor. Factory default is off. Select Remote On and Remote in (for indoor) or Outdoor Remote.
    Local Temperature Sensor disable – This is applicable only when indoor remote temperature sensor is enabled. Factory default is Loc On. You can make it Loc Off if you desire by using or buttons. Then, only the indoor remote temperature reading will be used for control
  • Select Daylight Saving Time Calculation – This feature will allow the thermostat to calculate the DST automatically and apply it to the Real Time Clock display. Default On. Use or touch keys to select the feature OFF.
  • Keypad Lockout – This step allows you to select the type of lockout or limited range security required. If no lockout or limited-range security is required, press MENU to advance the menu. Three security settings are available in this menu item. Use the or buttons to select the lockout desired.

OPERATING YOUR THERMOSTAT

Fan Operation
If your system does not have a G terminal connection, skip to

Heating System.

  •  Turn on power to system.
  • Press fan button to select ON. The blower should begin to operate.
  • Press Emerson 1F95-0680 Non-Programmable Thermostat 9fan button to select AUTO. The blower should stop immediately.

Heating System

  • Press SYSTEM button to select Heat. If the auxiliary heating system has a standing pilot, be sure to light it.
  • Press Emerson 1F95-0680 Non-Programmable Thermostat 9to adjust thermostat setting to 1° above room temperature. The heat pump system should begin to operate.
  • The display should show “System On”. However, if the system configuration is set to HP1 or HP2 and setpoint temperature display is flashing, the 5 minute compressor lockout feature is operating (see Configuration menu, item 11).
  • Adjust temperature setting to 3° above room temperature.
  • If your system configuration is set at MS2, HP2 or HP1, the auxiliary heat system should begin to operate and the display will show “System On +2”.
  • PressEmerson 1F95-0680 Non-Programmable Thermostat 9 to adjust the thermostat below room temperature.
  • The heating system should stop operating

Emergency System

  • EM bypasses the Heat Pump to use the heat source wired to terminal W/E on the thermostat. EM is typically used when compressor operation is not desired, or you prefer back-up heat only.
  • PressEmerson 1F95-0680 Non-Programmable Thermostat 9 SYSTEM button to select EM. “EM” will flash on the display.
  • Press to adjust thermostat setting above room temperature. The Emergency heating system will begin to operate. The display will show “System On” and flashing “EM” to indicate that the Emergency system is operating.
  • Press Emerson 1F95-0680 Non-Programmable Thermostat 9to adjust the thermostat below room temperature.
  • The Emergency heating system should stop operating.

Cooling System

  • Press SYSTEM button to select Cool.
  • Press to adjust thermostat setting below room temperature. The blower should come on immediately on high speed, followed by cold air circulation. The display should show “System On”. If the setpoint temperature display is flashing, the compressor lockout feature is operating (see Configuration menu, item 5).
  • Adjust temperature setting to 3° below room temperature. The second stage cooling should begin to operate and the display should show “System On +2”.
  • Press Emerson 1F95-0680 Non-Programmable Thermostat 9to adjust the temperature setting above room temperature. The cooling system should stop operating.

Choose the Fan Setting (Auto or On)
Fan Auto is the most commonly selected setting and runs the fan only when the heating or cooling system is on. Fan On selection runs the fan continuously for increased air circulation or to allow additional air cleaning. Fan Prog On indicates that the fan is programmed to be on for the entire period. The Prog Fan On can be overridden to have the fan cycle with the system. Press the FAN button to change the fan to Auto. The fan programming will be overridden until the next program period begins or until Run Schedule is pressed

PROGRAMMING

  • Set Current Time and Day
  • Press Emerson 1F95-0680 Non-Programmable Thermostat 9Menu button to enter installer menu. Then press
  • Time button once to indicate hour & AM or PM designation in clock display.
  • Press and hold either the or button until you reach the correct hour and AM or PM designation.
  • Press Time again to display minutes only in clock display.
  • Press Emerson 1F95-0680 Non-Programmable Thermostat 9and hold either the or button until you reach the correct minutes.
  • Press Time once again to display year.
  • Press and hold either the or button until you reach the correct year
  • Press Time once again to display month.
  • Press and hold either the or button until you reach the correct month.
  • Press Time once again to display date of the month along with day of the week at top row (which is automatic).
  • PressEmerson 1F95-0680 Non-Programmable Thermostat 9 and hold either the or button until you reach the correct day of the month and day of the week is automatically calculated and displayed at the top row.
  • Press RunSched button once; now the display will show the correct time and room temperature

Energy Saving Factory Pre-Program
The 1F95-0680 thermostats are programmed with the energy saving settings shown in the table below for all days of the week. If this program suits your needs, simply set the thermostat clock and press the RunSched button. The table below shows the factory set heating and cooling schedule for all days of the week.

* Wake Up (Morn) Leave For Work (Day) * Return Home (Eve) Go To Bed (Night)
Heating Program 6:00 AM 70°F 8:00 AM 62°F 5:00 PM 70°F 10:00 PM 62°F
Cooling Program 6:00 AM 75°F 8:00 AM 83°F 5:00 PM 75°F 10:00 PM 78°F

Planning Your Program – Important

  • The Heating and Cooling Program schedules below allow you to pencil in your own program times and temperatures.
  • The 1F95-0680 comes configured for 7 day programming and can also be configured for 5+1+1 programming (see configuration section).
  • Factory settings are listed on Monday, Saturday and Sunday. If you are re-programming a 5+1+1 day schedule, pencil in your own times and temperatures directly below the factory times and temperatures.
  • If you are re-programming a 7 day schedule, fill in all lines with the times and temperatures you want.
  • Keep the following guidelines in mind when planning your program.
  • In Heating, lower temperatures will save energy.
  • In Cooling, higher temperatures will save energy.
  • If you plan on using Auto Changeover, do not program the heating temperature higher than the cooling temperature

Worksheet for Re-Programming 5+1+1 and 7 Day Program

Heating Program Wake Up (Morn)  

Fan

Leave For Work (Day)  

Fan

Return Home (Eve)  

Fan

Go To Bed (Night)  

Fan

 

MON

6:00 AM 70°F Auto 8:00 AM 62°F Auto 5:00 PM 70°F Auto 10:00 PM 62°F Auto
TUE
WED
THU
FRI
 

SAT

6:00 AM 70°F Auto 8:00 AM 62°F Auto 5:00 PM 70°F Auto 10:00 PM 62°F Auto
 

SUN

6:00 AM 70°F Auto 8:00 AM 62°F Auto 5:00 PM 70°F Auto 10:00 PM 62°F Auto
Cooling Program Wake Up (Morn)  

Fan

Leave For Work (Day)  

Fan

Return Home (Eve)  

Fan

Go To Bed (Night)  

Fan

 

MON

6:00 AM 75°F Auto 8:00 AM 83°F Auto 5:00 PM 75°F Auto 10:00 PM 78°F Auto
TUE
WED
THU
FRI
 

SAT

6:00 AM 75°F Auto 8:00 AM 83°F Auto 5:00 PM 75°F Auto 10:00 PM 78°F Auto
 

SUN

6:00 AM 75°F Auto 8:00 AM 83°F Auto 5:00 PM 75°F Auto 10:00 PM 78°F Auto

Automatic Daylight Saving Calculation
The Real Time Clock will adjust automatically for daylight savings time, in the following manner: Increment one hour at 2 AM on the second Sunday of March and decrement one hour at 2 AM on the first Sunday of November. (New DST effective 2007). The daylight saving feature can be enabled or disabled in installer configuration menu. Default is DS ON (enabled). After entering installer configuration mode, momentarily press MENU button until the display indicates dS (in actual temperature digits) and on (default – in clock digits). or buttons will toggle display and operation from on to OFF.

Programming Tip: Copy Program
When programming your thermostat, you may copy the program from one day to another day or group of days using the Copy key. In 7 day programming mode, a day can be copied to another day or all six other days. In 5/1/1 day programming mode the weekday (Mon – Fri) program can be copied into Sat and Sun or either Sat or Sun. To copy a program from one day to another:

  • In Set Schedule mode, enter the program for the day or select the day you wish to copy by pressing Advance Day.
  • Press Copy. On the display, “Copy” will begin to flash. The day of the week being copied will show.
  • Press Advance Day. The day being copied will be indicated and the other days will be flashing.
  • If you wish to copy to all days skip to next step or press Advance Day until the day you wish to copy to is flashing.
  • Press Copy. “Copy” will be on, the day you copied from will disappear and the day(s) you copied to will be on.
  • If you wish to copy this same program into other days, press Copy and repeat steps 2 through
  • Press RunSched to return to normal operation. Fill in the blank schedule on the next page then:

Enter the Heating Program

  • Press SYSTEM button to select Heat in the system switch area indicating the active mode being programmed.
  • Press the Menu button and then press Schedule.
  • The top of the display will show the day(s) being programmed. The first period to be programmed will appear. The set temperature will also be displayed and the time will be flashing to indicate that the time can be changed.
  •  Press or buttons to adjust the start time for the period. The time will change in 15 minute increments.
  •  Press the System Time button to change to the temperature flashing.
  • Press or buttons to change the temperature to your selected temperature for the first heating period.
  • After you have set the time and temperature for the first period, press Schedule to advance to the next program period.
  •  Repeat steps 4 through 7 until all of the program times and temperatures are entered for all program periods for that day.
  •  Press Schedule button to change to the next day and repeat steps 4 through 8 until all program days and periods are entered.
  • When programming is complete and all of the times and temperatures match your desired heating schedule, press RunSched. The thermostat will now run your program.

Wired Remote Temperature Sensing

One remote temperature sensor can be installed indoor or outdoor and connected to the thermostat by a maximum cable length of 100 meters (300 feet). Terminals +, S and – on the terminal block allow connection of the remote sensor. The thermostat must have 24 VAC Common connection to terminal C for the remote sensor to operate. The remote sensor can be enabled or disabled in the Installer/Configuration menu, item 20. When remote sensor, Remote, is selected Off (factory default), no remote sensor is enabled. When remote sensor is selected On, the next step is to select the remote as indoor, Remote In, or outdoor, Remote Outdoor. If the remote is selected as Remote In, an additional step will be to select if the temperature shown on the display will be from the thermostat, Loc On, or the remote sensor Loc Off. In normal operation, when a remote sensor is enabled the time digits of the display will alternate between the time and the remote temperature for three seconds each. Above the remote temperature will be “Remote”, for indoor sensor or “Outdoor Remote”, for outdoor sensor. If the remote sensor is an indoor sensor and the local display has been disabled, the temperature displayed as the room temperature will be the remote sensor temperature

Weighing of Remote Reading:
The thermostat will weight or average the temperature of the indoor remote sensor with the local sensor in the thermostat for each program period. The averaging will be active only when the local sensor and the indoor remote sensor are both functional and enabled in the Installer/Configuration menu. When the thermostat is in the Set Schedule mode, the weight of the indoor sensor will be shown in the current temperature digits of the display. The weight will show as A2 (average and default), H4 (high) or L1 (low). Pressing the or buttons at the same time will change the weight for the program period. The weight of the thermostat sensor is fixed. In normal operation of the thermostat, the current temperature displayed will be the weighted average of the local sensor and the remote sensor using the formula (local sensor weight x local sensor temperature) + (remote sensor weight x remote sensor temperature) / (local sensor weight + remote sensor weight).

Dual Fuel Temperature Setpoint
When the thermostat is configured for Heat Pump mode and an outside remote sensor is installed and enabled, the thermostat can monitor the outside temperature to determine when to switch to auxiliary heat and shut down the compressor. This eliminates the need for a fossil fuel kit. The Compressor Off temperature (CO) set in the configuration menu, item 25, will determine when the auxiliary heat will start and the compressor will shut off. Default setting is 05° (feature disabled) and can be set for 06 to 50°. When the outside temperature falls to the selected temperature, the auxiliary heat system will begin. The auxiliary heat system can be fossil fuel (dF) or electric heat (EA). This is selected after CO is set greater than 05. If the auxiliary heat is fossil fuel, (df), a delay time for the compressor shut down (Cd) can be selected. Default for this delay is 60 seconds but can be set from 0 to 99 seconds. If EA is selected, there is no selection for Cd because the compressor will shut down immediately.

TROUBLESHOOTING

Symptom Possible Cause Corrective Action
No Heat/No Cool/No Fan (common problems) 1. Blown fuse or tripped circuit breaker.

2. Furnace power switch to OFF.

3. Furnace blower compartment door or panel loose or not properly installed.

4. Loose connection to thermostat or system.

Replace fuse or reset breaker. Turn switch to ON.

Replace door panel in proper position to engage safety interlock or door switch.

Tighten connections.

No Heat 1. Pilot light not lit.

2. Furnace Lock-Out Condition. Heat may also be intermittent.

 

 

3. Heating system requires service or thermostat requires replacement.

Re-light pilot.

Many furnaces have safety devices that shut down when a lock-out condition occurs. If the heat works intermittently contact the furnace manufacturer or local HVAC service person for assistance.

Diagnostic: Set SYSTEM Switch to HEAT and raise the setpoint above room temperature. Within a few seconds the thermostat should make a soft click sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a HVAC service person to verify the heating is operating correctly.

No Cool 1. Cooling system requires service or thermostat requires replacement. Same as diagnostic for No Heat condition except set the thermostat to COOL and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling.
Heat, Cool or Fan Runs Constantly 1. Possible short in wiring.

2. Possible short in thermostat.

3. Possible short in heat/cool/fan system.

4. FAN Switch set to Fan ON.

Check each wire connection to verify they are not shorted or touching together. No bare wire should stick out from under terminal block. Try resetting the thermostat as de- scribed above. If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat/Cool system for correct operation. If the system operates correctly, replace the thermostat.
Thermostat Setting & Thermostat Thermometer Disagree 1. Thermostat thermometer setting requires adjustment. The thermometer can be adjusted +/- 4 degrees. See Temperature Display Adjustment in the Configuration Menu section.
Furnace (Air Conditioner) Cycles Too Fast or Too Slow (narrow or wide temperature swing) 1. The location of the thermostat and/or the size of the Heating System may be influencing the cycle rate. Digital thermostats provide precise control and cycle faster than older mechanical models. The system turns on and off more frequently but runs for a shorter time so there is no increase in energy use. If you would like an increased cycle time, choose SL for slow cycle in the Configuration menu, step 7 (heat) or 8 (cool). If an ac-

ceptable cycle rate is not achieved, contact a local HVAC service person for additional suggestions.

Forgot Keypad Lockout Code Press the menu button (button will disappear) and hold in for 20 seconds. This unlocks the thermostat.

White-Rodgers

REFERENCE

DOWNLOAD MANUALS

Emerson 1F95-0680 Non-Programmable Thermostat Installation Guide

Emerson logo

Emerson 1F95-0680 Non-Programmable Thermostat Installation Guide

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *