MERCURY NOTICE: This product does not contain mercury. However, this product may replace a product that contains mercury. Mercury and products containing mercury must not be discarded in household trash. Refer to www.thermostat-recycle.org for information on disposing of products containing mercury.

SPECIFICATIONS

Electrical Rating:

THERMOSTAT INSTALLATION

WIRING

Refer to equipment manufacturer’s instructions for specific system wiring information. After wiring, see INSTALLER MENU for proper thermostat configuration. Wiring table shown are for typical systems and describe the thermostat terminal functions. Wiring will change when dedicated emergency heat is on (See Installer Menu #15

Terminal Designations Terminal Function
RC Power (24V) – Cooling
RH Power (24V) – Heating
O/B

6 (not shown) – 3 wire zone valve

Reversing Valve or output for 3 wire zone valves Configurable as “O” or “B” Reversing Valve or 3 wire zone heat (power close)
Y 1st Stage Compressor (conventional or heat pump)
G Fan Relay
 

W/E

1st Stage Heat (conventional);

1st Stage Auxiliary Heat (heat pump) Can operate as Emergency Heat only (See Installer Menu #15)

C Common wire for 24V (optional with batteries)
L Heat Pump Malfunction / Diagnostic terminal (input signal requires common)
Y2 2nd Stage compressor (conventional only)
 

W2

2nd Stage Heat (Conventional)

Can operate as 1st Stage Auxiliary Heat (See Installer Menu #15)

Emerson 1F85U-22NP Non-Programmable Thermostat 1

Precautions

RC/RH Jumper Wire
This thermostat electrically connects the RC and RH terminals so a jumper wire is not required. If the application provides a separate wire for RC and RH, clip the RC/RH jumper. This will isolate both terminals so they can be independently used.
Battery Location
Premium AA alkaline batteries are required when C-wire is not available. When C-wire is available, the batteries provide a back-up source of power (this will maintain the clock in the event of a power outage).Emerson 1F85U-22NP Non-Programmable Thermostat 2

INSTALLER MENU
To prevent changes that may affect system performance, this thermostat has an INSTALLER MENU and a USER MENU. The INSTALLER MENU provides access to every option, while the USER MENU provides access to items that will not affect system performance. To access the INSTALLER MENU press the Menu button for 8 seconds. The display will show item 05 in the table below. Use Next and Back to navigate through menu items. Press Emerson 1F85U-22NP Non-Programmable Thermostat 8to change a menu setting.

Installer Menu #

(Hold Menu 8 Seconds)

Description Default Setting

(flashing icons)

Settings

(Press  Emerson 1F85U-22NP Non-Programmable Thermostat 8)

05 Outdoor Equipment: selects air conditioner (AC) or heat pump (HP) equipment as well as the number of stage  

AC2

AC0 AC1 AC2 HP1
10  

Indoor Equipment: selects whether the equipment is a gas furnace, electric furnace or fan only

 

 

EL2

FAN GA1

GA2 (conventional only)

EL1

EL2 (conventional only)

15Emerson 1F85U-22NP Non-Programmable Thermostat 9 Dedicated Emergency: W/E only operates in Emergency Aux mode. W2 becomes 1st stage Aux. Heat  

OFF

On OFF
20Emerson 1F85U-22NP Non-Programmable Thermostat 10  

O,B or 3 Wire Zone Valve Selection

 

O

O B 3
25Emerson 1F85U-22NP Non-Programmable Thermostat 11 Circulation Fan Mode: Allows user to set fan circulation time when equipment has not cycled for 1hr.  

OFF

10 minutes to 100 minutes in 5 minute increments
30Emerson 1F85U-22NP Non-Programmable Thermostat 12 Heat Cycle Rate: how often                the heat will turn on  

MEd

SLO – slow MEd – medium FAS – fast
32Emerson 1F85U-22NP Non-Programmable Thermostat 12 Aux Cycle Rate: how often the auxiliary heat will turn on  

MEd

SLO – slow MEd – medium FAS – fast
35Emerson 1F85U-22NP Non-Programmable Thermostat 12 Cool Cycle Rate: how often                 the cooling will turn on  

MEd

SLO – slow MEd – medium FAS – fast
50Emerson 1F85U-22NP Non-Programmable Thermostat 12 Compressor Lockout:

protects the compressor                        from short cycling

 

OFF

On – 5 minute delay

OFF – no delay

65 Max Heat Limit: maximum set point for heat mode 99 47 to 99
66 Minimum Cool Limit: minimum set point for cool mode 45 45 to 97
Installer Menu #

(Hold Menu 8 Seconds)

Description Default Setting

(flashing icons)

Settings

(Press  or )

79 Fahrenheit or Celsius °F °F – Fahrenheit

°C – Celsius

81 Temperature Display Adjustment: adjust the displayed “Room Temperature”  

0

 

-5 to +5

83Emerson 1F85U-22NP Non-Programmable Thermostat 6 Continuous Display Light: keep the

backlight always on – “C” wire required

OFF On – always on

OFF – momentarily

88 Auto Changeover: thermostat automatically switches between heat and cool  

OFF

On – enable auto

OFF – disable auto

99Emerson 1F85U-22NP Non-Programmable Thermostat 7 Keypad Lock: prevent unwanted changes to the thermostat OFF On – disable buttons

OFF – all buttons are active

TEST EQUIPMENT

Turn on power to the system.

Fan Operation

Heating System

Auxiliary System ( only for heat pumps with auxiliary)

THERMOSTAT OVERVIEW

Before you begin using your thermostat, you should be familiar with its features, display and the location/operation of the thermostat buttons and switches

THERMOSTAT BUTTONS AND SWITCHES THE DISPLAY
1.) Fan Button 8.) Next (Menu button) is used to navigate within a menu
2.) Away Button (set a frequently used temperature) 9.) Back (Fan button) is used to navigate within a menu
3.) System Button 10.) Exit (Away button) returns to the home screen
4.) Backlight Button (located on the top of the thermostat) 11.) Thermostat is protecting the equipment from short cycling (5-minute delay)
5.) Raises Temperature Setting 12.) Indicates that the system is running in Cool, Heat or Auxiliary mode. (Heat Pump Only -The auxiliary will run in Heat mode when the heat pump cannot maintain the set temperature.)
6.) Access Menu Options 13.) SEE TROUBLESHOOTING
7.) Lowers Temperature Setting 14.) Battery status indicator
15.) Replace battery indicator
16.) Temperature setpoint
17.) Appears when the keypad is locked (to prevent unwanted changes)

Emerson 1F85U-22NP Non-Programmable Thermostat 5

USER MENU
To customize thermostat settings, press and hold the Menu button for ½ second from the home screen. Use the Emerson 1F85U-22NP Non-Programmable Thermostat 8buttons to highlight Settings and press Next. Use Next and Back to navigate through menu items. Press Emerson 1F85U-22NP Non-Programmable Thermostat 8to change the setting.

User’s Menu # (Press Menu button and release)  

Description

Default Setting

(flashing icons)

Settings

(Press  or )

01 Fahrenheit or Celsius °F °F – Fahrenheit

°C – Celsius

02 Temperature Display Adjustment: adjust the Room Temperature  

0

 

-5 to +5

03 Continuous Display Light: keep the backlight always on – “C” wire required  

OFF

On – always on

OFF – momentarily

04 Auto-Changeover: thermostat automatically switches between heat and cool  

OFF

On – enable auto

OFF – disable auto

THERMOSTAT OPERATION

TROUBLESHOOTING

Symptom Possible Cause Corrective Action
 

 

No Heat/ No Cool/ No Fan

(common problem)

1.) Blown fuse or tripped circuit breaker

2.) Furnace power switch to OFF

3.) Furnace blower compartment door panel loose or not properly installed

4.) Loose connection to thermostat or system

1.) Replace fuse or reset breaker

 

2.) Turn switch to ON

3.) Replace door panel in proper position to engage safety interlock or door switch

 

4.) Tighten Connections

 

 

 

 

 

 

 

No Heat

1.) System not set to Heat

2.) Loose connection to thermostat or system

3.) Heating System requires service or thermostat requires replacement

1.) Set thermostat to Heat.

2.) Verify thermostat and system wires are securely

attached.

3.) Diagnostic: Set System to Heat and raise the setpoint above room temperature. Within five minutes the thermostat should make a soft click sound and “Heat On” should appear on display. This sound indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed below. If the thermostat does not click after being reset, contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating system is operating correctly.

 

 

 

 

 

No Cool

1.) System not set to Cool

2.) Loose connection to thermostat or system

3.) Cooling System requires service or thermostat requires replacement

1.) Set thermostat to Cool.

2.) Verify thermostat and system wires are securely

attached.

3.) Diagnostic: Set System to Cool and lower setpoint below room temperature. Same procedures as diagnostic for “No Heat” condition except set the thermostat to Cool and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling if the compressor lock-out option is selected in the installer menu. (see INSTALLER MENU, item 50)

 

Heat, Cool or Fan Runs Constantly

 

Possible short in wiring, thermostat, heat, cool or fan system

Check each wire connection to verify they are not shorted or touching other wires. Try resetting the thermostat. If the condition persists contact your HVAC service person.
Thermostat Display & Thermometer Disagree  

Thermostat display requires adjustment

 

Display can be adjusted +/-5°. See User Menu item

05

 

Furnace (Air Conditioner) Cycles Too Fast or Slow (narrow or wide temperature swing)

 

 

The location of the thermostat and/ or the size of the Heating System may be influencing the cycle rate

Digital thermostats provide precise control and cycle faster than older mechanical models. The system turns on and off more frequently, but runs for a shorter time. If you would like to increase cycle time, choose SLO for slow cycle in the Installer menu. (Reference menu items 30, 32 & 35.) If an acceptable cycle rate is not achieved, contact your HVAC service person.
Symptom Possible Cause Corrective Action
 

 

 

 

 

 

“Call for Service” icon appears on displayed

1.) Heating system is not able to heat the space to within 10 degrees of the setpoint within 2 hours

2.) Cooling system is not able to cool the space to within 10 degrees of the setpoint within 2 hours

3.) If “–” is displayed for the Room Temperature, a replacement thermostat is needed

4.) None of the buttons operate on the thermostat

5.) If “Call for Service” is flashing, compressor self diagnostic is detecting an issue with the

outdoor unit

1.) See corrective action for “No Heat” 2.) See corrective action for “No Cool” 3.) Replace thermostat

4.) Make sure keypad lockout is not turned on ( ), If it’s OFF, try reset shown below.

5.) Contact a service person to verify the outdoor equipment is operating correctly

WHITE REODGERS

REFERENCE

DOWNLOAD MANUAL

Emerson 1F85U-22NP Non-Programmable Thermostat Instruction Manual

Emerson logo

Emerson 1F85U-22NP Non-Programmable Thermostat Instruction Manual

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)