Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-featured

Daikin BACNET 2508034 Light Commercial Thermostat Installation Manual

Daikin logo

Daikin BACnet 2508034 Light Commercial Thermostat 

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-product

WARNING
Only personnel that have been trained to install, adjust, service or repair(hereinafter, “service”) the equipment specified in this manual should service the equipment. The manufacturer will not be responsible for any injury or property damage arising from improper service or service procedures. If you service this unit, you assume responsibility for any injury or property damage that may result. In addition, in jurisdictions that require one or more licenses to service the equipment specified in this manual, only licensed personnel should service the equipment. Improper installation, adjustment, servicing or repair of the equipment specified in this manual, or attempting to install, adjust, service or repair the equipment specified in this manual without proper training may result in product damage, property damage, personal injury or death.

Reference Documents

Number Title Company Source
DG-DAPPS BACnet™ AppStat™ Thermostat Design Guide Daikin North America LLC www.Daikinac.com

Limited Warranty

Consult your local Daikin representative for warranty details. To find your local Daikin representative, go to www.daikinac.com

General Information
This manual provides general information about BACnet thermostats. The controllers are space-mounted devices that combine a BACnet controller with temperature sensors. The controllers include programs for the following applications.

  • Rooftop units, both single or multi-stage
  • Heat pumps

The BACnet thermostats are native BACnet, Application Specific Controllers. BACnet communication parameters, device instance, MAC address, baud rate, user adjustments, and application con-figuration values are set from password-protected front panel controls. All models feature an integrated BACnet schedule and hardware real-time clock with 72-hour capacitor backup for standalone operation or network time synchronization. A two-piece mechanical design, featuring a removable backplate, facilitates easy wiring and installation.

Hazardous Information Messages

CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.
WARNING
Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided.
DANGER
Dangers indicate a hazardous situation that will result in death or serious injury if not avoided.
NOTICE
Notices give important information concerning a process, procedure, special handling or equipment attribute

User Interface

The user interface is a color display and has five push buttons. Through the menu-driven display, an operator can do the following.

  • Add or change user passwords
  • Change setpoints
  • Set BACnet addressing
  • Set up and commission the installation
  • Configure any available options

Security
Separate passwords for users and control technicians.

Display Type

  • 128 × 128 pixels
  • Active color LCD with LED backlighting
  • 1.00 × 1.04 inches (25 × 26 mm)

Inputs and Outputs
All inputs and outputs are pre-programmed and application specific. No field configuration is required for most installations. For details on input and output connections see the section Application Drawings on page 31.

Analog Inputs
Analog inputs represent BACnet analog input objects and are configured for discharge air temperature, remote temperature sensor, water temperature sensor, and fan status. Not all input sensors are applicable or required for all models.

  • Sensors are automatically detected
  • Inputs accept industry-standard 10,000Ω, Type II thermistor sensors
  • Input overvoltage protection up to 24 volts AC, continuous
  • 12-bit analog-to-digital conversion
  • Short-circuit protected
  • Loads up to 10 mA at 0-12 volts DC
  • 8-bit PWM digital-to-analog c

Relay Outputs

Relay outputs are configured to represent BACnet binary objects. The outputs control ON/OFF valves, speeds for three-speed fans, fan start circuits, or other equipment that requires an on or off input signal.

  • All relay outputs are normally open, SPST, Form “A” relays
  • 1 Ampere maximum per relay at 24 volts AC or DC for each output.
  • The maximum for all relay outputs is 3 amperes (72VA)

Connectors

  • Screw terminal block mounted to the backplate
  • Wire size 14-22 AWG

Communications – BACnet™ MS/TP

  • Integral peer-to-peer BACnet MS/TP network communications
  • Network speeds from 9600 to 76,800 baud
  • Front panel configurable device instance, MAC address, and baud
  • Automatic baud detection
  • Screw terminal block mounted to backplate; wire size 14-22 AWG
  • Meets or exceeds ANSI/ASHRAE BACnet Standard 135-2008 for Application Specific Controllers

Accuracy

  • Type Thermistor
  • Accuracy ±0.36°F (±0.2°C)
  • Resistance 10,000Ω at 77°F (25°C)
  • Operating Range 48 to 96°F (8.8 to 35.5°C)

Regulatory

  • UL 916 Energy Management Equipment
  •  FCC Class A, Part 15, Subpart B and complies with

Canadian ICES-003 Class B

  • SASO PCP Registration KSA R-103263 This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
  • This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
  • The FCC responsible party is KMC Controls, Inc., and may be contacted at 19476 Industrial Drive, New Paris, IN 46553

Environmental Limits

  • Operating 32 to 120°F (0 to 49°C)
  • Shipping -40 to 140°F (-40 to 60°C)
  • Humidity 0-95% relative humidity (non-condensing)

Installation

  • Supply Voltage
  • 24 volts AC (-15%, +20%), 50-60 Hz, 12 VA, Class 2 only, non-supervised. All circuits, including supply voltage, are power-limited circuits.
  • Weight Approx 6 ounces (170 grams)
  • Case Material Flame retardant plastic

Dimensions

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-1Table 1: BACnet Thermostat Dimension

A B C
3.50 in (89 mm) 5.12 in (130 mm) 1.12 in (29 mm)

BACnet™ Thermostat Product Numbers

Description Product Number
Roof Top Unit
Modulating or ON/OFF valves One or two-stages heat

One or two stages cooling

Fan control Economizer

 

 

2508034

Heat Pump Unit
3 heat, 2 cool

Fan Control Economizer

 

2508036

Installing the BACnet™ Thermostat

This section provides important instructions and guidelines for installing the BACnet Thermostat. Carefully review this information before installing the controllers. Mounting the BACnet Thermostat For the most accurate performance, install the BACnet Thermostat on an inside wall where it can sense the average room temperature. Avoid locations with direct sunlight, heat sources, windows, air vents, and ai  circulation or obstructions such as curtains, furniture, etc. The BACnet Thermostat must not be:

  • Mounted on an exterior wall
  • Mounted on or near an object with a large thermal mass such as a concrete block wall
  • Blocked from normal air circulation by obstructions
  • Exposed to heat sources such as lights, computers, copiers, or coffee makers, or to direct sunlight at any time of the day
  • Exposed to drafts from windows, diffusers, or returns
  • Exposed to airflow through connecting conduits or empty spaces behind walls

Rough-in Preparation
Complete rough-in wiring at each location before mounting a BACnet Thermostat. This includes the following steps.

  • Install the supplied mounting base directly to a wall, a vertical electrical box, or a box with a wall plate kit
  • Routing the connecting cable or cables from the BACnet Thermostat to the equipment it is controlling
  • Block leaks and airflow from conduits with plumber’s putty or similar material
  •  If replacing an existing thermostat, label existing wires for reference when removing the existing thermostat Figure 2: BACnet Thermostat Mounting Base DetailsDaikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-2

Installing the BACnet Thermostat

CAUTION
Can cause equipment damage. To prevent mounting screw heads from touching the circuit board in the controller, use only the mounting screw supplied by Daikin. Using screws other than the type supplied may damage the BACnet Thermostat.
To install the controller on a mounting base, do the following:

  1. Turn the Allen screw in the base of the sensor clockwise until it clears the case.
  2. Swing the BACnet Thermostat away from the mounting base to remove it.
  3. Route wiring for the BACnet Thermostat through the mounting base.
  4. Position the base with the embossed UP toward the ceiling and fasten it directly to a vertical 2 × 4-inch electrical box.
  5. Connect the wires for the BACnet Thermostat to the terminals in the mounting base.
  6. Place the top of the sensor over the top of the mounting base and swing it down over the Allen screw bracket. Be careful not to pinch any wiring.
  7. Turn the Allen screw counterclockwise until it backs out of the mounting base and engages the case.

Figure 3: Allen Head Directions

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-3

Connecting Inputs
The inputs for the BACnet™ Thermostat are configured for specific functions and do not require setup in the field. Not all inputs are required for every application.

Remote Space Temperature Sensor (optional)
Connect a 10kΩ, Type II thermistor temperature sensor to the remote space temperature (RS) input and ground (GND) terminals. The input includes the internal pull-up resistor. Follow the instructions supplied
with the sensor for installation. When a remote space temperature input is connected to the BACnet In the thermostat, the remote temperature is used instead of the internal temperature sensor.

 

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-4

Discharge Air Temperature
Connect a 10kΩ, Type II thermistor temperature probe to the discharge air temperature (DAT) input. The input includes the internal pull-up resistor. Follow the instructions supplied with the sensor for installation.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-5

Fan Status Switch (optional)
Connect a Normally Closed Fan Status switch to the Discharge Air Temperature (DAT) input and ground (GND) terminals. The input includes the internal pull-up resistor. Follow the instructions supplied
with the switch for installation.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-6

Outside Air Temperature
Connect a 10kΩ, Type II thermistor temperature probe to the outside air temperature (OAT) input. The input includes the internal pull-up resistor. Follow the instructions supplied with the sensor
for installation.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-7

Connecting Outputs

CAUTION
Can cause equipment damage. Improperly connecting loads or equipment to output terminals may damage the equipment. Connect only as shown in the following diagrams or application drawings.

The BACnet™ Thermostat outputs are product dependent and are configured for specific applications.

  •  No field programming or setup is required or possible
  • Depending on the model and application, the BACnet Thermostat outputs are designed for either 24-volt AC or 0-10 volt DC loads
  • The outputs may represent analog or digital signals

Connecting Power
The BACnet Thermostat requires an external, 24-volt AC power source. Use the following guidelines when choosing and wiring transformers.

  • Use only a Class-2 transformer of the appropriate size to supply power
  • Daikin recommends powering the BACnet Thermostat from a dedicated controls transformer
  • Connect the transformer’s neutral lead to the COM terminal
  • Connect the AC phase lead to the 24VAC terminal
  • Power is applied to the controller when the transformer is poweredDaikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-8

Maintenance

Remove dust as necessary from the holes in the top and bottom. Clean the display with a soft, damp cloth and mild soap.

User Functions

This section covers topics for the end user in a facility. BACnet™ Thermostat user functions are limited to changing the following functions.

  • Active temperature setpoints
  • Fan operation
  • Changing between heating and cooling
  • Override scheduled occupancy or occupancy based on the schedule in the BACnet Thermostat
  • Change the display between Fahrenheit and Celsius

Operating the BACnet Thermostat
BACnet Thermostat functions are accessible through a user interface consisting of simple, context-sensitive menus. The menus are opened and options are selected by using the buttons and a color display on
the front of the BACnet Thermostat.

  • Pressing either the up button ▲ or down button ▼ changes a selection, setting, or value
  •  Pressing the Enter button saves the selected setting or value. The Enter button is in the middle of the three buttons below the display
  •  Saving a selection also advances to the next displayDaikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-9

The three buttons below the display are defined by labels in the soft key bar. The buttons are designated for the following functions.

  • Back – Returns to the previous menu
  • Cncl – Cancels current changes
  •  Done – Push this button at any point while entering a value. For example, if you have entered the first two digits of a password and the remaining two digits are correct, pushing Done completes the entry of the password
  •  Enter – Pushing this button enters the selection and advances to the next step
  • Exit – Returns to the temperature display The operating modes of the BACnet Thermostat are represented by the display icons

Table 2: Operating Mode Icons

Icon Description Mode
Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-10  

The FAN icon rotates when the system fan is operational. In systems with multispeed fans the icon rotation is the same regardless of speed. When fan operation is set to automatic, the word “Auto” is placed under the icon.

 

 

Fan

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-11  

Occupied – Occupancy is set to occupied by the schedule maintained in the controller or through the network.

 

Occupancy

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-12  

Unoccupied – Occupancy is set to unoccupied by the schedule maintained in the controller or through the network.

 

Occupancy

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-13  

Override – A user has entered temperature setpoints that override the unoccupied setpoints.

 

Occupancy

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-15  

Cooling – The system will cool the space until the cooling setpoint is reached. The icon is in motion when cooling is taking place.

 

Heating/Cooling

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-14  

Heating – The system will heat the space until the heating setpoint is reached. The icon is in motion when heating is taking place.

 

Heating/Cooling

Off System is OFF. Heating/Cooling

Entering a User Password
User functions may require a password consisting of four numbers. Once a user password is entered it will remain active for 60 seconds after the last button is pushed.

Table 3: Entering a User Password

Procedure Steps Display
 

 

Starting display

 

 

Start at the temperature display

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-16
 

 

 

Enter the Level 1 password

1.     Press any button on the BACnet™ Thermostat. The display changes

to the Security User Level display.

2.     Press either the ▲ or ▼ button to change the first digit

of the password.

3.     Press the Enter button to select the next digit. Repeat for all four digits.

4.     If the password is correct, the display will advance to the first menu.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-17

Changing the Active Setpoints
To enter or change the active temperature setpoints you may need to enter a user password.
NOTE:   In the following procedure the current active setpoint – either cooling or heating – is the first setpoint to change. Once that setpoint is entered, the display advances to the next setpoint

Table 4: Changing the Active Setpoints

Procedure Steps Display
 

 

Starting display

 

 

Start at the temperature display

NOTE: The next step may require a user password.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-18
 

 

 

 

Change the active setpoints

1.      Press either the ▲ or ▼ button to change the active

temperature setpoint.

NOTE: A user password may be required after pushing the first button.

2.      Press the Enter button to save the value. The display will advance

to the next setpoint.

3.      Press the ▲ or ▼ button to change the next setpoint.

4.     Press the Enter button to save the value. The display will return to

the temperature display.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-19

 

 

Setting the Operating Modes

The operating modes set the following functions.

  • Fan operation
  • Changing between heating and cooling
  • Override scheduled occupancy or occupancy that has been set by a schedule
  • Change the display units from Fahrenheit to Celsius

Table 5: Setting the Operating Modes

Procedure Steps Display
 

 

Starting display

 

 

Start at the temperature display

NOTE: The next step may require a user password.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-20
 

 

 

 

 

 

 

Change the heating or cooling mode

1.     Push the button under the heating/cooling icon.

NOTE: If a user password has previously been entered or if the BACnet™ Thermostat has not been set up with a user password, entering a password is not required.

2.     Press either the ▲ or ▲ button to select the heating/cooling mode. The mode may be one of the following.

Emergency – (Option) Turns on the auxiliary heating in a heat

pump unit

Heat – The system will only heat the space

Cool – The system will only cool the space

Auto – The system will switch between heating and cooling

Off – The system is turned OFF

3.     Press the Enter button to save the setting. The display returns to

the temperature display.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-21

 

 

 

Heating/cooling icons

 

 

 

 

 

 

 

Set the fan mode

1. Push the button under the fan icon.

NOTE: If a user password has previously been entered or if the BACnet Thermostat has not been set up with a user password, entering a password is not required.

2.  Press the Enter button to select the next digit. Repeat for all f our digits.

3.  Press either the ▲ or ▲ button to select the fan mode from the following options.

Auto – Sets the fan to run only when there is a call for heating or cooling. The word AUTO will be placed under the fan icon

On – Sets a single speed fan to run continuously

Low, Med, High – Sets the speed at which 3-speed or modulating fans will run continuously.

4.  Press the Enter button to save the setting. The display returns to

the temperature display.

 

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-22

Fan icon

 

1-speed fan option Multi-speed fan option

Procedure Steps Display
 

 

 

 

 

 

 

 

Change the override setpoint

Entering an override setpoint can only take place if the BACnet™

Thermostat is in the unoccupied mode.

1.     Push the button under unoccupied icon .

NOTE: If a user password has previously been set up with a user

password, entering a password is not required.

2.     Press either the ▲ or ▼ button to change the first digit of the

password.

3.     Press the Enter button to select the next digit of the password.

4.     Press either the ▲ or ▼ button to turn the override ON or OFF.

Override Off – The controller uses the unoccupied setpoint as the active setpoint

Override On – The controller changes to the occupied setpoint which can then be temporarily changed

5.     Press the Enter button to save the setting.

NOTE: When the system is in the unoccupied mode, changing the active setpoint will automatically place the system in the override mode.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-23

 

 

 

 

 

 

 

Change the display units

 

 

To temporarily change the display units to either Celsius or Fahrenheit, press and hold the middle button under the display until the units change.

 

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-24

Commissioning Functions
The topics in this section are advanced topics for control technicians and engineers. These topics cover procedures for the initial BACnet™ Thermostat setup. The BACnet Thermostat commissioning functions are values and settings that are entered during the installation and commissioning of a controller and the equipment it is controlling. Typically these functions do not change after the installation and commissioning process. To set up the commissioning functions, you will need the following information.

  • Information about the equipment
  • The sequence of operation for the equipment
  • The building automation plans for controllers that are part of a network Users may change the occupied heating and cooling setpoints without accessing the commissioning functions.

NOTE:   The instructions for the BACnet Thermostat commissioning functions cover all of the functions that can be set in the controller. Not all functions are available on every model of controller.

Enter the Commissioning Mode

For access to the commissioning functions, you will need to know Password 2.

  • If the controller has not been previously set up, no password is required
  • A new Password 2 can be entered in the advanced commissioning functions

Table 6: Enter the Commissioning Mode

Procedure Steps Display
 

 

Starting display

 

 

Start from the temperature display

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-25
 

 

 

 

 

 

 

Enter the commissioning password

 

 

 

1.      Press the left and right buttons below the display at the same time and hold them until the display changes to the SECURITY USER LEVEL display.

NOTE: If Password 2 has not previously been entered, the display will change to the MAIN menu.

2.      Press either the ▲ or ▼ button to change the first digit of

Password 2.

3.      Press the Enter button to select the next digit. Repeat for all four digits. The Enter button is the middle of the three buttons below the display.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-26

 

 

 

Select a commissioning function

 

 

Access to the commissioning functions always starts at the MAIN

menu display.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-27

Setting the Commissioning Setpoints
The commissioning setpoints set the operational setpoints and limits for the BACnet™ Thermostat. Setting commissioning setpoints requires entering Password 2.

NOTE:     Not all setpoints in the following procedure are applicable to all models of BACnet Thermostat. Those setpoints are marked as (optional).

Table 7: Setting the Commissioning Setpoints

Procedure Steps Display
 

 

Starting display

 

1.     Start at the temperature display.

2.     Enter Password 2. The display changes to the MAIN menu

display.

 

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-28

 

 

 

 

 

 

 

 

 

 

Choose and set the setpoints

 

1.      From the MAIN menu, press either the ▲ or ▼ button to

select SETPOINT.

2.      Press Enter. The SETPOINT menu opens.

3.      Choose and set each of the following setpoints.

OCC COOL – The cooling setpoint that is used as the active setpoint when the system is occupied

OCC HEAT – The heating setpoint that is used as the active setpoint when the system is occupied

UNOCC COOL – The cooling setpoint that is used as the active setpoint when the system is unoccupied

UNOCC HEAT – The heating setpoint that is used as the active setpoint when the system is unoccupied

MIN COOLING – The minimum cooling setpoint that a user can select as the active setpoint

MAX HEATING – The maximum heating setpoint that a user can select as the active setpoint

DIFFERENTIAL – The minimum value between the cooling or heating setpoints. The BACnet Thermostat will always maintain this difference between setpoints

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-29

 

 

 

 

 

 

Set Up Communications
Setting BACnet™ communications properties is required only if the BACnet Thermostat is integrated into a network with other BACnet controllers. Entering the properties of the communication requires entering Password 2.

Table 8: Set Up Communications

Procedure Steps Display
 

 

Starting display

 

 

1.     Start at the temperature display.

2.     Enter Password 2. The display changes to the MAIN menu display.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-30

 

 

 

 

 

 

 

 

Change the network communication properties

 

1.      From the MAIN menu, press either the ▲ or ▼ button to select COMM.

2.      Press Enter. The COMM menu opens up.

3.      Choose and set the following properties.

DEVICE ID – This is the BACnet device instance. The device

instance must be within the range of 1 to 4,194,302.

MAC – The MAC address must be in the range of 1 – 127.

BAUD – Set to match other devices on the BACnet MS/TP network. The choices are Auto, 9600, 19200, 38400, or 76800.

NOTE: After changing a communication property the BACnet

Thermostat will reset.

NOTE: If setting up with the MicroTech Integrated System contact a Daikin representative for the appropriate values.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-31

 

 

 

 

Set the Time and Date
Setting the time and date requires entering Password 2.
NOTE:     If the BACnet™ Thermostat is connected to a BACnet network that includes a time service master, the time and date are automatically set to the network time and date.

Table 9: Set the Time and Date

Procedure Steps Display
 

 

Starting display

 

 

1.     Start at the temperature display.

2.     Enter Password 2. The display changes to the MAIN menu display.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-32

 

 

 

Select the SCHEDULE menu

1.      From the MAIN menu, press either the ▲ or ▼ button to

select SCHEDULE.

2.      Press Enter. The SCHEDULE menu opens.

3.      Choose SET CLOCK and then press Enter. The SET CLOCK

menu opens.

 

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-33

 

 

 

 

 

 

Choose a clock function to set.

Choose one of the features in the SET CLOCK menu to change the date, time, or Daylight Saving Time (DST) setting.

DATE – The current calendar date.

TIME – Time is set according to a 12-hour clock.

DST ENABLE – Set to TRUE to enable Daylight Saving Time and FALSE to use standard time year-round.

DST AUTO – When set to TRUE, the BACnet Thermostat automatically calculates the start and end dates from relative dates. For example, set DST START to the first Sunday in March instead of a calendar date.

DST START and DST END – Enter the dates and time to begin observing DST. If DST AUTO is set to TRUE the dates are relative; if set to FALSE the date is a calendar date.

 

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-34

 

Setting the Occupancy Schedule
The schedule in the BACnet™ Thermostat controls the occupancy mode. If the schedule is set to ON, the BACnet Thermostat uses the occupied setpoint as the active setpoint. If the schedule is OFF, the unoccupied setpoint is used.
NOTE: The schedule in the BACnet Thermostat is a BACnet schedule object. If the BACnet Thermostat is connected to a BACnet network the schedule can be set up with a BACnet operator workstation. Setting the occupancy schedule requires entering Password 2.

Table 10: Setting the Occupancy Schedule

Procedure Steps Display
 

 

Starting display

 

 

1.     Start at the temperature display.

2.     Enter Password 2. The display changes to the MAIN menu display.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-35

 

 

 

Select the SCHEDULE menu

 

1.      From the MAIN menu, press either the ▲ or ▼ button to

select SCHEDULE.

2.      Press Enter. The SCHEDULE menu opens.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-36
 

 

 

 

 

 

 

Choose and set a weekly schedule

1.     From the SCHEDULE menu, choose one of the following schedule

entry methods to enter a weekly schedule.

ENTIRE WEEK – Sets the schedule for all seven days of the week at one time

WEEKDAYS – Sets the schedule for Monday to Friday. Saturday and Sunday are not changed

WEEKEND – Sets the schedule for Saturday and Sunday. Monday to Friday remain unchanged

INDIVIDUAL DAYS – Sets the schedule for just the selected day

of the week

2.     Change the daily times and values in the schedule to set the

occupancy mode to either ON or OFF.

• When finished with each pair push Enter or Done

• When finished with the schedule push Exit to return to the

SCHEDULE menu.

 

 

 

 

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-37

 

 

 

 

 

 

 

Choose and set a holiday schedule

Use a holiday schedule to override the values in the weekly schedule.

Months and years can be entered as follows:

• To choose ANY as the year, select the year and push the down

arrow past the current year.

• For month, the choices are any of the twelve months of the year, ANY, EVEN, and ODD.

1.     From the SCHEDULE menu, choose HOLIDAYS.

2.     From the HOLIDAYS list, choose a holiday to edit.

3.     From the menu for the holiday, choose

DATE – Enter a single date on which the holiday schedule will

override the values of the weekly schedule

DATE RANGE – Enter a range of dates on which the values and times listed in the holiday schedule will override the values of the weekly schedule

WEEK N DAY – A day of the week and month on which the values and times listed in the holiday schedule will override the values of the weekly schedule.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-38

 

 

 

 

Set Rooftop Unit System Options

The items in the system menu control application-specific functions for rooftop units. Entering the system options requires entering Password 2.

Table 11: Set Roof Top Unit System Options

Procedure Steps Display
 

 

Starting display

 

 

1.     Start at the temperature display.

2.     Enter Password 2. The display changes to the MAIN menu display.

 

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-39

 

 

 

 

 

 

 

Choose and set the roof top system options

1.      From the MAIN menu, press either the ▲ or ▼ button to select SYSTEM.

2.      Press Enter. The SYSTEM menu opens.

3.      Choose any of the following items.

LOCAL OVRD TIME

FAN DELAY OFF

•  OCCUPIED FAN

MIN OFF TIME

•  STAGE DELAY

ECON ENABLE

MIN ECON DAMPER

ECON ENABLE TEM

•  MIN DAT

•  HEATING FAN

 

 

 

 

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-40

 

 

Set the local override time

 

From the SYSTEM menu choose LOCAL OVRD TIME to set the time the BACnet™ Thermostat will hold an override temperature

setpoint as the active setpoint. At the end of the period, the BACnet Thermostat will use either an occupied or unoccupied setpoint as the active setpoint.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-41
 

 

Set the fan delay

 

 

From the SYSTEM menu choose FAN DELAY OFF to set the time the system fan will continue to run after the last heating or cooling stage is turned OFF.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-42
 

 

Set the occupied fan control

From the SYSTEM menu choose OCCUPIED FAN to choose the following:

• When ON, the fan will run continuously when the BACnet

Thermostat schedule is ON (occupied)

• When the BACnet Thermostat schedule is OFF (Unoccupied) the

fan will run only when there is a call for heating or cooling.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-43
Procedure Steps Display
 

 

Set up staged cooling and heating

To set up staged cooling and heating do the following:

1.     From the SYSTEM menu choose MIN OFF TIME to enter the time a stage must remain turned off before it can be turned on again.

2.     From the SYSTEM menu choose STAGE DELAY to enter the time the first stage must remain turned on before the second stage can be turned on.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-44

 

 

 

 

 

 

Enable the economizer

 

To set up the economizer do the following:

1.     From the SYSTEM menu choose ECON ENABLE to enable the economizer application.

2.     From the SYSTEM menu choose MIN ECON DAMPER to set the minimum position for the economizer damper.

3.     From the SYSTEM menu choose ECON ENABLE TEM. Enter the value that the outside air temperature must fall below before the economizer damper can open.

4.     From the SYSTEM menu choose MIN DAT. Enter the minimum discharge air temperature that will be allowed during cooling when the economizer is enabled.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-45

 

 

 

 

 

 

Set heating fan control

From the SYSTEM menu choose HEATING FAN and then choose one for the following.

AUTO – The fan runs only on a call for heat.

OFF – The BACnet™ Thermostat will not command the fan to run. Typically this setting used for systems with baseboard heat or some similar split system configuration.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-46

Set Heat Pump Unit Systems Options
The items in the system menu control application-specific functions for heat pump units. Entering the system options requires entering Password 2.

Table 12: Set Heat Pump Unit Systems Options

Procedure Steps Display
 

 

Starting display

 

 

1.     Start at the temperature display.

2.     Enter Password 2. The display changes to the MAIN menu display.

 

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-47

 

 

 

 

 

 

 

 

 

Choose and set the heat pump system options

1.      From the MAIN menu, press either the ▲ or ▼ button to select SYSTEM.

2.      Press Enter. The SYSTEM menu opens.

3.      Choose any of the following items.

LOCAL OVRD TIME

FAN DELAY OFF

•  OCCUPIED FAN

•  MIN OFF TIME

•  STAGE DELAY

ECON ENABLE

MIN ECON DAMPER

ECON ENABLE TEM

MIN DAT (optional)

REV VLV PLRTY

AUX HEAT (optional)

AUX HT LOCKOUT (optional)

COMP LOCK TEMP

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-48

 

 

 

 

 

 

 

 

Set the local override time

 

From the SYSTEM menu choose LOCAL OVRD TIME to set the time the BACnet™ Thermostat will hold an override temperature setpoint as the active setpoint. At the end of the period, the BACnet Thermostat will use either an occupied or unoccupied setpoint as the active setpoint.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-49
 

 

Set the fan delay

 

 

From the SYSTEM menu choose FAN DELAY OFF to set the time the system fan will continue to run after the last heating or cooling stage is turned OFF.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-50
 

 

Set the occupied fan control

From the SYSTEM menu choose OCCUPIED FAN to choose the following:

• When ON, the fan will run continuously when the BACnet

Thermostat schedule is ON (occupied).

• When the BACnet Thermostat schedule is OFF (Unoccupied) the

fan will run only when there is a call for heating or cooling.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-51
 

 

Set up staged cooling and heating

To set up staged cooling and heating do the following:

1.     From the SYSTEM menu choose MIN OFF TIME to enter the time a stage must remain turned off before it can be turned on again.

2.     From the SYSTEM menu choose STAGE DELAY to enter the time the first stage must remain turned on before the second stage can be turned on.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-52

 

Procedure Steps Display
 

 

 

 

 

Enable the economizer

 

To set up the economizer do the following:

1.     From the SYSTEM menu choose ECON ENABLE to enable the economizer application.

2.     From the SYSTEM menu choose MIN ECON DAMPER to set the minimum position for the economizer damper.

3.     From the SYSTEM menu choose ECON ENABLE TEM. Enter the value that the outside air temperature must fall below before the economizer damper can open.

4.     From the SYSTEM menu choose MIN DAT. Enter the minimum discharge air temperature that will be allowed during cooling when the economizer is enabled.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-53

 

 

 

 

 

Set the reversing valve polarity

From the SYSTEM menu choose REV VLV PLRTY. Select one of the polarity settings.

Active Heating – The O/B output terminal is active on a call for heating.

Active Cooling – The O/B output terminal is active on a call for cooling.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-54
 

 

 

Set up auxiliary heat (Optional feature)

From the SYSTEM menu choose AUX HEAT.

Comp Lockout – The BACnet™ Thermostat will enable auxiliary heat only when the compressors are locked out because of low outside air temperature.

3rd Stage – The BACnet Thermostat uses the auxiliary heat as a

third stage of heating.

None – No auxiliary heat is enabled.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-55
 

 

Set the lockout temperature for auxiliary heat

 

 

From the SYSTEM menu choose AUX HT LOCKOUT to set the minimum outside air temperature for auxiliary heat lockout. Auxiliary heat will not operate above this temperature.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-56
 

 

Set the compressor low temperature lockout.

 

 

From the SYSTEM menu choose COMP LOCK TEMP to set the minimum outside air temperature for compressor operation. Compressors will not operate below this temperature.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-57

Advanced Options

Use the advanced options to set up the following items.

  • Choosing an application and units of
  • Adjusting the PID loops
  • Changing passwords
  • Calibrating inputs
  • Setting the display banking
  • Modifying access to users with Password

Setting the advance options requires entering Password 2.

Table 13: Advanced Options

Procedure Steps Display
 

 

Starting display

 

 

1.     Start at the temperature display.

2.     Enter Password 2. The display changes to the MAIN menu display.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-58

 

 

 

 

 

 

Choose the ADVANCED menu

1.      From the MAIN menu, press either the ▲ or ▼ button to

select ADVANCED.

2.      Press Enter. The ADVANCED menu opens.

3.      Choose any of the following functions

RESTORE APP

LOOPS

PASSWORDS

CALIBRATION

•  DISPLAY

•  KEY LOCKOUT

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-59

 

 

 

 

 

 

Reset the application and choose units of measure

 

Choose RESTORE APP from the ADVANCED menu to reset the BACnet™ Thermostat to the original configuration and settings. Use it also to change the BACnet Thermostat application program and the units of measure to display. There are two version of each application program in every BACnet Thermostat.

• The Metric version displays temperature in Celsius and uses

metric values for units of measure

• The English version displays temperature in Fahrenheit and uses English values for units of measure

NOTE: Choosing an application will reset the BACnet Thermostat.

 

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-60

 

 

 

Adjust the PID loops

 

Choose LOOPS from the ADVANCED menu to adjust the values for the cooling or heating PID loops. Only the proportional and integral properties can be changed from the display.

•  The proportional default is 2°F.

• The integral default is zero (0).

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-61
 

 

 

 

 

 

Enter or change passwords

Choose PASSWORDS from the ADVANCED menu to set either Password 1 or Password 2

• Password 1 is for a facility user and limits changes to active setpoints, fan operation, occupancy, and heating and cooling modes

• Password 2 is for a controls technician to set up and commission the BACnet Thermostat

NOTE: Entering four zeros (0000) removes the password.

The BACnet Thermostat is supplied without passwords.

1.     From the PASSWORD1 or PASSWORD2 menu press either the ▲

or ▼ button to change the first digit of the password.

2.     Press the Enter button to select the next digit. Repeat for all four digits.

3.     When the Enter button is pressed for the last digit, the new

password is saved and the display advances.

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-62

 

 

 

 

Procedure Steps Display
 

 

 

Calibrate the inputs

Choose CALIBRATION from the ADVANCED menu to calibrate an input. The BACnet™ Thermostat includes two calibration entries; one for the internal temperature sensor and one for the optional remote temperature sensor connected to the RS terminal.

Enter a calibration factor to adjust either input for

sensor inaccuracies.

• For a low input reading enter a positive correction value

• For a high input reading enter a negative correction value

 

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-63

 

 

 

 

 

Set the display blanking

 

Choose DISPLAY from the ADVANCED menu to set the display appearance after the last button is pushed.

BLANKING – Choose one of the blanking options

CLOCK – An analog clock replaces the temperature and

mode icons

BACKLIGHT OFF – The display brightness changes to the level set by DIM LEVEL after the last button interaction

NONE – The temperature and mode icons always

remain visible

DIM LEVEL – Sets the level of brightness of the display back light if BACKLIGHT OFF is the selected blanking option

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-64

 

 

 

 

 

 

 

Lockout user buttons

 

Choose KEY LOCKOUT from the ADVANCED menu to limit the accessibility to users with only Password 1, the user password.

MODE/SETPOINT – Users with Password 1 cannot change any

value or mode

MODE – Users with Password 1 cannot change the heating/ cooling, fan, or occupancy modes

NONE – Users with Password 1 have full access to active setpoints, heating/cooling, fan, and occupancy modes

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-65

Topics in this section cover the sequences of operation for the BACnet™ Thermostat. These are advanced topics for control technicians and engineers.

Room Temperature Setpoints

There are three temperature setpoints each for heating and cooling for a total of six set points.

  • Active cooling
  • Occupied cooling
  • Unoccupied cooling
  • Active heating
  • Occupied heating
  • Unoccupied heating

Types of Setpoints

Active setpoint – The active setpoint is the current setpoint. The active setpoint is determined by the following.

  • If the space is occupied, the controller uses the occupied setpoint
  • If the space is unoccupied the controller uses the unoccupied setpoint
  • A user with Password 1 can enter an active setpoint from the This change is for a limited time or until the next time the space status changes from unoccupied to occupied

Occupied setpoint – A temperature setpoint entered by the controls technician during controller setup and system commissioning. This is the setpoint used when the system is occupied which is usually controlled by the schedule in the controller.
Unoccupied setpoint – A temperature setpoint entered by the controls technician during controller setup and system commissioning. This is the setpoint used when the system is unoccupied which is usually controlled by the schedule in the controller.

Setpoint Limits

No cooling setpoint can be higher than any heating setpoint. If a user is adjusting a setpoint and it comes with the range set by Minimum Setpoint Differential, the corresponding setpoint will be changed to maintain the differential. For example, the Minimum Setpoint Differential is 4°F and the Occupied Heating setpoint is 70°F. If the user lowers the Occupied Cooling setpoint to 71°F, the controller recalculates the Occupied Heating setpoint and changes it to 67°F.

Occupancy

The BACnet Thermostat is designed to operate as a stand-alone controller and can determine occupancy based on its internal occupancy schedule. The two occupancy states of the BACnet Thermostat are Occupied and Unoccupied. An occupancy state can also be commanded by another BACnet controller on the building automation network.

Occupied

If the internal schedule is enabled, the state of the schedule is set to either occupied or unoccupied as the initial state.

Unoccupied

The unoccupied state is entered only if the internal occupancy schedule is enabled and if the schedule is inactive.

Automatic Cooling and Heating Changeover

The BACnet Thermostat can be set to automatically change between the heating and cooling modes.

  • If the space temperature rises above the active cooling setpoint, the mode is set to cooling
  • If the space temperature falls below the active heating setpoint, the mode is set to heating

Schedules

The internal occupancy schedule changes the BACnet Thermostat between the occupied (active) and unoccupied (inactive) states

PID Control Loops
A PID control loop calculates an error value from the difference between the measured room temperature and the active setpoint. The error value is expressed as a percentage and is typically used in a BAS controller to control the state of output. When the difference between the setpoint and room temperature is large, the error is large. As the system reduces the difference between the setpoint and space temperature, the error becomes smaller. In a simple example, if the output of the PID loop that is controlling a modulating valve is 50% the valve would be opened half way; if the output of the loop is 100% the valve position is fully open. The BACnet™ Thermostat heating and cooling PID loops are implemented in all models. The BACnet Thermostat uses a PID loop for the discharge air temperature. The discharge air loop controls the position of the economizer. For this loop the setpoint is the measured temperature of the air that is discharged by a rooftop or heat pump unit. The PID loops in the BACnet Thermostat are standard BACnet objects.

Staged Heating and Cooling for Rooftop and Heat Pump Units

Staged heating and cooling is used for an application other than chilled or hot water systems. Typically the BACnet Thermostat controls gas heat, electric heat, or direct expansion (DX) cooling with stage heating and cooling. Staged cooling or heating can be mixed with a modulating valve for cooling or heating.

Staged Cooling
As the demand for cooling increases, the BACnet Thermostat starts the first stage of cooling when the cooling PID loop rises above 95% and the first stage of cooling has been turned off for at least the time set by the value of MINIMUM OFF TIME. The second stage of cooling is turned on when the cooling loop rises above 99% and the first stage has been turned on for the period set by STAGE DELAY and the second stage has been turned off for at least as long as the value of MINIMUM OFF TIME. As the demand for cooling is satisfied, the second stage is turned off when the cooling PID loop drops below 50%. This first stage is turned off when the cooling loop drops below 5%.

Staged Heating
As the demand for heating increases, the BACnet Thermostat starts the first stage of heating when the heating PID loop rises above 95%. The second stage of heating is turned on when the heating loop rises above 99% and the first stage has been turned on for the period set by STAGE DELAY. As the demand for heating is satisfied, the second stage is turned off when the heating PID loop drops below 50%. This first stage is turned off when the heating loop drops below 5%.

Fan Control for Rooftop and Heat Pump Units
A user with Password 1 can set the BACnet™ Thermostat controlled fan to either run continuously or to start automatically on a call for cooling or heating.
Auto – When Auto is selected, the fan runs only when there is a call for heating or cooling. It continues to run for the period set by the fan delay timer after the call for heating or cooling.
ON – The fan will run continuously regardless of the heat/cool modes or occupied state.

Economizer Cooling for Rooftop and Heat Pump Units

Some models of the BACnet Thermostat include programming for an economizer. This programming controls an economizer outside air damper connected to the output terminal (ECON).
NOTE: The economizer can be enabled only if the outside air temperature and discharge air temperature sensor are connected to the BACnet Thermostat. The economizer mode is enabled for cooling when the outside air temperature (OAT) is 2°F below the value of the limit set by the Economizer Enable Temperature and disabled if the OAT is 2°F above the value of the Economizer Enable Temperature. Once enabled, the economizer outside air damper opens to the larger value of either the minimum damper position limit (Minimum Econ Damper) or the Discharge Air Temperature loop. The Discharge Air Temperature loop modulates from 0% to 100% as the Discharge Air Temperature rises above the Discharge Air Temperature setpoint. The Discharge Air Temperature setpoint resets between room temperature and the limit for minimum discharge air temperature as the cooling loop varies between 0 and 50%. If the Discharge Air Temperature decreases below 55°F, the Outside Air Damper returns to the minimum damper position.

Heat Pump Unit-Specific Functions

The heat pump unit fan and staging is similar to the rooftop unit fan and staging principles.

Reversing Valve Action

The BACnet Thermostat reversing valve output (O/B) is energized on a call for cooling (‘O’ function). The action can be changed from the user interface to be active on a call for heating (‘B’ function). The ‘O’ function is the default.

Auxiliary or Emergency Heat Action
The heat pump unit AUX/E output is for auxiliary or emergency heat. The operation can be configured for one of three modes.
Compressor lockout – The AUX/E output is active only on a call for heating when the compressors are locked out because the outside air temperature has dropped below the value of the Compressor OAT Low Limit. The lockout is cleared when the outside air temperature rises 2°F above the value of the Compressor OAT Low Limit.
Third stage – The AUX/E output functions as the output for a third stage of heat.
None – This function is a manual operation that can only be turned on from the user interface. When emergency heat is turned on, the AUX/E output is used to maintain the active heating setpoint and both compressor outputs are locked-out.

Rooftop Unit Applications
This section covers applications for rooftop units.

Roof Top Unit – Two-Stage Gas Heat and Two-Stage DX Cooling

  • Fan status switch (FST) and discharge air temperature (DAT) and outdoor air temperature (OAT) sensors are optional. They are typically used only when the BACnet™ Thermostat is connected to a
  • The remote temperature sensor (RS) is
  • For single-stage heating, do not connect
  • For single-stage cooling, do not connect
  • Connect outputs to 24-volt AC pilot duty
  • For additional details on connecting sensors, see Connecting Inputs on page
  • For additional details on connecting the fan and valves, see Connecting Outputs on pageDaikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-66

Heat Pump Unit Applications

This section covers applications for heat pump units.

Heat Pump Unit – Three Heat, Two Cool

  • Fan status switch (FST) and discharge air temperature sensor (DAT) are optional. They are typically used only when the BACnet™ Thermostat is connected to a
  • The outdoor air temperature sensor (OAT) is required for compressor lockout based on outside air temperature.
  • The remote temperature sensor (RS) is For a single compressor, installations do not connect If auxiliary heat is not required do not connect AUX/E.
  • Connect outputs only to 24-volt AC pilot duty For additional details on connecting sensors, see Connecting Inputs on page

Topics in this section cover integrating BACnet™ Thermostat controllers into a building automation network. These are advanced topics for control technicians and engineers. The BACnet Thermostat can function as a stand-alone controller or it can be connected to a BACnet MS/TP network. The topics in this section are reference material for control technicians or engineers that will be installing and setting up a BACnet Thermostat that is connected to a network

Connecting to a Network

Daikin-BACNET-2508034-Light-Commercial-Thermostat-Installation-Manual-fig-68

Before connecting the BACnet Thermostat to a BACnet MS/TP network, configure the network properties. See the topic Set Up Communications on page 15 for the procedure to set the following.

  • Device Instance
  • MAC address
  • Baud

Use the following principles when wiring the BACnet Thermostat to an MS/TP network:

  • Connect no more than 128 addressable BACnet devices to one MS/TP network.
  • Use 18 gauge, twisted pair, shielded cable for all network
  • Connect the (–A) terminal in parallel with all other (–)
  • Connect the (+B) terminal in parallel with all other (+)
  • Connect the shield to the earth’s ground at only one location on the network.

The controllers or devices on the physical ends of the MS/TP wiring segment must have end-of-line (EOL) termination installed for proper network operation. Set the end-of-line termination to ‘On’ using the EOL switches. A 120Ω resistor across the positive and negative communication wires will also work as an EOL termination.

Training and Development
Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on Daikin HVAC products, please visit us at www.daikinac.com and click on Training.

Warranty
Consult your local Daikin representative for warranty details. To find your local Daikin representative, go to www.daikinac.com.

Aftermarket Services
To find your local parts or service office, visit www.daikinac.com or call 855-770-5678. Daikin North America LLC reserves the right to discontinue or change at any time, specifications or designs without notice or without incurring obligations. Our continuing commitment to quality products may mean a change in specifications without notice. ©2019 Houston, Texas Printed in the USA  (855) 770-5678  www.daikinac.com

REFERENCE

Download Manual

Daikin BACnet 2508034 Light Commercial Thermostat Installation Manual

OTHER MANUALS

Daikin BACNET Light Commercial Thermostat Product Information

Daikin logo

Daikin BACnet 2508034 Light Commercial Thermostat Installation Manual

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *