Bryant A07045 Programmable Thermostat
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Follow all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wiring or installation may damage AC/HP Control. Recognize safety information. This is the safety–alert symbol . When you see this symbol on the equipment and in the instruction manual, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety–alert symbol. DANGER identifies the most
serious hazards which will result in severe personal injury or death. WARNING signifies a hazard that could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions that will result in enhanced installation, reliability, or operation.
INTRODUCTION
Bryant’s 7–day, 5/2–day, 1–day programmable and non–programmable Preferred Series Thermostat Control is a wall–mounted, low–voltage control which combines temperature and humidity control in either a single unit or a two-piece unit. In a two-piece configuration, the relays are located near the equipment and a two-wire connection is used between the Display Module and the Equipment Control Module. Single–piece installation requires more wiring and results in a higher profile. The Preferred Series Thermostat has no need for batteries to store user-configured settings in memory. During power loss, its internal memory saves settings for unlimited time, and the clock continues to run for at least 24 hours. An extension of Bryant’s proven line of thermostats; it provides separate setpoints for heating and cooling in addition to humidification and dehumidification.
In the control’s programmable configuration, different heating and cooling setpoints and times are programmable for 4 periods per day or 2 periods per day. Programming can be done for 7 days per week, 5/2 days per week, or 1 day. The programmable Thermostat Control can also be user configured as a non–programmable Thermostat Control. When operating as non–programmable, the Preferred Series Thermostat Control will still have both temperature and humidity control.
The non–programmable Thermostat Control features Touch ’N’ Got settings for quick and easy temperature changes without complicated programming schedules. The non–programmable Preferred Series Thermostat Control will still have both temperature and humidity control. And, its Touch ’N’ Go technology enables the user to switch between three different user-configurable settings through intuitive buttons located just below the display
INSTALLATION CONSIDERATIONS
Power
This control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and C terminals) of the low–voltage transformer to be connected to it for proper operation. It will not operate without these 2 connections. Rh and Rc are connected via PCB breakout jumper. See Fig. 1. For applications using two 24VAC transformers, one in the indoor unit and one in the outdoor unit, connect the common from each to the C terminal. Connect R from the indoor unit to the Rh terminal. Connect R from the outdoor unit to the Rc terminal. Then, break the jumper on the circuit board. The W and HUM signals are taken from the Rh power and the G signal is taken from the Rc power. If Thermidistat Control has been installed in a two–transformer application that is later changed to a single–transformer installation, the installer must install a field-supplied jumper between Rc and Rh. Depending on the installation, up to 14 wires may be required. Installation as the two-piece unit is recommended. Only 2 wires are required for the connection between Display Module and Equipment Control Module. These two wires (V+ and Vg) do not provide ordinary 24VAC. They carry a combination of power and communications data that is unique to these products.
Models
There are programmable and non–programmable models for all applications. They can be configured for AC or HP installations, allowing it to be used in place of all Bryant thermostats. Programmable thermostats may be configured as non–programmable if the user desires.
Outdoor Temperature Sensor
The outdoor air temperature sensor is not included with the AC/HP Control. It is available as an accessory, part number TSTATBBSEN01–B. Optimum performance is obtained when an outdoor temperature sensor is used with the AC/HP Control. Plan installation so that 2 wires can be run from the Equipment Control Module to an outdoor location, preferably on the north side of the house or refer to the Installation Instructions included with the outdoor temperature sensor for a simplified connection. The sensor can be mounted to the outdoor unit and existing dedicated sensor wires may be used for its connection. Details are provided in
sensor instructions.
Remote Indoor Temperature Sensor
A remote temperature sensor may be used with the programmable heat pump and programmable air conditioner thermostats where it is desirable to install the thermostat in a limited access location while measuring the temperature in the living space. The remote room sensor may be used as a stand-alone or average with the local sensors.
Two–Piece Thermostat Configuration
The Preferred Series AC/HP Control can be installed in one of two configurations. The control may be installed as a single–piece thermostat or it may be split into two pieces and mounted in separate locations. As a single–piece unit, all required wiring must be brought to the Equipment Control Module for connection to the terminal strip. In a two-piece configuration, the Display Module can be mounted in the living space while the Equipment Control Module may be mounted near the indoor furnace or fan coil. Connection from the display to the equipment Control Module requires only two wires. All other control wires are connected to the Equipment Control Module from the HVAC equipment. This configuration results in a slimmer display and locates the Equipment Control Module containing the switching relays away from the main living space where relay clicking will not be heard.
INSTALLATION
Carton contains the following components. See Fig. 2 for programmable models or Fig. 3 for non–programmable models.
- Display Module
- Standoff for Equipment Control Module
- Screws and pigtail
- Equipment Control Module
- Display Module
- Standoff for Equipment Control Module
- Screws and pigtail
- Equipment Control Module
AC/HP Control Location
AC/HP Control should be mounted:
- Approximately 5 ft (1.5m) from the floor.
- Close to or in a frequently used room, preferably on an inside partitioning wall.
- On a section of wall without pipes or ductwork.
AC/HP Control should NOT be mounted
- Close to a window, on an outside wall, or next to a door leading to the outside.
- Exposed to direct light or heat from a lamp, sun, fireplace, or other temperature–radiating objects which could cause a false reading.
- Close to or in direct airflow from supply registers and return–air registers.
- In areas with poor air circulation, such as behind a door or in an alcove. Installer should determine whether the control will be installed as a single–piece or two-piece. In a single–piece configuration, as many as 14 wires may need to run to the wall mounting location for connection to the control. In a two-piece configuration, the Display Module and Equipment Control Module are connected by two wires.
Install AC/HP Control
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death. Before installing AC/HP Control, turn off all power to the equipment. There may be more than 1 power disconnect
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation. Improper wiring or installation may damage AC/HP Control. Check to make sure the wiring is correct before proceeding with
installation or turning on the power.
- Turn off all power to the equipment.
- If an existing thermostat is being replaced
- Remove the existing thermostat from the wall.
- Disconnect wires from the existing thermostat, 1 at a time.
- As each wire is disconnected, record the wire color and terminal marking.
- A new or additional wire may be needed to accommodate added humidity outputs.
- Discard or recycle old thermostats
CAUTION ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental damage. Mercury is a hazardous waste. Federal regulations require that Mercury be disposed of properly
Two–Piece Installation
The following steps should be followed for the installation of the two-piece configuration.
NOTE: The 2–wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the equipment Control Module screw terminals.
- Remove the mounting plate from the back of the Display Module by pressing the two tabs on the bottom edge and pulling away. See Fig. 4 and 5.
- Route wires through a large hole in the mounting base. Level mounting base against the wall (for aesthetic value only—Display Module need not be leveled for proper operation) and mark the wall through 2 mounting holes. See Fig. 6.
- Drill two 3/16–in. mounting holes in wall where marked. The thermostat may be mounted to a standard junction box, if desired. Hole pattern on the thermostat mounting base matches the junction box mounting holes.
- Secure rear plastic mounting base to wall with 2 screws and anchors provided. Additional mounting holes are available for more secure mounting if needed. Make sure all wires extend through the hole in the mounting base.
- Adjust length and routing of each wire to reach proper connector block and terminal on the mounting base with 1/4–in. extra wire.
- Match and connect equipment wires to proper terminals of each connector block being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the thermostat mounting base. If wires are connected incorrect-ly, the Display Module will not operate. See Fig. 7, 8 and 9.
- Red is V+
- Black is Vg
- NOTE: The 2–wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the equipment Control Module screw terminals.
- S Red is V+
- S Black is Vg
- Push any excess wire into wall and against mounting base. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature and/or humidity measurement.
- Make sure to attach 2–wire pigtail to Display Module mounting base. It is packed loose in the box from the factory. Then attach 2–wire pigtail to the back of the Display Module via 2 pin, keyed connector.
- Reattach Display Module body to mounting base by first setting on at top of mounting base and then push bottom corners of Display Module to snap into place. See Fig. 10.
- Find suitable indoor mounting location for Equipment Control Module either near or on equipment. See Fig. 11.
IMPORTANT NOTE: Equipment Control Module should not be mounted to duct work or below any other controls or equipment (i.e. humidistat, humidifier, etc.). - Route wires through rear of Equipment Control Module using either a clearance hole or supplied standoff. See Fig. 12.
- Match and connect equipment wires to proper terminals of each connector block being careful not to over-tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the thermostat mounting base. If wires are connected incorrect-ly, the Display Module will not operate. See Fig. 7, 8 and 9.
- Snap cover over top of Equipment Control Module. See Fig. 13.
- 14. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2–digit code appears on large display which identifies AC/HP Control configuration. Refer to Option 33.
- AC — 1–stage air conditioner, AC, HP
- HP — 1–stage heat pump, HP only
- H — heating only system, AC, HP
- C — cooling only system, AC, HP
Single–Piece Installation
The following steps should be followed for the installation of the single–piece configuration.
- Remove cover from Equipment Control Module by pressing the two tabs on the bottom edge and pulling away. Route wires through large hole in Equipment Control Module. Level Equipment Control Module against wall (for aesthetic value only — Equipment Control Module need not be leveled for proper operation) and mark wall through 2 mounting holes.
- Drill two 3/16–in. mounting holes in wall where marked. Thermostat may be mounted to a standard junction box if desired. Hole pattern on Equip-ment Control Module matches junction box mounting holes.
- Secure rear plastic Equipment Control Module to wall with 2 screws and anchors provided. Additional mounting holes are available for more se-cure mounting if needed. Make sure all wires extend through hole in Equipment Control Module.
- Adjust length and routing of each wire to reach proper connector block and terminal on Equipment Control Module with 1/4–in. extra length. See Fig. 14.
- Match and connect equipment wires to proper terminals of each connector block.
- Push any excess wire into wall and against Equipment Control Module. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature and/or humidity measurement.
- Remove 2–wire pigtail from thermostat mounting base and attach to Equipment Control Module terminal block (terminals V+ and Vg). Attach two–wire pigtail to the back of the Display Module via 2 pin, keyed con-nector.
- Reattach Display Module body to Equipment Control Module by first setting on at top and then push bottom corners to snap into place. See Fig. 15.
- Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2–digit code appears on large display which identifies AC/HP Control configuration. Refer to Option 33.
- AC — 1–stage air conditioner, AC, HP
- HP — 1–stage heat pump, HP only
- H — heating only system, AC, HP
- C — cooling only system, AC, HP
Set AC/HP Control Configuration
Configuration options enable the installer to configure the thermostat for a particular installation. Most are not presented to the homeowner and therefore must be properly set by the installer. (Only those marked with an asterisk * below are available to the homeowner.) The homeowner configurations are described in the owner’s manual. A special procedure allows entry into the configuration mode. While in configuration mode, up to 29 selections can be made. A description of each selection and how to use the configuration mode follows.
CONFIGURATION OPTIONS — SUMMARY
- Option 01 — Equipment Type
- Option 02 — Clean Filter Timer Adjustment
- Option 03* — Fahrenheit/Centigrade Selection
- Option 04 — Fan (G) on with W/W1 Selection
- Option 05 — Room Air Temperature Sensing (programmable models only)
- Option 06 — Cooling Lockout Below 55_F Selection (only available if outdoor air sensor is present)
- Option 07 — Zoning
- Option 08 — Auxiliary Heat Lockout Temperature Setting (only available when heat pump is used and when outdoor air temperature sensor is present)
- Option 10 — Reversing Valve
- Option 11 — Adjustable Setpoint Deadband
- Option 12 — Smart Recovery (programmable models only) Option 13 — Room Temperature Offset Adjustment
- Option 15 — Enable Auto Mode
- Option 16 — Cycles Per Hour
- Option 17 — Time Between Stages
- Option 18* — Backlight Configuration
- Option 19 — Dry Contact (programmable models only) Option 20 — Outdoor Air Temperature Offset Adjustment Option 21* — Keypad Lockout
- Option 24* — Programmable/Non–Programmable (programmable models only)
- Option 25* — Number of Programmable Periods per Day (programmable models only)
- Option 26 — Minimum Cooling Setpoint
- Option 27 — Maximum heating Setpoint
- Option 28 — UV Light Reminder
- Option 29 — Humidifier Pad Reminder
- Option 30* — Programmable Fan (programmable models only)
- Option 31* — Daylight Savings Time Configuration (programmable models only)
- Option 32 — Furnace Heat Staging
- Option 33 — Single or Two–Piece Installation
- Option 99 — Reset to Factory Defaults
TO ENTER CONFIGURATION MODE
Press and hold FAN button for approximately 10 sec. The Display Module is now in configuration mode. It will automatically exit this mode if no button is pressed for 3 minutes. Pressing either FAN or DONE button will exit configuration mode immediately.
WHILE IN CONFIGURATION MODE
The option number is displayed in the heat setpoint location and the configuration setting is displayed in the cool setpoint location. On the T6–PAC/PHP (programmable) models, a box will surround the option number. The mode button is used to move the box between the two displayed values. The soft keys below the listed values may also be used to move the box between selected values. The value inside the box is changed by using the UP/DOWN buttons. On the T6–NAC/NHP (non–programmable) models, one of the values will be flashing. The mode button is used to change which value is flashing or the Home and Sleep buttons may also be used to select which value to flash. The value that is flashing is changed by using the UP/Down buttons. All changes made are saved at the time of selection and will be saved in the event of the 3 minute time–out or when installer exits from configuration menu.
Configuration Options —Selection
- Option 01 — Equipment Type
- HP model — Range: HP, AC, H, C.24
- AC model — Range: AC, H, C.
HP — operates a single–speed heat pump with a fan coil.
AC — operates a single–speed AC.
H — operates a heat–only system. Furnace or fan coil only;
no outdoor unit.
C — operates a cool only–system. Outdoor AC unit with an
indoor fan coil with no strip heaters. Defaults
HP model defaults to HP.
AC model defaults to AC.
Option 02 — Clean Filter Timer
Select hours of blower operation (heating, cooling, or fan) before CHECK FILTER icon is displayed. With OF selected, icon will never come on, disabling this feature. Time selection can range from 800 to 7200 hr by selecting numbers 1 through 9. (Time is 800 X number selected.) Default is 4 (3200 hr). Recommended selections are disposable filter–800 to 2400 hr, media filter–2400 to 3200 hr, or electronic air cleaner–1600 to 2400 hr of blower operation. For higher efficiency filter, please consult filter’s Installation Instruction for details.
Option 03 — Fahrenheit/Centigrade
Select between Fahrenheit (F) and Centigrade (C) operation. Factory default is Fahrenheit (F).
Option 04 — Fan (G) On With W/W1
This selection determines whether fan (G) output is to be On or OFF when any W/W1 (furnace or strip heat) output is On. Most furnaces and fan coils manage their own blowers and do not require separate G signal. For these applications, select OFF. Some auxiliary heaters require separate G signal to turn on blower. In this case, select On.
Default is OF (off).
Option 05 — Room Air Temperature Sensing (programmable models only)
This selection determines which sensor the control will use for measuring room air temperature. Room air temperature can be sensed in one of three ways; the local sensor (L) located on the Display Module, the remote room air sensor (r), or the average of local and remote sensors (Lr). Settings are L, r, Lr.
Default is L.
Option 06 — Cooling Lockout Below 55_F
This selection disables cooling when outdoor temperature is below 55_F. It requires an outdoor temperature sensor. Setting is not available if valid outdoor sensor is not connected. Set to OF (off) to allow cooling below 55_F. Set to On to prevent cooling below 55_F.
Factory default is OF (off).
Option 07 — Zoning
This selection should be set to On when the thermostat is to be used as part of a zoning system. It is assumed that the zoning equipment will take care of time guard and cycle timers. The minimum on time is still controlled by the thermostat. Default is OF (off).
Option 08 — Auxiliary Heat Lockout Temperature
This selection is available on heat pump systems with a valid outdoor temperature sensor connected. Available settings are: Off, 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55. OF (off) — function is disabled. Auxiliary heat is allowed to operate whenever sufficient demand for heat is available. 5–55_F — Outdoor temperature above which the auxiliary heat is not allowed to operate (unless MODE is set to Emergency Heat).
Default is OF (off).
Option 10 — Reversing Valve
This selection is only available on heat pump systems. “O” terminal can be configured to be energized in either heating mode or in cooling mode, depending on heat pump operation. “O” is used to describe a heat pump system that energizes its reversing valve in cooling. “B” is used to describe a heat pump system that energized its reversing valve in heating.
H — Reversing valve output (O/W2/B) is energized when HEAT mode is selected.
C — Reversing valve output (O/W2/B) is energized when COOL mode is selected. Default is C.
Option 11 — Deadband Setting Between Heat & Cool
This option is not available on Heat Only and Cool Only systems. This selection is to allow the installer to choose how much differential exists between the heating and cooling setpoints. Allowable selections are 1–6.The default is 2.
Option 12 — Smart Recovery
Smart Recovery OF (off) means setpoints change precisely at setback recovery time. Thirty, 60, or 90 selects the number of minutes recovery starts before programmed recovery time. Recovery takes place smoothly during the selected recovery time, ending at the recovery time and temperature which is programmed. Not available with non–programmable thermostats or when thermostat is configured as non–programmable.
Default is 90.
Option 13 — Room Air Temperature Offset Adjust
The number of _F to be added to the displayed temperature to calibrate or deliberately miscalibrate the measured room temperature ( –5 to +5_F). Default is 0.
Option 15 — Enable Auto Mode
This selection is not available if the thermostat is configured as Heat Only or Cool Only in Option 1. This allows the homeowner to select auto changeover mode in addition to heat and cool. This allows the thermostat to automatically change between heating mode and cooling mode when sufficient demand for heating or cooling exists.
On — Auto mode is available.
OF — Auto mode is not available.
Default is On.
Option 16 — Maximum Cycles Per Hour
This selection limits the number of cycles per hour that the thermostat allows the system to operate. Selections are 2, 4, 6.
2 — The heating and cooling outputs will be energized no more than 2 times per hour. When an output is energized, it will not be energized again for 30 minutes.
4 — The heating and cooling outputs will be energized no more than 4 times per hour. When an output is energized, it will not be energized again for 15 minutes
6 — The heating and cooling outputs will be energized no more than 6 times per hour. When an output is energized, it will not be energized again for 10 minutes.
Default is 4.
Option 17 — Time Between Equipment Stages
This selection is only available for heat pump systems. This determines the minimum number of minutes of equipment operation on the highest compressor stage before allowing the transition to auxiliary heat. Available selections are 10, 15, 20, and 25. The time between stages of any individual piece of equipment, such as low speed and high speed compressor or fan coil stages, will be fixed at 10 minutes.
Default is 15.
Option 18 — Backlight Configuration
When OF (off), the backlight will be lit for 10 seconds after a button is pressed. After 10 seconds of no button presses, the backlight turns off. When On, the backlight will normally be on and dim in appearance. The backlight brightness becomes brighter when a button is pressed. After 10 seconds of no button presses, the backlight will return to the dimmer level until another button press occurs. The range of brightness is 1 through 5 with 5 being full brightness.
The default is 3.
Option 19 — Dry Contact Configuration (programmable models only)
There are 2 available selections, OF and 1.
OF — The dry contact is always de-energized.
1 — The dry contact will be energized for the specified number of minutes per hour. This selection is programmable by period. When this selection is changed from OF to 1, the period icons are shown and the minute segments of the clock display are shown. The triangle icon next to the WAKE period will be on and a value between 0 and 60 will be shown in the minute’s display. See Operational Information and Wiring Diagrams for further explanation of dry contact configuration and use. To change the period or minutes, press the soft key below the period or minutes and then use the UP/DOWN buttons to change to the desired value. Default is OF (off).
Option 20 — Outdoor Air Temperature Offset Adjustment
This selection allows the calibration, or deliberate miscalibration of the outdoor air temperature sensor reading. The selection ranges from –5 to +5_F.
Default is 0.
Option 21 — Keypad Lockout (programmable models only)
This selection allows the installer to limit access to the keypad. Selections are OF (off), 1, 2, 3.
OF (off) — The user has full access to the keypad.
1 — The user has access to modify setpoints, time of day.
2 — The user has access to change the setpoints only.
3 — The entire keypad is locked. When a button is pressed, the backlight will turn on but none of the operating parameters will be changed.
When the keypad lock selection is turned on, the padlock icon will be displayed. To unlock the keypad, press and hold the UP/DOWN buttons simultaneously for five seconds. When the keypad is unlocked, the padlock icon will turn off. The keypad will remain unlocked for two minutes after the last button press. After two minutes with no button presses, the keypad will lock again. The keypad will not lock in the software configuration mode or in the installer test mode. Default is OF (off).
Option 21 — Keypad Lockout (non–programmable models only)
This selection allows the installer to limit access to the keypad. Selections are OF (off), 1, 2.
OF (off) — The user has full access to the keypad.
1 — The user has access to change the setpoints.
2 — The entire keypad is locked. When a button is pressed, the backlight will turn on but none of the operating parameters will be changed.
When the keypad lock selection is turned on, the padlock icon will be displayed. To unlock the keypad, press and hold the UP/DOWN buttons simultaneously for five seconds. When the keypad is unlocked, the padlock icon will turn off. The keypad will remain unlocked for two minutes after the last button press. After two minutes with no button presses, the keypad will lock again. The keypad will not lock in the software configuration mode or in the installer test mode. Default is OF (off).
Option 24 — Programmable/Non–Programmable
This selection allows the installer to configure the thermostat as either programmable or non–programmable. Selections are P, nP.
Default is P (programmable models only).
Option 25 — Number of Programmable Periods
This selection allows the installer to configure the thermostat for two or four periods per day. Two periods is a common commercial application and four periods is more common for residential. This selection is not available if Option 24 has been set to nP to configure the thermostat for non–programmable operation. 2 — Periods DAY and SLEEP are available 4 — Periods WAKE, DAY, EVE, and SLEEP are available.
Default is 4.
Option 26 — Minimum Cooling Setpoint
This selection allows the installer to configure the minimum cooling setpoint that the user is allowed to set. The range is based on the value of the adjustable deadband Option 11, such that the minimum of the range is 50_Fplusthe adjustable deadband and the maximum is 90_F.
The default is 52_F (based on the adjustable deadband default = 2).
Option 27 — Maximum Heating Setpoint
This selection allows the installer to configure the maximum heating setpoint. The range is based on the adjustable deadband value Option 11, such that the minimum of the range is 50_F and the maximum is 90_F minus the headband. Default is 88_F (based on the adjustable deadband default = 2).
Option 28 — UV Light Reminder
This selection allows the installer to select the number of months after which the UV Light icon will be displayed to indicate to the homeowner that it is time to call the dealer to have the UV Lights replaced. Selections available are OF (off), 6, 12, 18, 24, 30, 36, 42, 48.
OF (off) — The UV Light reminder is turned off and will never be displayed.
6–48 — The number of months after which the UV Light reminder will be displayed, “CHECK UV LIGHT”. The default is OF (off).
Option 29 — Humidifier Pad Reminder
This selects the number of months after which the Humidifier Pad Reminder icon will be displayed. This is not based on run time.OF (off) — The Humidifier Pad Reminder is disabled and will never be displayed.
1–24 — The number of months after which the Humidifier Pad Reminder icon will be displayed, “CHECK HUM PAD”. Default is OF (off).
Option 30 — Programmable Fan (programmable models only)
This selection allows the homeowner to program the fan selection to “Auto” or “On” fan operation for each of the program schedule periods. This selection is only available on programmable models.
OF (off) — Programmable fan is disabled and the homeowner must manually select “Auto” or “On” for fan operation.
On — Programmable fan is enabled. The homeowner can program “Auto” or “On” fan operation along with the heat and cool setpoints for each programmed period. When the program schedule is running, the programmed heat setpoint, cool setpoint, and fan selection for that period will be used. If the homeowner “overrides” the programmed fan setting by pressing the fan button, the override selection will remain in effect until the next programmed period time. Default is OF (off).
Option 31 — Daylight Savings Time Configuration (programmable models only)
This selection allows the installer to set the thermostat to automatically change by one hour on the specified day, month, and week specified. OF (off) — Daylight Savings Time Function disabled. 1,2 On — The first time the UP/DOWN button is pressed, the value of this selection changes from OF (off) to 1. When 1 is displayed, the days of the week and clock digits will be turned on. The installer will set the start date (Spring) for Daylight Savings Time by setting the day of the week by selecting the appropriate triangle icon next to the days of the week, the month of the year will be set in the clock hours location (range 1–12) and the week of the month will be set in the clock minutes location. The week of the month selections will be F, 2, 3, 4, and L for First, 2nd, 3rd, 4th, and Last. So for the first Sunday in April, the display would show SUN, 4, F. When 2 is displayed, the installer will then choose the end date for daylight savings time (Fall). To activate the function, the installer changes the “2” by pressing the up button and “On” is displayed. The setting shall be left “On” to enable the Daylight Savings Time function. Default is OF (off).
Option 32 — Furnace Heat Staging Control
(available only when the HP thermostat is configured to operate AC equipment).
1 — The thermostat controls W1 output only and furnace controls the turn on and turn off of higher stages of heat.
2 — The thermostat will control the W1 and O/W2/B outputs. Default is 1.
Option 33 — Single or Two–Piece Installation
This configuration allows the thermostat to compensate for the amount of heat generated by the thermostat electronics to allow more accurate sensing of the temperature sensor. The amount of heat compensation will be different between single installation and two-piece installation.
Range: 1P or 2P
1P — The installation is single piece.
2P — The installation is two separate pieces. Default is 2P
Option 99 — Reset to Factory Defaults
Use this capability to reset the stat to “out of the box” conditions. BEWARE! All configuration settings, program settings, clock, and calendar which have been manually entered will be lost! When this option is selected, the configuration number (99), will appear on the left and 10 will appear on the right. To perform the reset, first use the MODE key to move the box from the 99 to the 10 (programmable model) or to flash the 10 (non–programmable model). Then press and hold the DOWN key. The 10 will start counting down toward zero. If the DOWN key is kept pressed until the count reaches zero, the reset will be performed. When the value reaches zero, the heat setpoint shall display —-. The cool setpoint shall display — and the room air temperature shall display Fd. When the factory defaults have been restored, the thermostat will act as if power was cycled and return to normal operation. If the DOWN key is released early, the number will return to 10 and the reset will not occur.
SYSTEM START-UP AND CHECKOUT
The AC/HP Control is designed with a built-in installer test capability. It allows easy operation of equipment without delays or setpoint adjustments to force heating or cooling. To enable installer test mode, press and hold the fan button for 15 seconds. After 10 seconds, the thermostat will enter Configuration Mode. Continuing to hold the Fan button through 15 seconds will cause the thermostat to enter Installer Test Mode. Pressing the Mode button will change the system operating mode to test the heating and cooling equipment. Auto Mode is not available during Installer Test Mode. If no buttons are pressed for 15 minutes, the installer test mode will be terminated. Pressing DONE at any time will exit installer test mode.
Heat — The first stage of heating will be energized for three minutes, then the first and second stages (if a second stage exists) will turn on for an additional three minutes. During the first stage of heating, the HEAT ON icon will be displayed. The “auxiliary heat on” icon will be displayed if the second stage is electric heat (HP unit type). For heat pump installation, only 1 stage of auxiliary heat is available. Any staging of auxiliary heat must be managed by the furnace or fan coil. At the end of the equipment cycle the MODE will return to OFF. The display will count down from 180 seconds to 0 for each stage when the equipment is energized. The test of a heating or cooling cycle can be terminated before the timer expires by pressing the MODE button and changing the system mode to OFF. Installer test for cooling is the same as described for heating above. COOL ON will be displayed during cooling in Installer Test Mode. In a heat pump application, when the mode is set to “em heat” the auxiliary heat will turn on for 3 minutes. The clock display will count down from 180 to 0 during this test.
TO TEST FAN
Fan button switches FAN icon between AUTO and On. While On is displayed, G output will be energized, turning fan on. Allow up to 10 sec after button is pressed for fan to turn on and off. On some fan coils, fan continues to operate for 90 sec after G signal is removed.
Final Settings
Be sure to press DONE to exit installer setup mode. If the system is to be left in operation after installation is complete, use MODE button to select between HEAT, COOL, or AUTO to provide desired operation of heating, cooling, or auto. On the programmable models, the default setpoints and programmed schedule conform to the Energy Starr requirements of the U.S. Department of Energy for both heating and cooling. These provide energy-saving temperature settings. Refer to Table 1.
Table 1 – Energy Star Default Schedule
SCHEDULE | HEAT | COOL |
Wake 6:00 AM | 68_F | 78_F |
Day 8:00 AM | 60_F | 85_F |
Evening 5:00 PM | 68_F | 78_F |
Sleep 10:00 PM | 60_F | 82_F |
If the programmed schedule is to be used, make sure the triangle icon next to the FOLLOW SCHEDULE icon is turned on. Pressing the Schedule button will cycle the triangle icon through the FOLLOW SCHEDULE, HOLD and VACATION selections.If fixed temperatures are desired, use SCHEDULE button to turn on arrow icon next to HOLD. This will maintain setpoints, not allowing them to change with programmed schedule.
The FAN button may be used to select between AUTO (fan on only with equipment) and On (fan on continuously) fan modes. For further information on temperature selection and programming, refer to Homeowner’s Guide. Setting The Clock, Calendar, Daily Schedule, and Vacation Settings (programmable models only) To set the clock, press the SET button once. The Clock will be displayed at the bottom center of the screen. Use the soft keys to move the box around the digits to be set and the UP/DOWN buttons to change the setting. Concurrent presses of the set button will cycle through the calendar, daily schedule, and vacation settings. Calendar may be changed by using the soft keys to select the Month, Day, or Year. The UP/DOWN buttons are used to change the Month, Day, or Year setting when the box surrounds it. Day of the week (Mon–Sun) is determined by calendar settings and is not directly adjustable. When changing daily schedule settings, the soft keys are used to set the days, period times, heating setpoints, and cooling setpoints. The UP/DOWN buttons are used to change the setting with the box around it. ALL PROGRAM PERIODS (WAKE, DAY, EVE, SLEEP) MUST OCCUR WITHIN THE SAME 24 HOUR PERIOD. When changing Vacation settings, the soft keys are used to choose the selection to be adjusted and the UP/DOWN buttons are used to change the setting
Vacation (programmable models only)
A vacation selection is available specifically for times where the home will not be occupied for an extended period. Vacation mode has an automatic hold, meaning that setpoints are not affected by the programmed schedule. Vacation mode is active for a specified period of time. While in vacation mode, the system provides temperature protection for the home in the selected mode, but not comfort. When vacation mode is active, an arrow will be displayed beside “VACATION” in the upper left corner of the display.
Vacation Setpoints
A special set of temperature setpoints exist which are active in vacation mode. They are adjustable by the homeowner, are exclusively for vacation mode, and are remembered from one vacation selection to the next. See Table 2 for default values.
Table 2 – Vacation Setpoints Default Values
MODE | AUTO |
Fan | Auto |
Heat Setpoint | 55 |
Cool Setpoint | 85 |
OPERATIONAL INFORMATION
Timers
Five–Minute Compressor Timeguard This timer prevents the compressor from starting unless it has been off for at least 5 minutes. It can be overridden for 1 cycle by simultaneously pressing FAN and UP buttons.
Cycle Timer
Based on the selection of 2, 4, or 6 cycles per hour, this timer is set to 30, 15, or 10 minutes. This much time must elapse from the start of one cycle before another cycle can start. It serves to impose the cycles per hour limits. It can be defeated for one cycle by simultaneously pressing the FAN and UP buttons.
Ten-Minute Staging Timer
In multistage heating or cooling, this timer prevents any higher stage from turning on until the preceding stage has been on for 10 minutes. When staging between compressor and electric heat or between compressor and furnace heat, the time is configurable. The timer is configurable via Option 17. This timer is overridden if the temperature error is greater than 5_F (usually due to a large change in desired temperature) and equipment stages up in 60-second intervals.
Defrost
Detection of defrost will not work properly if the installer has configured the O/W2/B output to function as a B output. During heat pump heating, a defrost signal shall be considered valid if the compressor output is energized and the defrost signal has been active for less than 15 consecutive minutes. Any defrost signal present for longer than 15 minutes shall be considered invalid.
Heat pump/fan coil systems shall use this input to:
- Detect that defrost is in progress and energize the auxiliary heat to provide homeowner comfort during the defrost cycle
- Allow a defrost cycle to run to completion regardless of the system demand
Three–Minute Minimum on Time
In normal operation, when a stage turns on, it will not turn off for a minimum of 3 minutes. If the setpoint is changed, this timer is canceled, allowing the equipment to turn off immediately when the demand is removed.
Heat/Cool Setpoints (Desired Temperature)
A minimum difference of 1_F and maximum of 6_F is enforced between heating and cooling desired temperatures. This is done by allowing 1 setting to “push” the other, to maintain this difference. This difference is adjustable via Configuration Option 11.
Equipment On Indicators
When cooling equipment is on, a COOL ON icon is displayed. While cooling equipment operation is delayed by the timeguard or cycle timer, COOL ON will flash. Thesameistruefor HEAT ON.
During second stage compressor operation a “2” will be displayed with the HEAT ON or COOL ON icon. This is displayed when the thermostat is configured as H2, A2, or h2.
When the W is energized in a heat pump or Hybrid Heat system, the auxiliary heat on icon will be displayed.
Auto Changeover
When auto changeover mode is selected, a change from heat to cool (or vice versa) will not occur until an opposite mode demand has existed for 20 minutes. If setpoint is changed, 20–minute requirement is deleted.
Emergency Heat Mode
When AC/HP Control is configured as a heat pump and emergency heat is selected, all Y signals are locked out, and W becomes energized upon a call for heat.
Programmable Fan (programmable models only)
The fan output can be programmed based on period of the day. When programming for each day and period the fan can be set to On or AUTO.
Dry Contact
On the programmable models, the dry contact that can be used for control of an auxiliary device. The dry contact may be configured to be closed for a specific number of minutes per hour for each period of the program schedule. This can be used to operate a ventilator, damper, system blower, or another auxiliary device. There are two terminals, D1 and D2. If it is desired to operate a ventilator or other device, the D1 and D2 terminals can be connected directly to the equipment. This will provide a closed contact for the specified number of minutes per hour. See Option 19. If timed control of the system blower is required, the dry contact can be used for this function. The G terminal can be connected to one of the dry contact terminals with the other terminal being connected to Rc and/or Rh for timed control of the fan. Note that this is not the same as the programmable fan Option 30. See Wiring Diagrams for more information
TROUBLESHOOTING
If the display module doesn’t power up after power is applied, check the Rc/Rh and C terminals for 24VAC. If 24VAC is present, check the voltage between Vg and V+. This voltage will be approximately 12–20VDC. If voltage is present, check the polarity to make sure it is wired correctly. The display will not power up if polarity is reversed.
Error Codes
“—-” — If AC/HP Control cannot properly read room temperature, display will indicate “—-” and all outputs (except fan, if on) will turn off. In the case where the installer has selected to average the local sensor and the remote room sensor, the AC/HP display will alternate between “—-” for the failed sensor and the temperature sensed by the working sensor every 10 seconds. The control will operate from the temperature sensed by the working sensor.
- E1 — If the Display Module and the Equipment Control Module cannot communicate via two–wire connection, an E1 will be displayed.
- E2 — ThereisnoE2errormessage.
- E3 — If AC/HP Control cannot properly read outdoor temperature, and it is needed for proper operation, display will indicate “—-” in the outdoor temperature location.
- E4 — If AC/HP Control’s internal memory fails, E4 will be displayed. Replace AC/HP Control.
- Table 3 can be used as a troubleshooting tool for determining which outputs will be active for a particular configuration and each operating mode.
Table 3 – Equipment Configuration Outputs
EQUIPMENT- CONFIGURATION OPTION #1 |
HARDWARE CONFIGURATION |
COOL STAGE 1 | COOL STAGE 2 | HEAT STAGE 1 | HEAT STAGE 2 | HEAT STAGE 3 | EM HEAT STAGE 1 |
Single– stage AC | AC | Y/Y2 | — | W/W1 | — | — | — |
Single– stage AC | HP | Y/Y2 | — | W/W1 | W/W1
O/W2/B |
— | — |
Single– stage HP RVS = C | HP | Y/Y2
O/W2/B |
— | Y/Y2 | Y/Y2 W/W1 | — | W/W1 |
Single– stage HP RVS = H |
HP |
Y/Y2 |
— |
Y/Y2
O/W2/B |
Y/Y2 W/W1
O/W2/B |
— |
W/W1 |
Heat Only Unit | AC HP | — | — | W/W1 | — | — | — |
Cool Only Unit | AC HP | Y/Y2 | — | — | — | — | — |
WIRING DIAGRAMS
Indicates connection may not be required/available.
Indicates connection may not be required/available
Indicates connection may not be required/available.
Indicates connection may not be required/available.
Indicates connection may not be required/available.
Indicates connection may not be required/available.
Indicates connection may not be required/available.
Indicates connection may not be required/available.
Indicates connection may not be required/available.
NOTE: Rc/Rh jumper is cut on the Equipment Control Module.
THERMOSTAT CONFIGURATION RECORD
Installer
_________________________
Model Number
______________________________
Date
_________________________
Hardware Configuration
__________ Seal Hole In Wall
Mode Settings
__________ Mode (Off, Heat, Cool, Auto, Em Heat)
__________ Heating Setpoint Value
__________ Cooling Setpoint Value
__________ Fan (Auto or On)
Home, Away, Sleep Settings
Heat Cool
Home ____ ____
Away ____ ____
Sleep ____ ____
D. Schedule (For Programmable Thermostats)
Period 1 Period 2 Period 3 Period 4
Time Heat Cool Time Heat Cool Time Heat Cool Time Heat Cool
All Days ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____
Weekdays ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____
Weekend ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____
Configuration Options
- Option 01 Equipment Type Option 02
- Clean Filter Timer Adjustment Option 03*
- Fahrenheit/Centigrade Selection Option 04
- Fan (G) on with W/W1 Selection Option 05
- Room Air Temperature SensingOption 06
- Cooling Lockout Below 55_F Selection (only available if outdoor air sensor is present) Option 07
- Zoning Option 08 Auxiliary Heat Lockout Temperature Setting (only available when the heat pump is used and when outdoor air the temperature sensor is present)
- Option 10 Reversing Valve
- Option 1 Adjustable Setpoint Deadband
- Option 12 _____ Smart Recovery (programmable models only)
- Option 13 Room Air Temperature Offset Adjustment
- Option 15 Enable Auto ModeOption 16
- Cycles Per Hour Option 17 Time Between Stages
- Option 18* Backlight Configuration
- Option 19 Dry Contact (programmable models only)
- Option 20 Outdoor Air Temperature Offset Adjustment
- Option 21*.Keypad Lockout
- Option 24*Programmable/Non–Programmable (programmable models only)
- Option 25* Number of Programmable Periods Per Day (programmable models only)
- Option 26 Minimum Cooling SetpoinT
- Option 27 Maximum Heating Setpoint
- Option 28 UV Light Reminder
- Option 29 Humidifier Pad Reminder
- Option 30*Programmable Fan (programmable models only)
- Option 31* Daylight Savings Time Configuration (programmable models only)
- Option 32 Furnace Heat Staging
- Option 33 Single or Two–Piece Installation
Options with an asterisk can also be set/changed by the homeowner.E2007 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Printed in the U.S.A. Edition Date: 09/07 The manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.