Warning For installation by experienced service technicians only.
Caution  Possible electric shock or damage to equipment can occur. Disconnect power before beginning installation.
This thermostat requires 24 Volt AC Power or 2 properly installed “AA” Alkaline batteries for proper operation. When connecting 24 Volt AC Power, the batteries may be installed as a backup.
For use only as described in this manual. Any other use will void warranty.
This manual is for Installer use only – do not leave with end user.

SPECIFICATIONS

This thermostat is compatible with:

  • Single stage conventional and heat pump systems
  • Single stage heat pumps with auxiliary heat
  • Heat pump systems with 2 compressors and auxiliary heat (4235 only)
  • Conventional systems up to 2 stages of heat and 2 stages of cool (4235 only)
  • 250 – 750 millivolt heating only systems
  • 2 or 3 wire hydronic zone systems

Electrical and Control Specifications

  • Electrical Rating: 24 Volt AC
  • 1 amp maximum load per terminal
  • AC Power: 18 – 30 Volts AC
  • DC Power: 3.0 Volt DC (2 “AA” Alkaline Batteries Included)
  • Control Range: 45° to 90° F (7° to 32° C)
  • Temperature Accuracy: +/- 1° F (+/- .5° C)
  • Outdoor Temperature Display Range: – 40° to 120° F (-40° to 49° C)
  • DRY1, DRY2 Terminals: Dry Contact Relay

Humidity Control Specifications

  • Humidification Control Range: 10% – 50% RH
  • Dehumidification Control Range: 40% – 80% RH

Terminations

  • 4030: Rc, Rh, W1/E, Y1, G, O/B/V3, L, C, S1, S2, DRY1, DRY2
  • 4235: Rc, Rh, W1/E, W2/AUX, Y1, Y2, G, O/B/V3, L, C, S1, S2, DRY1, DRY2

INSTALLATION

Warning Disconnect power before beginning installation.

Thermostat Location
Install the thermostat approximately 5 feet (1.5m) above the floor in an area that has a good amount of air circulation and maintains an average room temperature.
Avoid installation in locations where the thermostat can be affected by drafts, dead air spots, hot or cold air ducts, sunlight, appliances, concealed pipes, chimneys and outside walls.Braeburn-4030-Programmable-Thermostats-fig-1

Install the Sub-Base: 

  • Remove the sub-base from the body of the thermostat.
  • Mount the sub-base as shown below:Braeburn-4030-Programmable-Thermostats-fig-2

INSTALLATION

Provide PowerBraeburn-4030-Programmable-Thermostats-fig-3

  • Battery Power – Insert the 2 supplied “AA” type alkaline batteries into the battery compartment located in the rear housing of the thermostat. Make sure to position the Positive (+) and Negative (-) sides of the batteries correctly with the +/- symbols in the battery compartment.
  • Optional 24 Volt AC power – Connect the common side of the transformer to the C terminal on the thermostat sub-base. In dual transformer installations, the transformer common must come from the cooling transformer.

Attach to Thermostat Sub-Base

Braeburn-4030-Programmable-Thermostats-fig-4

NOTE: This thermostat ships configured as a
1 Heat / 1 Cool conventional (CONV 11) thermostat.

WIRING

Conventional Systems 
Typical Wiring Configurations

Conventional Systems

Typical Wiring Configurations

4030 / 4235 4235
Heat Only or Millivolt

System Type:

CONV 11

Hydronic Heat Only

System Type:

HD 1

Hydronic Heat/Cool

System Type:

HD 11

1 Heat/

1 Cool

System Type:

CONV 11

2 Heat/

2 Cool

System Type:

CONV 22

Wiring Terminal Terminal Description
Rh 24 VAC Heating Transformer Rh Rh Rh1 Rh1 Rh1
Rc 24 VAC Cooling Transformer Rc1,2 Rc1,2 Rc1,2
W1/E (W1) Conventional Heat Relay

(E) Emergency Heat Relay

W1 W1 W1 W1 W1
W2/AUX* (W2) 2nd Stage Conventional Heat (AUX) Heat Pump Auxiliary Heat W2
Y1 1st Stage Compressor Relay Y1 Y1 Y1
Y2* 2nd Stage Compressor Relay Y23
G Fan Relay G3 G3 G G G
 

O/B/V3

(O) Cool Active Reversing Valve

(B) Heat Active Reversing Valve (V3) Zone Valve Power Close

 

 

V33

 

V33

 

 

L System Malfunction Indicator
C 24 VAC Transformer Common C4 C4 C4,5 C4,5 C4,5

“System Type” is configured in the Installer Settings – See section 5.
NOTES – Conventional Systems

  1. Remove factory installed jumper wire for dual transformer systems
  2. Only required for dual transformer systems
  3. Only connect if needed for system
  4. Optional 24 VAC transformer common connection
  5. For dual transformer systems, common must come from cooling transformer Provide disconnect and overload protection as required.

Additional Wiring Options

Wiring Terminal Terminal Description Notes
S1  

Remote Sensor (Indoor or Outdoor)

These terminals can be used to connect a Braeburn® indoor

or outdoor remote sensor. For indoor remote sensor configuration, refer to installer setting 23 in section 5. No configuration is required for an outdoor sensor.

S2
 

H/D*

(H) Humidification Relay

(D) Dehumidification Relay

This terminal can be used to control an external humidifier or dehumidifier relay. Overcooling is also available.

For configuration, refer to Installer Settings 25-29 in section 5.

DRY1 Dry Contact Relay (no voltage) These terminals can be used to connect a condensate overflow monitor, door switch, spring timer or occupancy sensor. For dry contact configuration, refer to Installer Settings 30-32 in section 5.
DRY2

4235 Only.
NOTE: Use 18-22 gauge unshielded wire with a 200-foot maximum wire length. Avoid running wire along with 120 VAC wiring or near magnetic ballasts.

WIRING

Heat Pump Systems

Typical Wiring Configurations

4030 / 4235 4235
1 Heat/1 Cool 2 Heat/1 Cool (w/Aux Heat)

System Type: HP 21

2 Heat/2 Cool (No Aux Heat)

System Type: HP 32

3 Heat/2 Cool (w/Aux Heat)

System Type: HP 32

Wiring Terminal Terminal Description Syste HP m Type: 11
Rh 24 VAC Heating Transformer Rh1 Rh1 Rh1 Rh1
Rc 24 VAC Cooling Transformer
W1/E (W1) Conventional Heat Relay

(E) Emergency Heat Relay

E2 E2
W2/AUX* (W2) 2nd Stage Conventional Heat (AUX) Heat Pump Auxiliary Heat AUX2 AUX2
Y1 1st Stage Compressor Relay Y1 Y1 Y1 Y1
Y2* 2nd Stage Compressor Relay Y2 Y2
G Fan Relay G G G G
 

O/B/V3

(O) Cool Active Reversing Valve

(B) Heat Active Reversing Valve (V3) Zone Valve Power Close

 

O/B3

 

O/B3

 

O/B3

 

O/B3

L System Malfunction Indicator L4 L4 L4 L4
C 24 VAC Transformer Common C5 C5 C5 C5

NOTES – Heat Pump Systems

  1. Do not remove factory installed jumper wire
  2. If no separate emergency heat relay, connect to AUX and Install a field supplied jumper wire from AUX to E
  3. O (cool active) or B (heat active) is selected in the Installer Settings – See section 5
  4. If using optional L terminal, the 24 VAC common must be connected (C terminal)
  5. Optional 24 VAC transformer common connection
    Provide disconnect and overload protection as required.

Additional Wiring Options

Wiring Terminal Terminal Description Notes
S1  

Remote Sensor (Indoor or Outdoor)

These terminals can be used to connect a Braeburn® indoor

or outdoor remote sensor. For indoor remote sensor configuration, refer to installer setting 23 in section 5. No configuration is required for an outdoor sensor.

S2
 

H/D*

(H) Humidification Relay

(D) Dehumidification Relay

This terminal can be used to control an external humidifier or dehumidifier relay. Overcooling is also available.

For configuration, refer to Installer Settings 25-29 in section 5.

DRY1 Dry Contact Relay (no voltage) These terminals can be used to connect a condensate overflow monitor, door switch, spring timer or occupancy sensor. For dry contact configuration, refer to Installer Settings 30-32 in section 5.
DRY2

NOTE: Use 18-22 gauge unshielded wire with a 200-foot maximum wire length. Avoid running wire along with 120 VAC wiring or near magnetic ballasts.

QUICK REFERENCE

Braeburn-4030-Programmable-Thermostats-fig-5

Thermostat

  1. SYSTEM Button…………………..Selects the system you want to control
  2. PROG Button………………………Enters programming mode or hold for 3 seconds to enter SpeedSet® mode
  3. BACK Button*……………………..Secondary function of the PROG button – Moves to previous setting
  4. HOLD Button……………………….Enters / Exits the HOLD mode (program bypass mode)
  5. NEXT Button*……………………..Secondary function of the HOLD button – Moves to next setting
  6. FAN Button…………………………Selects the system fan mode
  7. RETURN Button*………………….Secondary function of the FAN button – Exits program or setting modes
  8. Up / Down Arrow Buttons…….Increases or decreases settings (time, temperature, etc.)
  9. MENU Button………………………Used to access thermostat User / Installer setting modes
  10. Lock / Unlock Thermostat…… Access user Lock / Unlock screen by holding PROG and HOLD together for 5 seconds
    Battery Compartment………….Located on the back side of thermostat (if installed)

BACK, NEXT and RETURN are secondary functions of the PROG, HOLD and FAN buttons When in programming or configuration modes, BACK, NEXT and RETURN appear in the display screen indicating that the PROG, HOLD and FAN buttons now function as BACK, NEXT and RETURN

QUICK REFERENCEBraeburn-4030-Programmable-Thermostats-fig-6

Thermostat Display

  1. Room Temperature ………………………..Displays the current room temperature
  2. Set Temperature ……………………………Displays the current setpoint temperature
  3. Outdoor Temperature ………………………If a Braeburn® outdoor sensor was connected the outdoor temperature will be displayed
  4. Room Humidity (4235 only) ……………. Displays the current room Relative Humidity level
  5. Humidity Call Indicator (4235 only). ….Indicates when there is a call for Humidification or Dehumidification (in enabled)
  6. Override Indicator ………………………… Indicates that the current program schedule has been temporarily overridden
  7. Time of Day …………………………………. Displays the current time of day
  8. Message Center …………………………… Displays various thermostat status and maintenance information
  9. System Mode ………………………………..Displays the system mode and current system status
  10. Fan Mode Indicator ………………………. Indicates the current system fan mode
  11. Fan Status Indicator …………………….. Indicates that the system fan is running
  12. Lock Mode Indicator …………………….. Indicates if the thermostat is locked
  13. Low Battery Indicator …………………… .Indicates when the batteries need to be replaced

INSTALLER SETTINGS

The Installer Settings must be properly configured in order for this thermostat to operate correctly. The Installer Settings are menu driven. The portion of these settings that do not apply to your setup will be skipped.

To Enter Installer Settings Menu

  1. Press and hold down the MENU button for 5 seconds.
  2. Release the MENU button after the first installer setting is displayed.
  3. Change settings as required using the or buttons.
  4. Press NEXT (HOLD) or BACK (PROG) to move to the next or previous setting.
  5. Press RETURN (FAN) to exit. Menu will exit automatically after last setting.
    If UNLOCK 0000 is displayed, you must enter your 4-digit installer lock code to proceed (see Installer Settings 39 and 40).Braeburn-4030-Programmable-Thermostats-fig-7
No. Installer Setting Displayed Default Setting Available Settings Description of Available Settings
1 Residential or Commercial Profile MODE RES RES Select for Residential profile
COMM Select for Commercial profile
If residential mode is selected, 4 programming events per day are available (MORN, DAY, EVE, NITE). If commercial profile is selected, 2 programming events per day are available (OCC, UNOC).
 

2

 

Programming Mode

 

PROGRAM DAYS

 

7

7 Select for 7-day programming mode
52 Select for 5-2 day programming mode
NO Select for non-programmable mode
[Only available if a Residential (RES) profile was selected in setting 1] Selects the programming capabilities of the thermostat, either full 7 individual days, 5-2 day (weekday/weekend) programming or non-programmable.
3 Pre-Occupancy Purge PREPURGE OFF OFF Pre-Occupancy Purge is disabled
:15 – 3:00 Select :15 – 3:00 Pre-Occupancy Purge
[Only available if a Commercial (COMM) profile was selected in setting 1] Selects the amount of time the system fan will run before the start of the Occupied (OCC) program period (15 minute increments).
4 Clock Format CLOCK 12HR 12HR Select for a 12-hour clock
24HR Select for a 24-hour clock
Selects either a 12 hour or 24 hour clock format.
5 Temperature Scale DEGREE F F Select for Fahrenheit temperature display
C Select for Celsius temperature display
Selects a temperature scale of either °F or °C.
6 Auto Changeover AUTO CNG OFF OFF Auto-Changeover disabled
ON Auto-Changeover enabled
When auto-changeover mode is enabled and selected, the system can automatically switch between heating and cooling modes. There is a 5 minute delay when switching modes if auto changeover is selected.
7 Auto Changeover Dead Band DEADBAND 3 2, 3, 4, 5 Select an Auto Changeover Dead Band of 2°, 3°, 4° or 5˚ F (1°, 1.5°, 2° or 2.5° C)
[Only available if Auto Changeover was enabled in setting 6] When using auto changeover mode, the dead band is a forced separation between the heating and cooling setpoints so that the systems do not work against each other.

This setting selects the amount of this dead band in degrees. If using the dehumidification overcooling feature in setting 28, the allowable deadband will be limited based on your dehumidification overcooling limit selection.

No. Installer Setting Displayed Default Setting Available Settings Description of Available Settings
 

 

 

8

 

 

 

System Type

 

 

 

SYSTEM

 

 

 

CONV 11

CONV 11 Select for 1H/1C Conventional system
CONV 22 Select for 2H/2C Conventional system (4235)
HP 11 Select for 1H/1C Heat Pump system
HP 21 Select for 2H/1C Heat Pump system
HP 32 Select for 3H/2C Heat Pump system (4235)
HD 1 Select for heat-only Hydronic system
HD 11 Select for Hydronic system with cooling
Select the type of equipment you are controlling. The HP 32 system type is for a 2-stage heat pump compressor (stage 1 and 2) with auxiliary heat (stage 3). System types CONV 22 and HP 32 are not available in model 4030.
9 1st Stage Differential DEGREE DIF1 0.5 0.5, 1.0, 2.0 Select a 1st stage temperature differential of 0.5°, 1° or 2° F (0.2°, 0.5° or 1.0° C)
Selects a 1st stage temperature differential which controls the degree of separation between the setpoint temperature and the 1st stage of heating or cooling.
10 2nd Stage Differential DEGREE DIF2 2.0 1.0, 2.0, 3.0

4.0, 5.0, 6.0

Select a 2nd stage temperature differential of 1°, 2°, 3°, 4°, 5° or 6° F (0.5°, 1.0°, 1.5°, 2.0°, 2.5° or 3.0° C)
[Only available if a 2 or 3 stage system was selected in setting 8] Selects a 2nd stage temperature differential which controls the degree of separation between the 1st and 2nd stage of heating or cooling.
11 3rd Stage Differential DEGREE DIF3 2.0 1.0, 2.0, 3.0

4.0, 5.0, 6.0

Select a 3rd stage temperature differential of 1°, 2°, 3°, 4°, 5° or 6° F (0.5°, 1.0°, 1.5°, 2.0°, 2.5° or 3.0° C)
[Only available if a 3 stage system was selected in setting 8] Selects a 3rd stage temperature differential which controls the degree of separation between the 2nd and 3rd stage of heating.
12 Conventional Heat Fan Control FAN 1 GAS GAS Select for conventional Gas heating
ELEC Select for conventional Electric heating
[Only available if a conventional system was selected in setting 8] Selects a 1st stage fan control of either gas or electric heat. If Electric is selected, the thermostat turns on the system fan with a call for heating.
13 Emergency Heat Fan Control EMER FAN ELEC ELEC Select for Electric Emergency Heat
GAS Select for Gas Emergency Heat
[Only available if a 2 or 3 stage heat pump system was selected in setting 8] Selects emergency heat fan control

of either gas or electric heat. If Electric is selected, the thermostat turns on the system fan with a call for emergency heat.

14 Finish with High Stage AUX FNSH NO N0 Finish with High Stage is disabled
YES Finish with High Stage is enabled
[Only available if a 2 or 3 stage system was selected in setting 8] When Finish with High Stage is enabled, once engaged, the supplemental heat source (2nd or 3rd stage) will remain on until temperature is satisfied. When disabled, these supplemental heat source(s) will turn off approximately 0.5 degrees before setpoint to let the 1st stage heat source complete the heat call.
15 Reversing Valve (O/B Terminal) R VALVE 0 0 Select for cool active Reversing Valve
B Select for heat active Reversing Valve
[Only available if a heat pump system was selected in setting 8] Selects the output state of the O/B terminal. Select O for this terminal to be active in the cool mode or select B for this terminal to be active in the heat mode.
16 Fossil Fuel Backup Heat AUX HEAT ELEC ELEC Select for Electric Auxiliary heat (with compressor)
GAS Select for Gas Auxiliary heat (without compressor)
[Only available if a 2 or 3 stage heat pump system was selected in setting 8] When set to electric, both the compressor and auxiliary stage will run when a call for auxiliary heat is made. When set to gas, the compressor stage(s) will be locked out one minute after a call for auxiliary heat. This setting can be overridden if setting an auxiliary heat balance point in setting 34.
No. Installer Setting Displayed Default Setting Available Settings Description of Available Settings
17 Compressor Power Outage Protection CPOP OFF 0FF Power outage lockout delay is disabled
0N Power outage lockout delay is enabled
[Only available if a heat pump system was selected in setting 8 and thermostat is powered with a 24 VAC common (C) wire] When enabled, this thermostat will provide cold weather compressor protection by locking out the compressor stage(s) of heating for a period of time after a power outage greater than 60 minutes.
18 AC Power Interrupt Warning POWR MON OFF OFF AC Power Interrupt Warning is disabled
ON AC Power Interrupt Warning is enabled
[Only available if thermostat is powered with a 24 VAC common (C) wire] When enabled, the thermostat will display NO POWER when AC power to the thermostat is lost. Batteries must also be installed for this feature to operate.
19 Compressor Short Cycle Protection (CSCP) CSCP MIN 5 5, 4, 3,

2, 1, 0

Select CSCP delay duration in minutes
Selects the number of minutes the compressor(s) will be locked out after turning off. This delay will run simultaneously with any delay built into the equipment.
20 Residual Cooling Fan Delay RESIDUAL COOL 60 90, 60,

30, 0

Select fan delay duration in seconds
Selects a delay for the system fan after the cooling compressor has turned off. This delay will help remove the remaining cool air out of the ductwork providing additional efficiency.
21 Circulating Fan Lock CIRCLOCK OFF OFF Circulating Fan Lock is disabled
ON Circulating Fan Lock is enabled
[Not available if 1 HD was selected in setting 8] When enabled, the only user fan settings available are ON and CIRC (Circulation). The AUTO and PROG fan settings are not available with this setting enabled.
22 Adaptive Recovery Mode (ARMTM) RECOVER OFF OFF Adaptive Recovery Mode is disabled
ON Adaptive Recovery Mode is enabled
[Not available if non-programmable was selected in setting 2] During ARM, room temperature is recovered by turning on the heating or cooling up to 3-hours before the end of the set back period. The setpoint temperature is changed to that of the upcoming program temperature.
 

 

23

 

 

Indoor Remote Sensor

 

 

REMOTE SENS

 

 

I

I Temperature is sensed from thermostat only (Internal)
E Temperature is sensed from remote sensor only (External)
A Temperature is averaged between thermostat and remote sensor (Average)
[Only available if Braeburn model 5390 remote indoor sensor is connected] If a Braeburn indoor remote sensor is connected, the thermostat will automatically detect the sensor. When an indoor sensor is detected, you may select between thermostat only (1), remote sensor only (E) or the average of the thermostat and remote sensor (A).
 

24

 

User Lock Security Level

 

USERLOCK LVL

 

3

3 If locked, all buttons are disabled
2 If locked, all buttons except  and  are disabled
1 If locked, only the PROG, HOLD and MENU buttons are disabled
Selects the level of keypad lockout when the thermostat has been locked by the user. See the User Manual for instructions on setting the 3-digit lock code and locking/unlocking the thermostat.
No. Installer Setting Displayed Default Setting Available Settings Description of Available Settings
25 Humidification (4235 only) HUMID OFF OFF Humidification is disabled
DEP Dependent humidification is enabled
IND Independent humidification is enabled
For use with an external humidifier. Select between disabling humidification, dependent control or independent control.

The DEP setting controls humidification only during a call for heating. The IND setting allows humidification output in the heat mode, but does not require a call for heating. It is recommended that the IND setting only be used with systems designed for low air temperature humidification such as steam humidification. Always ensure the heat exchanger or other system parts are not exposed to excess water from condensation or other sources. When there is any doubt, use the OFF or DEP setting.

26 Auto Humidity Set Point Limit (4235 only) HUMID MAN MAN Maximum humidity setpoint is not limited
AUTO Maximum humidity setpoint is limited based on outdoor temperature
[Only available if Braeburn® model 5490 remote outdoor sensor is connected] When AUTO is selected, the humidity setpoint maximum is limited based on the outdoor temperature. Selecting MAN allows you to manually control the

level of humidity between 10% and 50%.

 

27

 

 

Dehumidification (4235 only)

 

DEHUMID

 

OFF

OFF Dehumidification is disabled
DEP Dependent dehumidification is enabled
IND Independent dehumidification is enabled
[IND (independent) dehumidification is not available if Humidification was enabled in setting 25] (DEP) If the humidity level is above the humidity setpoint, cooling stays on until the humidity level drops below the setpoint or when the over cooling limit in setting 28 is reached in. (IND) For use with an external dehumidifier – When the humidity level rises above the dehumidification setpoint, both the G (Fan) and D terminals are activated. Not available in 1HD system mode.
28 Dehumidification Overcooling Limit (4235 only) OVERCOOL LIM 1.0 1.0°, 2.0°,

or 3.0° F

(.5°, 1.0°,

or 1.5° C)

Select a dehumidification overcooling limit in degrees
[Only available if dependent dehumidification (DEP) was selected in setting 27] Select the number of degrees the system is allowed to over cool while attempting to reduce humidity. This setting will affect the maximum allowable deadband set in setting 7.
29 Dehumidification (D) Terminal Output (4235 only) DH RELAY N:0 N:0 Select a normally open relay
N:C Selects a normally closed relay
[Only available if independent dehumidification (IND) was selected in setting 27] Select normally open relay (N:O) or normally closed (N:C) relay for D terminal output in independent dehumidification mode. This setting can also be used for dehumidification fan speed control.
No. Installer Setting Displayed Default Setting Available Settings Description of Available Settings
 

30

 

Dry Contact Type

 

CONTACT

 

OFF

OFF Dry contact is disabled
COND Select for condensate overflow monitoring
DOOR Select for door open monitoring
OCC Select for occupancy monitoring
[If a Residential profile was selected in setting 1, only the condensate (COND) setting will be available] The dry contact can be used to monitor several conditions. See the table below for an outline of these conditions. WARNING: DRY1, DRY2 terminals are a dry contact relay and should never have voltage applied to them. If not using the dry contact, make sure to select OFF for this setting.
Detailed Description of Dry Contact Settings (Installer Setting 30)
 

Condensate

 

COND

This setting is intended for a condensate pan overflow monitor. When the contact is active, the thermostat will immediately disable the cooling compressor(s) and display the message OVERFLOW. After the contact is inactive for 1 minute, the compressor(s) will resume operation and the thermostat display will return to normal.
 

 

Door Switch

 

 

DOOR

This setting is intended for a door switch monitor. When this mode is selected, the thermostat will only run the occupied (OCC) portion of the program schedule while the contact is inactive (door closed). When the contact becomes active (door open), the thermostat will turn OFF and display the message DOOROPEN until the contact becomes inactive again. There is a 3-minute delay before the thermostat turns OFF. Temperature override is not permitted while the contact is active (door open).
 

 

Occupancy

 

 

OCC

This setting is intended for the use of an occupancy sensor or mechanical spring-wound timer switch. When active, the thermostat will be forced into the occupied (OCC) portion of the program schedule until the contact becomes inactive. In setting 32 below, the Occupancy Trigger Control

can be selected (PROG or UNOC).

No. Installer Setting Displayed Default Setting Available Settings Description of Available Settings
31 Dry Contact Relay State CONTACT N:0 N:0 Selects a normally open relay
N:C Selects a normally closed relay
[Not available if OFF was selected in setting 30] Select normally open (N:O) or normally closed (N:C) for the dry contact relay terminals (DRY1, DRY2).
32 Occupancy Trigger Control OCCUPIED PROG PROG Follows current program schedule until the occupied state is triggered
UNOC Follows the unoccupied (UNOC) program schedule until the occupied state is triggered
[Only available if occupancy monitoring (OCC) was selected in setting 30] If the dry contact type was set to occupied (OCC) in setting 30, there will be 2 selections for the occupied state. If PROG is selected (default), the thermostat will follow its normal program schedule until the dry contact is active. When the dry contact is active, the thermostat will only operate

the occupied portion of the program schedule and ignore the unoccupied portion of the program schedule. If UNOC is selected, the thermostat will ignore the program schedule and always operate in the unoccupied state. When the dry contact is active, the thermostat will operate in the occupied state for the duration of the contact being active.

No. Installer Setting Displayed Default Setting Available Settings Description of Available Settings
33 Compressor Balance Point BALPOINT COMP NO NO Compressor balance point is disabled
0 to 50

(-18˚ to 10˚C)

Select a Compressor Balance Point of 0˚ to 50˚ (-18˚ to 10˚C)
[Only available for 2 or 3 stage heat pump systems with a Braeburn® 5490 outdoor sensor connected] Locks out the use of the heat pump compressor’s heat stage(s) when the outside air temperature is less than the selected setting. During this lockout period, only the auxiliary heat stage will operate.
34 Auxiliary Heat Balance Point BALPOINT AUX NO NO Auxiliary heat balance point is disabled
70 to 40

(21 ˚ to 4˚C)

Select a Auxiliary Heat Balance Point of 70° to 40°F (21° to 4°C)
[Only available for 2 or 3 stage heat pump systems with a Braeburn 5490 outdoor sensor connected] Locks out the use of the auxiliary heat stage when the outside air temperature exceeds the selected setting. This balance point overrides the fossil fuel compressor lockout in setting 16. If setting 16 is set to gas and the outdoor temperature is over the auxiliary balance point, the compressor will remain on during a call for auxiliary heat.
35 Heat Setpoint Upper Limit HIGH LIM HEAT 90 90 – 45

(32˚ to 7˚C)

Select a Heat Setpoint Upper Limit of 90° to 45°F (32° to 7°C)
Selects the upper setpoint adjustment limit that cannot be exceeded in heat mode.
36 Heat Setpoint Lower Limit LOW LIM HEAT 45 45 – 90

(7˚ to 32˚C)

Select a Heat Setpoint Lower Limit of 45° to 90°F (7° to 32°C)
Selects the lower setpoint adjustment limit that cannot be exceeded in heat mode.
37 Cool Setpoint Lower Limit LOW LIM COOL 45 45 – 90

(7˚ to 32˚C)

Select a Cool Setpoint Lower Limit of 45° to 90°F (7° to 32°C)
[Not available for heat-only hydronic systems] Selects the lower setpoint adjustment limit that cannot be exceeded in cool mode.
38 Cool Setpoint Upper Limit HIGH LIM COOL 90 90 – 45

(32˚ to 7˚C)

Select a Cool Setpoint Upper Limit of 90° to 45°F (32° to 7°C)
[Not available for heat-only hydronic systems] Selects the upper setpoint adjustment limit that cannot be exceeded in cool mode.
39 Installer Lock INSTLOCK NO NO Installer Lock disabled
YES Installer Lock enabled
When enabled, a 4-digit lock code can be entered in setting 40. This lock code will be required the next time the Installer Settings menu is accessed. Select NO to skip the installer lock.
40 Installer Lock Code IL CODE 0000 0-9 Select 0-9 for each digit
[Only available if Installer Lock was enabled in setting 39] Select a 4-digit lock code (0-9 for each digit) to lock the Installer Settings menu. The code 0000 is not a valid lock code and cannot be used.
41 Installer Clear (factory reset) CLEAR NONE NONE Clear disabled – No changes made
ALL Clear enabled – Factory Reset
Selecting ALL will return thermostat to all factory default settings. Factory reset will take affect upon exiting Installer settings menu.

Additional options such as Service Monitors, setting the lock code, etc. are located in the User Settings – See User Manual.

SYSTEM TESTING

Warning Read Before Testing

  • Do not short (or jumper) across terminals on the gas valve or at the heating or cooling system control board to test the thermostat installation. This could damage the thermostat and void the warranty.
  • Do not select the COOL mode of operation if the outside temperature is below 50º F (10º C). This could possibly damage the controlled cooling system and may cause personal injury.
  • This thermostat includes an automatic compressor protection feature to avoid potential damage to the compressor from short cycling. When testing the system, make sure to take this delay into account.

NOTE: The compressor delay can be bypassed by adjusting Installer Setting 19 – See section 4.

  1. Press the SYSTEM button until the thermostat is in HEAT mode.
  2. Press the button to raise the set temperature a minimum of 3 degrees above the current room temperature. The system should start within a few seconds. With a gas heating system, the fan may not start right away.
  3. Press the SYSTEM button until the thermostat is in the OFF mode. Allow the heating system to fully
    shut down.
  4. Press the SYSTEM button until the thermostat is in the COOL mode.
  5. Press the button to lower the set temperature a minimum of 3 degrees below the current room temperature. The system should start within a few seconds (unless compressor short cycle protection is active – See note above).
  6. Press the SYSTEM button until the thermostat is in the OFF mode. Allow the cooling system to fully shut down.
  7. Press the FAN button until the thermostat is in FAN ON mode. The system fan should start within a few seconds.
  8. Press the FAN button until the thermostat is in FAN AUTO mode. Allow the system fan to turn off.
  9. If the thermostat is controlling auxiliary equipment such as a humidifier, adjust settings to test these devices.

Limited Warranty

When installed by a professional contractor, this product is backed by a 5-year limited warranty. Limitations apply. For limitations, terms, and conditions, you may obtain a full copy of this warranty:

Braeburn Systems LLC
2215 Cornell Avenue Montgomery, IL 60538
Technical Assistance: www.braeburnonline.com
Call us toll-free: 866-268-5599 (U.S.)
630-844-1968 (Outside the U.S.)
©2022 Braeburn Systems LLC • All Rights Reserved.