Braeburn-2020NC-Programmable-Thermostats-featured

Braeburn 2020NC Programmable Thermostats User Guide

Braeburn-logo

Braeburn 2020NC Programmable Thermostats 

Braeburn-2020NC-Programmable-Thermostats

Warning Turn off power to the heating or cooling equipment before installation.
Attention For installation by experienced service technicians only.

Read all instructions before proceeding.
This thermostat requires 24 Volt AC Power or two (2) properly installed “AA” Alkaline batteries for proper operation. When connecting 24 Volt AC Power the batteries may be installed as a backup. Thermostat installation and all components of the system shall conform to Class II Circuits per NEC code.
For use only as described in this manual. Any other use will void warranty.

Specifications

This thermostat is compatible with:

  • Single stage heat / cool conventional and heat pump systems
  • Conventional systems up to 2 heat / 1 cool (2220NC only)
  • Single compressor heat pump systems with an auxiliary heat stage (2220NC)
  • 250 – 750 millivolt heat only systems

Electrical and control specifications:

  • Electrical Rating: 24 Volt AC
  • 1 amp maximum load per terminal
  • AC Power: 18 – 30 Volts AC
  • DC Power: 3.0 Volt DC (2 “AA” Alkaline Batteries Included)
  • Control Range: 45° – 90° F (7° – 32° C)
  • Temperature Accuracy: +/- 1° F (+/- .5° C)

Terminations

  • 2020NC – Rc, Rh, O, B, Y1, W1, G, C
  • 2220NC – Rc, Rh, O, B, Y1, E/W1, G, W2, C

About Your ThermostatBraeburn-2020NC-Programmable-Thermostats-fig-1

  1. Room Temperature………….Displays the current room temperature
  2. Day of Week……………………Displays the current day of week
  3. Program Event Indicator….Indicates the current program event
  4. Time of Day…………………….Displays the current time of day
  5. Low Battery Indicator……..Indicates when batteries need to be replaced
  6. Fan Indicator………………….Indicates when the system fan is running
  7. Hold Mode Indicator………..Displays if in HOLD mode
  8. System Status Indicator…..Displays information about system status
  9. Set Temperature……………..Displays the current set point temperature
  10. Service Filter Indicator…….Displays service/maintenance remindersBraeburn-2020NC-Programmable-Thermostats-fig-2
  11. Reset Button…………Resets thermostat back to factory defaults
  12. System Switch………Selects system preference
  13. PROG Button…………Selects programming mode
  14. HOLD Button…………Enters/Exits the HOLD mode (program bypass)
  15. RETURN Button……..Returns to normal from program or setting modes
  16. DAY/TIME Button…..Used to set the time and day of week
  17. Quick Reference
    Instructions………… .Stored in slot at top of thermostat
  18. Arrow Buttons…….. .Used to increase or decrease settings
  19. Fan Switch……………Selects the system fan mode
    Battery Compartment……Located in back of the thermostat

Installation

Warning Disconnect power before beginning installation.

Thermostat Location
Install the thermostat approximately 5 feet (1.5m) above the floor in an area that has a good amount of air circulation and maintains an average room temperature.
Avoid installation in locations where the thermostat can be affected by drafts, dead air spots, hot or cold air ducts, sunlight, appliances, concealed pipes, chimneys and outside walls.Braeburn-2020NC-Programmable-Thermostats-fig-3

Install your new Braeburn thermostat in 5 basic steps:

  1. Install the Sub-Base
  2. Provide Power
  3. Connect Your Wires
  4. Set Installer Switches
  5. Attach Thermostat to Sub-Base

Install the Sub-Base:

  • Remove the sub-base from the body of the thermostat.
  • Mount the sub-base as shown below:Braeburn-2020NC-Programmable-Thermostats-fig-4

NOTE: After sub-base installation, you may insert the quick reference card into the slot on the top of the base.

Provide PowerBraeburn-2020NC-Programmable-Thermostats-fig-5

  • For 24 Volt AC power, you must connect the common side of the trans- former to the C terminal on the thermostat sub-base.
  • For primary or back-up power, insert the 2 supplied “AA” type alkaline batteries into the battery compartment located in the rear housing of the thermostat. Make sure to position the Positive (+) and Negative (-) sides of the batteries correctly with the +/- symbols in the battery compartment.

Connect Your Wires

Wiring Terminations

Terminal Function Description
Rc Input 24 Volt AC Cooling Transformer (Dual Transformer Systems Only)
Rh Input Power Connection (24 Volt AC Heating Transformer or Millivolt Power Source)
O Output Reversing Valve (Cool Active)
B Output Reversing Valve (Heat Active)
Y1 Output Compressor Relay
G Output Fan Control
W1 Output Conventional Heat Relay
C Input 24 Volt AC Transformer Common

Additional Terminations (2220NC only)

Terminal Function Description
W1/E Output (W1) 1st Stage Conventional Heat

(E) Emergency Heat Relay

W2 Output 2nd Stage Heat / Auxiliary Heat

Conventional Systems

Typical Wiring Configurations
NOTE: The “Installer Switch” option will be configured in the next step.

Heat Only or Millivolt
Set Installer Switch to CONV

Rh Power Connection
W Heat Relay (appears as W1/E on 2220NC)
G Fan Relay [note 4]
C 24 Volt AC Transformer Common [note 1]

1 HEAT / 1 COOL Single or Dual Transformer
Set Installer Switch to CONV

Rh 24 Volt AC Power (heating transformer) [note 2]
Rc 24 Volt AC Power (cooling transformer) [note 2]
W1 Heat Relay (appears as W1/E on 2220NC)
Y1 Compressor Relay
G Fan Relay
C 24 Volt AC Transformer Common [note 1, 3]

2 HEAT / 1 COOL Single or Dual Transformer (2220NC Only)
Set System Type to CONV

Rh 24 Volt AC Power (heating transformer) [note 2]
Rc 24 Volt AC Power (cooling transformer) [note 2]
W1 Heat Relay Stage 1
W2 Heat Relay Stage 2
Y1 Compressor Relay Stage 1
G Fan Relay
C 24 Volt AC Transformer Common [note 1, 3]

NOTES – Conventional Systems

  1. If batteries are installed the 24 Volt AC common connection is optional
  2. Remove factory installed jumper for dual transformer systems
  3. In dual transformer systems, transformer common must come from cooling transformer
  4. If needed for system
    Provide disconnect and overload protection as required.

Heat Pump Systems

Typical Wiring Configurations

NOTE: The “Installer Switch” option will be configured in the next step.

HEAT / 1 COOL – No Auxiliary Heat
Set Installer Switch to HP

Rh 24 Volt AC Power
Rc Connected to Rh with supplied Jumper Wire
O or B Changeover Valve [note 2]
Y1 Compressor Relay
G Fan Relay
C 24 Volt AC Transformer Common [note 1]

HEAT / 1 COOL – Including Auxiliary Heat (2220NC only)
Set Installer Switch to HP

Rh 24 Volt AC Power
Rc Connected to Rh with supplied Jumper Wire
O or B Changeover Valve [note 2]
Y1 Compressor Relay (1st stage heating/cooling)
W2 Auxiliary Heat Relay (2nd stage heating) [note 3]
E Emergency Heat Relay [note 3]
G Fan Relay
C 24 Volt AC Transformer Common [note1]

NOTES – Heat Pump Systems

  1. If batteries are installed the 24 Volt AC common connection is optional.
  2. Select O for cool active or B for heat active.
  3. Install a field supplied jumper between the W2 and E terminals if there is no separate emergency heat relay installed.
    Provide disconnect and overload protection as required.

Set Installer Switches
The Installer switches are located on the back of the thermostat and must be properly set for this thermostat to operate properly.

 

Switch

Factory Default Setting Options  

Comments

CONV / HP CONV CONV Select for conventional systems
HP Select for heat pump systems
F / C F F Select for fahrenheit temperature scale
C Select for celsius temperature scale
HE / HG HG HG Select for gas heat
HE Select for electric heat

NOTE: Installer switches are located on the back of the thermostat. The reset button must be pressed after making any changes to these switches.

Attach Thermostat to Sub-Base

  1. Line up the thermostat body with the sub-base.
  2. Carefully push the thermostat body against the sub-base until it snaps into place.
  3. Insert quick reference card into slot on top of thermostat.Braeburn-2020NC-Programmable-Thermostats-fig-6

System Testing

Warning Read Before Testing

  • Do not short (or jumper) across terminals on the gas valve or at the heating or cooling system control board to test the thermostat installation. This could damage the thermostat and void the warranty.
  • Do not select the COOL mode of operation if the outside temperature is below 50º F (10º C). This could possibly damage the controlled cooling system and may cause personal injury.
  • This thermostat includes an automatic compressor protection feature to avoid potential damage to the compressor from short cycling. When testing the system, make sure to take this delay into account.

NOTE: The compressor delay can be bypassed by pressing the reset button on the front of the thermostat. All user settings will be returned to factory default.

  1. Move the SYSTEM switch to HEAT mode.
  2. PressBraeburn-2020NC-Programmable-Thermostats-fig-7 to raise the set temperature a minimum of 3 degrees above the current room temperature. The system should start within a few seconds. With a gas heating system, the fan may not start right away.
  3. Move the SYSTEM switch to the OFF mode. Allow the heating system to fully shut down.
  4. Move the SYSTEM switch to the COOL mode.
  5. Press Braeburn-2020NC-Programmable-Thermostats-fig-8to lower the set temperature a minimum of 3 degrees below the current room temperature. The system should start within a few seconds (unless compressor short cycle protection is active – See note above).
  6. Move the SYSTEM switch to the OFF mode. Allow the cooling system to fully shut down.
  7. Move the FAN switch to the ON mode. The system fan should start within a few seconds.
  8. Move the FAN switch to the AUTO mode. Allow the system fan to turn off.

Setting User Options 

Advanced User Options
User options allow you to customize some of your thermostat’s features. Most users will not need to make any changes to the settings in this section.
To enter the User Options menu, hold down the RETURN button for approximately 3 seconds until the screen changes and displays the first User Option.
Press the Braeburn-2020NC-Programmable-Thermostats-fig-10 button to change the setting for the displayed User Option. After you have made your desired setting, press RETURN to advance to the next User Option. The thermostat will return to normal mode after your last user option is made or after no keys have been pressed for 15 seconds.

Table of User Options

 

No.

User Options Factory Default Setting Options  

Comments

1 Programming Mode PRO 7 PRO 7

PRO 52 PRO NO

Select for 7 Day Programming Mode Select for 5-2 Day Programming Mode Select for Non-Programmable Mode
2 1st stage differential 0.5 0.5, 1.0,

2.0

Select a 1st stage temperature differential of .5˚, 1˚ or 2˚F (0.2˚,

0.5˚ or 1˚C)

3 2nd stage differential (2220NC Only) 2.0 1.0, 2.0,

3.0, 4.0,

5.0, 6.0

Select a 2nd temperature differential of 1˚, 2˚, 3˚, 4˚, 5˚ or 6˚F (.5˚, 1˚, 1.5˚, 2˚, 2.5˚ or 3˚C)
4 Extended Hold Period* LNG LNG Selects long (permanent) hold mode
24HRS Selects 24 hr. (temporary) hold mode
5 Filter Service Monitor OFF OFF Disables filter service monitor feature
30, 60, 90,

120, 180,

365

Selects a number of days before the thermostat will flash a Service

Filter reminder in the display.

6 Adaptive Recovery Mode(ARMTM)*  

OF REC

OF REC Disables adaptive (early) recovery mode
ON REC Enables adaptive (early) recovery mode

Detailed Explanation of User Options:

Programming Mode
(User Option 1)
Selects the programming mode (choose from 7 day, 5-2 Day (weekday/ weekend) programming or non-programmable.

Temperature Differential
(User Option 2 and 3)
The differential setting is the temperature control range that your thermostat will provide. The smaller the setting, the tighter your range of temperature control and comfort will be. The 2nd stage differential is only for systems with a second stage of heating (auxiliary heat).

Extended Hold Period*
(User Option 4)
The Extended Hold Period lets you select the period your thermostat will hold the temperature when the HOLD mode is activated (See “Temperature Adjustment”). When LNG is selected the thermostat will hold your temperature indefinitely. When 24HR is selected, the thermostat will hold your temperature for 24 hours and then return to the current program at that time.

Service Filter Monitor
(User Option 5)
The Service Filter Monitor is a user selectable service monitor that will display a reminder for a required air filter replacement by flashing the SERVICE FILTER segment in the display. When the selected interval has been reached, and required cleaning or replacement has been performed, touch the RETURN button to reset the timer and reset the service monitor. Select OFF or a set number of days before the reminder will appear.Braeburn-2020NC-Programmable-Thermostats-fig-9

Adaptive Recovery Mode (early recovery)
(User Option 6)
Adaptive Recovery Mode is a user setting that controls when the thermostat will start to recover from setback.

ARMTM Setting Result
OFF Start change at programmed time
ON Finish change at programmed time

Not available if User Option 1 is set to non-programmable

Setting Your Program Schedule

Setting the Time and Day

  1. In normal operating mode, press the DAY/TIME button. The display will switch to the day/time setting mode and the hour will be flashing.
  2. Press or to adjust the hour. Press DAY/TIME.
  3. Press or to adjust the minute. Press DAY/TIME.
  4. Press or to adjust the day of the week. Press RETURN to exit.Braeburn-2020NC-Programmable-Thermostats-fig-11

Tips Before Setting Your Program Schedule

  • Make sure your current time and day of the week are set correctly.
  • When programming, make sure the AM and PM indicators are correct.
  • Your NIGHT event cannot exceed 11:50 p.m.

This thermostat has been configured with one of the following programming options:

  • 7 day programming mode with 4 events per day (default)
  • 5-2 (weekday/weekend) programming mode with 4 events per day.
  • Non-Programmable mode
    NOTE: If this thermostat was set in the Installer Settings to be non-programmable, then you cannot set a user program. If you press the PROG or HOLD buttons, the word “NO” will appear in the display, indicating there is no program present. See section 5, “Setting User Options” to change this setting.Braeburn-2020NC-Programmable-Thermostats-fig-12

Energy Saving Programs
This thermostat comes pre-programmed with a default energy saving program. The following tables outline the pre-programmed times and temperatures for heating and cooling in each of your 4 daily events. If you wish to use these settings then no further programming is necessary:

7 Day Programming

Factory Settings

4 Event All Days
 

MORN

Time: 6:00 am Heat: 70˚ F (21˚ C) Cool: 78˚ F (26˚ C)
 

DAY

Time: 8:00 am Heat: 62˚ F (17˚ C) Cool: 85˚ F (29˚ C)
 

EVE

Time: 6:00 pm Heat: 70˚ F (21˚ C) Cool: 78˚ F (26˚ C)
 

NIGHT

Time: 10:00 pm Heat: 62˚ F (17˚ C) Cool: 82˚ F (28˚ C)
5-2 Day Programming– Weekday/Weekend

Factory Settings

4 Event Weekday Weekend
 

MORN

Time: 6:00 am Heat: 70˚ F (21˚ C) Cool: 78˚ F (26˚ C) Time: 6:00 am Heat: 70˚ F (21˚ C) Cool: 78˚ F (26˚ C)
 

DAY

Time: 8:00 am Heat: 62˚ F (17˚ C) Cool: 85˚ F (29˚ C) Time: 8:00 am Heat: 62˚ F (17˚ C) Cool: 85˚ F (29˚ C)
 

EVE

Time: 6:00 pm Heat: 70˚ F (21˚ C) Cool: 78˚ F (26˚ C) Time: 6:00 pm Heat: 70˚ F (21˚ C) Cool: 78˚ F (26˚ C)
 

NIGHT

Time: 10:00 pm Heat: 62˚ F (17˚ C) Cool: 82˚ F (28˚ C) Time: 10:00 pm Heat: 62˚ F (17˚ C) Cool: 82˚ F (28˚ C)

Programming a 7 Day Schedule
The 7 day programming mode gives you the option to program individual days (1 day at a time) or to use SpeedSet and program the entire week (all 7 days) with a 4 event program schedule.

Setting All 7 Days at Once (SpeedSet®)
NOTE: Setting all 7 days at once will copy over any previously programmed individual days.Braeburn-2020NC-Programmable-Thermostats-fig-13

  1. Hold the PROG button for 3 seconds. The display will switch to SpeedSet programming mode. All 7 days of the week will appear and the hour will be flashing.
  2. Select HEAT or COOL with SYSTEM switch.
  3. Press the or button to adjust the hour for the MORN (morning) event. Press PROG.
  4. Press the or button to adjust the minute for the MORN event. Press PROG.
  5. Press the or button to adjust the temperature for the MORN event. Press PROG.
  6. Repeat steps 3-5 for the DAY, EVE and NIGHT events.
  7. If needed, repeat steps 2-6 to program the opposite mode (HEAT or COOL).
  8. Press RETURN to exit.

Setting Individual Days (7 Day Mode)

  1. Press the PROG button. The display will switch to programming mode. M (Monday) will be displayed and the hour will be flashing.
  2. Select HEAT or COOL with SYSTEM switch.
  3. Press DAY/TIME to select the day you would like to program.
  4. Press the or button to adjust the hour for the MORN (morning) event. Press PROG.
  5. Press the or button to adjust the minute for the MORN event. Press PROG.
  6. Press the or button to adjust the temperature for the MORN event. Press PROG.
  7. Repeat steps 4-6 for your DAY, EVE and NIGHT events.
  8. If needed, repeat steps 3-6 to select a different day to program.
  9. If needed, repeat steps 2-8 to program the opposite mode (HEAT or COOL).
  10. Press RETURN to exit.Braeburn-2020NC-Programmable-Thermostats-fig-14

Programming a 5-2 Day Schedule
The 5-2 day programming mode allows you to program Monday – Friday with one 4 event schedule and then allows you to change Saturday and Sunday with a different 4 event schedule.

  1. Press the PROG button. The display will switch to programming mode. The days M, TU, W, TH, and F will be displayed and the hour will be flashing.
  2. Select HEAT or COOL with SYSTEM switch.
  3. Press the or button to adjust the hour for the MORN (morning) event. Press PROG.
  4. Press the or button to adjust the minute for the MORN event. Press PROG.
  5. Press the or button to adjust the temperature for the MORN event. Press PROG.
  6. Repeat steps 3-5 for your DAY, EVE and NIGHT events.
  7. Repeat steps 3-6 for your Saturday and Sunday (S, SU) program.
  8. If needed, repeat steps 2-7to program the opposite mode (HEAT or COOL).
  9. Press RETURN to exit.Braeburn-2020NC-Programmable-Thermostats-fig-15

Operating Your Thermostat

Setting the System Control Mode
The System Control has several modes of operation that can be selected by moving the SYSTEM switch to the appropriate position.

  • COOL Only your cooling system will operate
  • OFF Heating and cooling systems are off
  • HEAT Only your heating system will operateBraeburn-2020NC-Programmable-Thermostats-fig-16

Additional Switch Position (Model 2220NC Only):

  • EMER Operates a backup heat source (Emergency Heat) for heat pump systems only
  • NOTE: If your model 2220NC was set for a conventional system (CONV) then you will not have the EMER (emergency heat) option and “NO EMER SET” will flash in the display if  EMER is selected with the system switch.Braeburn-2020NC-Programmable-Thermostats-fig-17

Setting the Fan Control Mode
The Fan Control has 2 modes of operation – AUTO and ON. The mode can be selected by moving the FAN switch to the appropriate position.

  • AUTO The system fan will run only when your heating or cooling system is running
  • ON The system fan stays onBraeburn-2020NC-Programmable-Thermostats-fig-18

Temperature Adjustment

Temporary Adjustment – Press the or button to adjust the current set point temperature.
Extended Adjustment – Press the HOLD button so that HOLD appears in the display screen. Press or to adjust the current set temperature (See “Extended Hold Period”, page 8).

Status Indicators

Status indicators appear in the display to let you know if your system is heating, cooling or off.

  • HEAT ON Indicates that your heating system is running.
  • COOL ON Indicates that your cooling system is running.
  • SERVICE Indicates that a user service reminder was selected (see “Service Filter Monitor, page 8).Braeburn-2020NC-Programmable-Thermostats-fig-19

Additional status indicators (Model 2220NC Only):

  • AUX  Indicates that the auxiliary stage of heating is running (multi-stage systems only).
  • EMER  Indicates that the emergency heating system is running (heat pump systems only).

Program Event Indicators
Program Event Indicators appear in the display to let you know what part of your current program is active. The 4 different program event indicators are MORN, DAY, EVE and NIGHT.
When the program event indicator is flashing, your program has been temporarily bypassed and will resume at the next scheduled event.
Note: You will not see a program event indicator while in HOLD Mode.

Resetting the Thermostat
This thermostat provides you with a reset button that will erase all of your user settings and programming.
To reset the thermostat, use a small object such as a tooth pick or paper-clip and gently press the button located inside the small hole on the front of the thermostat housing labeled “reset”.

Additional Operation Features

Compressor Protection
This thermostat includes an automatic compressor protection delay to help avoid potential damage to your system from short cycling. This feature activates a short delay after turning off the system compressor.

Thermostat MaintenanceBraeburn-2020NC-Programmable-Thermostats-fig-20

Changing the Batteries
Depending on your particular installation, this thermostat may be equipped with two (2) “AA” type alkaline batteries.
If batteries are installed and they become low, a low battery indicator will appear in the display. You should change your batteries immediately when you see the low battery signal by following these instructions.

  1. Remove thermostat body by gently pulling it from base.
  2. Remove old batteries and replace with new batteries.
  3. Make sure to correctly position the (+) and (-) symbols.
  4. Gently push thermostat body back onto base.Braeburn-2020NC-Programmable-Thermostats-fig-21

NOTE: We recommend replacing the thermostat batteries annually or if the thermostat will be unattended for an extended period of time.

Thermostat Cleaning
Never spray any liquid directly on the thermostat. Using a soft damp cloth wipe the outer body of the thermostat. Never use any abrasive cleansers to clean your thermostat.
Store this manual for future reference

Limited Warranty

When installed by a professional contractor, this product is backed by a 5 year limited warranty. Limitations apply. For limitations, terms and conditions, you may obtain a full copy of this warranty:

Braeburn Systems LLC
2215 Cornell Avenue

Montgomery, IL 60538
Technical Assistance: www.braeburnonline.com
Call us toll-free: 866-268-5599 (U.S.)
630-844-1968 (Outside the U.S.)
©2018 Braeburn Systems LLC
All Rights Reserved. Made in China.

REFERENCE

Download Manual

Braeburn 2020NC Programmable Thermostats User Guide

OTHER MANUALS

Braeburn 2020NC Programmable Thermostat Product Specifications

Braeburn-logo

Braeburn 2020NC Programmable Thermostats User Guide

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post’s permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post’s URL again. (Find out more about Webmentions.)