Bitron- 902010-32 -Home- Thermostat -FEA

Bitron 902010-32 Home Thermostat Technical Manual

Bitron-logo

Bitron 902010-32 Home Thermostat  

Bitron- 902010-32 -Home- Thermostat -PRO -

GENERAL CHARACTERISTICS

902010/32 is a ZigBee Home Automation-compliant Thermostat. It is a battery-powered device where a thermostat function, temperature measuring function and user interface function are all performed by the same device. The device is equipped with a bistable relay

ELECTRICAL CHARACTERISTICS

POWER SUPPLY 2×1,5V AA Size Battery
BATTERY LIFE TIME >2 years (at normal conditions)
 

 

 

WIRELESS CHARACTERISTICS

2405 MHz ÷ 2480 MHz

DSSS Modulation

Nominal transmission Power +8dBm Internal PCB Antenna

Chipset Ember/SiliconLabs EM357 Stack EmberZNet5.3.1

IEEE 802.15.4 compliant

 

 

 

ZIGBEE PROFILE

Home Automation Profile (HA1.2) Profile ID: 0x0104

End-Point: 1 (=1)

Device ID: 0x0301 (Thermostat)

In-Cluster List: 0x0000, 0x0001, 0x0003, 0x000A, 0x0020, 0x0201, 0x0204, 0x0B05

Binding Table Size: 10 Reporting Table Size: 10

 

MEASURES

NTC Sensor Type 103AT (10K at 25°C; beta=3435K) Measurement range -50°C ÷ +100°C

Reading resolution 0,1°C Reading accuracy ±0,5°C

 

RELAY

Bistable Relay

Contacts Rated Current 5A (resistive load) Expected life: 100.000 cycles with resistive load

OPERATING CONDITIONS -10 ÷ +55°C
PROTECTION CLASS IP20

DEVICE VIEW

Bitron- 902010-32 -Home- Thermostat -1

JOIN NETWORK
If the device is not part of a ZigBee Network (device not joined), press any of the buttons for at least 1 second to start the join process (Network Steering). During the Join process, the device will look search all available and try to join ZigBee networks for a duration of 10 seconds. If no open ZigBee HA network is found, the termostat will return to the unjoined state (“no NET” message on the LCD), until a further pairing attempt will be started. If the Join process was successful, the device will store the configuration and remain connected to the new ZB network

Bitron- 902010-32 -Home- Thermostat -2

LEAVING NETWORK
If the device is part of a ZigBee Network (device joined), within one minute from the device reset, enter the “Program”/”Leaving” menu to quit the network.Bitron- 902010-32 -Home- Thermostat -3

COMMISSIONING

  • If the device is part of a ZigBee Network, enter the “Program”/”Identify” menu to activate the EZ-Mode Target Finding and Binding commissioning process.
  • The process is also activated at the end of the Joining process, if a suitable network is found. During this process, the device activates its own identify state and opens the network.
  • This process lasts maximum 3 minutes during which the device shows “Iden” message.
  • The process ends earlier if a button is pressed.

CHANGING SETPOINT

  • By pressing the “+” or “-” button you will enter in the SetPoint change menu.
  • The activation of this menu is highlighted by the blinking message “SET”and the current value of the SetPoint will be shown.
  • Use the buttons to change the SetPoint temperature at intervals of 0,5° within the range of the minimum and maximum values configured.
  • The new Set-Point will be confirmed after 5 seconds of inactivity of the keyboard.Bitron- 902010-32 -Home- Thermostat -4

CHANGING MODE

  • The Thermostat Mode selectable depends by “Control Sequence of Operation” attribute (Attribute-ID=0x001B, Cluster-ID=0x0201).
  • By default it is possible to switch from “Heating Mode” to “Off Mode” and vice versa.
  • To switch-off the thermostat press “-” button until the Setpoint is below the minimum allowed (default 7°C); to switch-on the thermostat simply press “-” or “+” buttonBitron- 902010-32 -Home- Thermostat -5

TEMPERATURE ACQUISITION AND THERMO-REGULATION LOOP
902010/32 measures the ambient temperature every 30 seconds using the on-board NTC sensor. This time is fixed at firmware level. After the temperature measurement the thermo-regulation cycle will be executed in which the measured temperature value is compared with with the SetPoint value. The relay will be switched accordingly.

System Mode (Regulation Mode)
The behaviour of the thermo-regulation cycle is managed by the “System Mode” Attribute (AttributeID=0x001C, Cluster-ID=0x0201) which control the thermostat’s Off/Cool/Heat state.

System Mode Temperature In-equation Relay State
Off (0x00) // Off
 

 

Cool (0x03)

Temperature >=

(Cooling SetPoint + High_Hysteresis)

On
Temperature <=

(Cooling SetPoint – Low_Hysteresis)

Off
 

 

Heat (0x04)

Temperature >=

(Heating SetPoint + High_Hysteresis)

Off
Temperature <=

(Heating SetPoint – Low_Hysteresis)

On

THERMOSTAT SCHEDULER

  • 902010/32 supports the weekly schedule extension described in the ZigBee HA specification. It allows to configure 10 schedules for 8 days (Sunday to Saturday plus vacation day).
  • The whole structure is duplicate for heating and cooling mode allowing separate schedules for both functions.
  • Each schedule describes a Transitions Time expressed in minutes from midnight and a SetPoint value.
  • If scheduling is active, 902010/32 compares its local time with all the schedule-slots of the current day. Once a schedule point is reach, temperature will be set to SetPoint.

Enable Thermostat Scheduler:
The activation/deactivation of the Thermostat Scheduler is managed by bit#0 of “Thermostat-Programming-Operation-Mode” Attribute (Attribute-ID=0x0025, Cluster- ID=0x0201).

Scheduled Set-Point Overriding:
A manual or remote change to the SetPoint remains unchanged until the next scheduling.

Behaviour at Start-Up:
At the re-ignition of the 902010/32 after a power failure (or after a reset), the device searches for the first schedule-slot preceding the current time and loads the corresponding SetPoint, this unless the last change of the SetPoint has been remote, in which case the SetPoint will remain until the next scheduling.

ADVANCED PROGRAMMING MODE

By pressing the “+” and the “-” buttons together for more than five seconds you will enter in the “Advanced Programming Mode”.Bitron- 902010-32 -Home- Thermostat -6

LCD
This is the display of the device with all segments enabledBitron- 902010-32 -Home- Thermostat -7

Meaning of the icons

Bitron- 902010-32 -Home- Thermostat -8

ZIGBEE DATA AND REFERENCES

The following sections describes some ZigBee characteristics of the device. More detailed information can be found in the ZigBee Alliance documents quoted in the references.

REFERENCES:

  • [R1] ZigBee Document 075123r04ZB – ZigBee Cluster Library
  • [R2] ZigBee Document 05-3520-29 – ZigBee Home Automation Public Application Profile
  • [R3] ZigBee Document 075356r16ZB – ZigBee Smart Energy Profile Specification

HA.1) END-POINT

Device Name ZigBee Node Type End-Point Device ID Main Function
902010/32 Sleepy-end-device 1 0x0301 HA Thermostat

HA.2) CLUSTER LIST

Cluster Name End-Point Cluster-ID Client/Server
Basic 1 0x0000 Server
Power Configuration 1 0x0001 Server
Identify 1 0x0003 Client/Server
Time 1 0x000A Server
Over the Air Bootloading 1 0x0019 Client
Poll Control 1 0x0020 Server
Thermostat 1 0x0201 Server
Thermostat User Interface Configuration 1 0x0204 Server
Diagnostic 1 0x0B05 Server

HA.3) BINDING TABLE SIZE
The Device’s Binding Table (non-volatile) has room for 10 entries

HA.4) REPORTING TABLE SIZE
The Device’s Reporting Table (non-volatile) has room for 10 entries

HA.5) EZ-MODE COMMISSIONING
The Device acts as an EZ-Mode Target. When the EZ-Mode is invoked (by entering in the specific user-menu) it activates its identifying state for up to 3 minutes.

HA.6) POLLING RATE

  • 902010/32 is a Sleepy-End-Device, therefore it can receives radio messages only after it has sent to its parent (router) a Polling message (Data Request).
  • The parent device has the task to keep messages for their children until the receiving of the polling message, this up to a limit of 7,68 seconds (as requested by standard ZigBee HA).
  • During normal functioning, 902010/32 sends a poll message each 7 seconds.
  • After the pressure of any button, 902010/32 enters in a state of “fast polling” for the duration of 20 seconds, in this state it sends one polling per half second.
  • 902010/32 implements the Poll Control Cluster (Cluster-ID 0x0020), therefore it is possible to change the long poll interval and the fast poll interval, moreover it is possible to manage the “Check-in” server-side command in order to simplify the communication management in devices which wish to communicate with 902010/32. Note that the poll parameters strongly influence the battery lifetime.

HA.7) REJOIN MECHANISM

The Rejoin process is the process by which a sleepy-end-device already part of a network tries to find another parent (due to the fact that the old parent was deemed as not working). The rejoin process is very expensive in energy terms, so to preserve the battery life, has been chosen this rejoin strategy:

  • At beginning of the orphaning state rejoin each 2 minutes
  • After one hours, rejoin each 30 minutes

CL.1) SERVER SIDE CLUSTER DESCRIPTION – BASIC CLUSTER (CLUSTER-ID=0x0000)

Implemented Attributes

Attribute-ID Name Attribute Type Range Access Attribute Default Value
0x0000 ZCL Version 0x20

(int8u)

0x00÷0xFF R- 1
0x0001 Application Version 0x20

(int8u)

0x00÷0xFF R- 1
0x0002 Stack Version 0x20

(int8u)

0x00÷0xFF R- 2

(ZigBee Pro)

0x0003 HW Version 0x20

(int8u)

0x00÷0xFF R- 2
0x0004 Manufacturer Name 0x42

(String)

0÷32 bytes R- “Bitron Home”
0x0005 Model Identifier 0x42

(String)

0÷32 bytes R- “902010/32”
0x0006 Date Code 0x42

(String)

0÷16 bytes R- Serial number
0x0007 Power Source 0x30

(enum8)

0x00÷0xFF R- 0x03

(Battery)

0x4000 SW Build ID 0x42

(String)

0÷32 bytes R- Firmware build like: “V1b225-20151013”

Commands Received (Client to Server

Command-ID Name
0x00 Reset to Factory Defaults

CL.2) SERVER SIDE CLUSTER DESCRIPTION – POWER CONFIGURATION CLUSTER (CLUSTER-ID=0x0001)
Implemented Attributes:

Attribute-ID Name Attribute Type Range Access Attribute Default Value
0x0020 Battery Voltage 0x20

(int8u)

0x00÷0xFF R-
0x0035 Battery Alarm Mask 0x18

(bit8)

0x00÷0xFF RW 1
0x0036 Battery Voltage min Threshold 0x20

(int8u)

0x00÷0xFF RW 25

(2,5 V)

0x003E Battery Alarm State 0x1B

(bit32)

0÷ 232-1 R-

CL.3) SERVER SIDE CLUSTER DESCRIPTION – IDENTIFY CLUSTER (CLUSTER-ID=0x0003)
Implemented Attributes

Attribute-ID Name Attribute Type Range Access Attribute Default Value
0x0000 Identify Time 0x21

(int16u)

0x0000÷

0xFFFF

RW 0

Commands Received (Client to Server

Command-ID Name
0x00 Identify
0x01 Identify Query

Commands Generated (Server to Client):

Command-ID Name
0x00 Identify Query Response

CL.4) SERVER SIDE CLUSTER DESCRIPTION – TIME CLUSTER (CLUSTER-ID=0x000A)
Implemented Attributes:

Attribute-ID Name Attribute Type Range Access Attribute Default Value
0x0000 Time 0xE2

(UTC Time)

0÷ 232-1 RW 0
0x0001 Time Status 0x18

(bit8)

0000xxxx RW 0
0x0002 Time Zone 0x2B

(int32s)

-86400 ÷ +86400 RW 0
0x0003 Daylight Saving Time Start 0x23

(int32u)

0÷ 232-1 RW 0
0x0004 Daylight Saving Time End 0x23

(int32u)

0÷ 232-1 RW 0
0x0005 Daylight Saving Time Shift 0x2B

(int32s)

-86400 ÷ +86400 RW 0
0x0006 Standard Time 0x23

(int32u)

0÷ 232-1 R- 0

Note about Attribute Time Status (Attribute-ID 0x0001)
902010/32 allows only setting/resetting of bit#1 (Synchronized) of this Attribute.

Note about Attribute Valid Until Time (Attribute-ID 0x0009)
902010/32 sets this attribute with the value of UTC Time immediately after a setting of the time.

Time Reference

The time reference is required for the properly operation of the Thermostat Scheduler. 902010/32 is not provided with a backup-battery Real Time Clock (RTC) therefore it does not retain a precise time reference through the absence of power supply (batteryreplacement). The internal crystal oscillator used has an error of about ±100ppm, therefore the expected time reference error is about ±5 minutes per month.

Gateway Requirements

The customer’s Gateway has the responsibility of maintenance a more precise time reference, the setting of the correct TimeZone and the setting of the annual beginning/end of summer time (DST).

To do that the Gateway must:

  • implements the Server-Side Time Cluster (Cluster-ID 0x000A).
  • keeps its UTC Time Attribute (Attribute-ID 0x0000) as precise as possible.
  • sets the correct value to its TimeZone Attribute (Attribute-ID 0x0002).
  • sets the correct value to its (annually changing) Dst Start, Dst End, Dst Shift
  • Attributes (Attribute-ID 0x0003, 0x0004, 0x0005).
  • sets bit#0 (Master) and/or bit#3 (Superseding) and sets bit #2 (Master Zone Dst) on the Time Status Attribute (Attribute-ID 0x0001)

Time Reference Synchronization

  • 902010/32 synchronizes its time reference following the rules described in ZigBee Cluster Library Specification.
  • After a time between 2 and 10 minutes from the reset (chosen randomly), and every 24 hours post, 902010/32 looks for the best time server presents on its radio network.
  • If it finds a suitable time server then it collects the relevant time attributes.

Note on Time Attributes

  • The Utc Time Attribute (Attribute-ID 0x0000) is expressed in seconds from 1/1/2000.
  • Standard Time Attribute (Attribute-ID 0x0006) is calculated as:
  • Standard Time = Utc Time + TimeZone
  • Local Time Attribute (Attribute-ID 0x0007) is calculated as:
  • Local Time = Standard Time (if Utc Time is not between Dst Start and End)
  • Local Time = Standard Time + Dst Shift (if Utc Time is between Dst Start and End)
  • Thermostat Scheduler uses the Local Time Attribute.
  • All the time attributes except Utc Time, Standard Time and Local Time, are saved in nonvolatile memory.

CL.5) SERVER SIDE CLUSTER DESCRIPTION – POLL CLUSTER (CLUSTER-ID=0x0020)
Implemented Attributes:

Attribute-ID Name Attribute Type Range Access Attribute Default Value
0x0000 Check-in Interval 0x23

(int32u)

0 ÷

0x6E0000

RW 57600

(4 hours)

0x0001 Long Poll Interval 0x23

(int32u)

0 ÷

0x6E0000

R- 28

(7 sec)

0x0002 Short Poll Interval 0x21

(int16u)

0x0001 ÷

0xFFFF

R- 2

(0,5 sec)

0x0003 Fast Poll Time Out 0x21

(int16u)

0x0001 ÷

0xFFFF

RW 240

(60 sec)

0x0004 Check-in Interval Min 0x23

(int32u)

R- 180

(45 sec)

0x0005 Long Poll Interval Min 0x23

(int32u)

R- 20

(5 sec)

0x0006 Fast Poll Time Out Max 0x23

(int32u)

R- 480

(120 sec)

Commands Received (Client to Server):

Command-ID Name
0x00 Check-in Response
0x01 Fast Poll Stop
0x02 Set Long Poll Interval
0x03 Set Short Poll Interval

Commands Generated (Server to Client):

Command-ID Name
0x00 Check-in

Note about Check-in server to client command:

  • This command is sent to all devices which are bound with 902010/32 through the cluster Poll Control.
  • This command is sent at the frequency controlled by the Check-in Interval attribute.
  • This command expects a Check-in Response command sent back from the Poll Control Client.
  • If 902010/32 does not receive a Check-in Response it returns to the normal polling rate, according to the Long Poll Interval Attribute.
  • Note that the poll parameters strongly influence the 902010/32 battery lifetime. See specification [R2]

CL.6) SERVER SIDE CLUSTER DESCRIPTION – THERMOSTAT CLUSTER (CLUSTER-ID=0x0201)
Implemented Attributes

Attribute-ID Name Attribute Type Range Access Attribute Default
0x0000 Local Temperature 0x29

(int16s)

0x954D ÷ 0x7FFF R-
0x0001 Outdoor Temperature 0x29

(int16s)

0x954D ÷ 0x7FFF R-
0x0002 Occupancy 0x18

(bit8)

0000000x R- 1
0x0003 Abs Min Heat Setpoint Limit 0x29

(int16s)

0x954D ÷ 0x7FFF R- 700 (7°C)
0x0004 Abs Max Heat Setpoint Limit 0x29

(int16s)

0x954D ÷ 0x7FFF R- 300 (30°C)
0x0005 Abs Min Cool Setpoint Limit 0x29

(int16s)

0x954D ÷ 0x7FFF R- 1600 (16°C)
0x0006 Abs Max Cool Setpoint Limit 0x29

(int16s)

0x954D ÷ 0x7FFF R- 3200 (32°C)
0x0010 Local Temperature Calibration 0x28

(int8s)

0xE7 ÷ 0x19 RW 0 (0°C)
0x0011 Occupied Cooling Setpoint 0x29

(int16s)

Min ÷ Max Cool SetPoint Limit RW 2600 (26°C)
0x0012 Occupied Heating Setpoint 0x29

(int16s)

Min ÷ Max Heat SetPoint Limit RW 2000 (20°C)
0x0013 Unoccupied Cooling Setpoint 0x29

(int16s)

Min ÷ Max Cool SetPoint Limit RW 2600 (26°C)
0x0014 Unoccupied Heating Setpoint 0x29

(int16s)

Min ÷ Max Heat SetPoint Limit RW 2000 (20°C)
0x0015 Min Heat Setpoint Limit 0x29

(int16s)

0x954D ÷ 0x7FFF RW 700 (7°C)
0x0016 Max Heat Setpoint Limit 0x29

(int16s)

0x954D ÷ 0x7FFF RW 3000 (30°C)
0x0017 Min Cool Setpoint Limit 0x29

(int16s)

0x954D ÷ 0x7FFF RW 1600 (16°C)
0x0018 Max Cool Setpoint Limit 0x29

(int16s)

0x954D ÷ 0x7FFF RW 3200 (32°C)
0x001B Control Sequence Of Operation 0x30

(enum8)

0 ÷ 5 R- 2

(Heating)

0x001C System Mode 0x30

(enum8)

0 ÷ 5 RW 4

(Heat)

0x0020 Start Of Week 0x30

(enum8)

0 ÷ 6 R- 0
0x0021 Number Of Weekly Transitions 0x20

(int8u)

0 ÷ 0xFF R- 70
0x0022 Number Of Daily Transitions 0x20

(int8u)

0 ÷ 0xFF R- 10
0x0025 Thermostat Programming Operation Mode 0x18

(bit8)

00xxxxxx RW 0

Commands Received (Client to Server):

Command-ID Name
0x00 Setpoint Raise/Lower
0x01 Set Weekly Schedule
0x02 Get Weekly Schedule
0x03 Clear Weekly Schedule

Commands Generated (Server to Client

Command-ID Name
0x00 Current Weekly Schedule

Note about Attribute Local Temperature (Attribute-ID 0x0000)

  • This value represents the local temperature, measured by the built-in probe.
  • This value is used in the thermo-regulation cycle.

Note about Attribute Outdoor Temperature (Attribute-ID 0x0001)
Same value present on the above attribute.

Note about Attribute Occupancy (Attribute-ID 0x0002)
Currently the Occupancy sensor management is not yet implemented, the value of this attribute is fixed to 1 (space occupied).

Note about Attribute Local Temperature Calibration (Attribute-ID 0x0010)
This attribute is used to correct the temperature of the local thermal measure.

Note about Attribute Control Sequence Of Operation (Attribute-ID 0x001B)
This Attribute is used to permit or not the selection of Cooling and Heating Mode.

Control Sequence of Operation Description Possible values of System Mode
0x00 Cooling Only 0x00(Off) / 0x03(Cool)
0x01 Cooling with Reheat 0x00(Off) / 0x03(Cool)
0x02

(Default)

Heating Only 0x00(Off) / 0x04(Heat)
0x03 Heating with Reheat 0x00(Off) / 0x04(Heat)
0x04 Cooling and Heating 4-pipes 0x00(Off) / 0x03(Cool) / 0x04(Heat)
0x05 Cooling and Heating 4-pipes with Reheat 0x00(Off) / 0x03(Cool) / 0x04(Heat)

Note about Attribute System Mode (Attribute-ID 0x001C)
This Attribute is used to chose the thermo-regulation mode.

System Mode Description
0x00 Off
0x03 Cool
0x04

(Default)

Heat

Note about Attribute Thermostat Programming Operation Mode (Attribute-ID 0x0025)
Bit#0 of this attribute controls the enabling of the Thermostat Scheduler.

Note about Attribute SetPoint Change Source (Attribute-ID 0x0030)
This Attribute is used to determine the source of the last changing of the SetPoint.

SetPoint Change Source Description
0x00 Manual, user-initiated SetPoint change via the thermostat
0x01 Schedule/internal programming-initiated SetPoint change
0x02 Externally-initiated SetPoint change

Note about Thermostat Scheduler Programming (Command-ID 0x01)
The Thermostat Scheduler programming procedure follows the ZigBee HA specifications (see [R2], Paragraph 10.2.3.4.1.1 (Set Weekly Schedule), page 325).Bitron- 902010-32 -Home- Thermostat -9

Example:
you want the schedule will be made as follows:

  • Time 06.30 → SetPoint = 22,5°C
  • Time 08.30 → SetPoint = 18,0°C
  • Time 12.00 → SetPoint = 20,0°C

This only for days:
Monday, Tuesday, Thursday, Friday

This only for the Heat mode.

  • This translates into the programming of 6 schedule-slots. 1° slot:
    • Time 06.30 = 390 minutes from midnight = 0x0186
  • Heat SetPoint = 22,5°C = 2250 (cents)°C = 0x08CA 2° slot:
    • Time 08.30 = 510 minutes from midnight = 0x01FE
  • Heat SetPoint = 18,0°C = 1800 (cents)°C = 0x0708 3° slot:
    • Time 12.00 = 720 minutes from midnight = 0x02D0
    • Heat SetPoint = 20,0°C = 2000 (cents)°C = 0x07D0

To the right the message sent from Gateway to a 902010/32, captured by the Ember radio sniffer.

CL.7) SERVER SIDE CLUSTER DESCRIPTION THERMOSTAT USER INTERFACE CONFIGURATION CLUSTER (CLUSTER-ID=0x0204)
Implemented Attributes:

Attribute-ID Name Attribute Type Range Access Attribute Default
0x0000 Temperature Display Mode 0x30

(enum8)

0 ÷ 1 RW 0
0x0001 Keypad Lockout 0x30

(enum8)

0 ÷ 5 RW 0
0x0002 Schedule Programming Visibility 0x30

(enum8)

0 ÷ 1 RW 0

CL.8) SERVER SIDE CLUSTER DESCRIPTION – DIAGNOSTIC CLUSTER (CLUSTER-ID=0x0805)
Implemented Attributes:

Attribute-ID Name Attribute Type Range Access
0x0000 Number of Resets 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0104 Mac Tx Unicast Retry 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0105 Mac Tx Unicast Fail 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0106 APS Rx Broadcast 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0107 APS Tx Broadcast 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0108 APS Rx Unicast 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0109 APS Unicast Success 0X21 (int16u) 0 ÷ 0xFFFF R-
0x010A APS Tx Unicast Retries 0X21 (int16u) 0 ÷ 0xFFFF R-
0x010B APS Tx Unicast Failures 0X21 (int16u) 0 ÷ 0xFFFF R-
0x010C Route Discovery Initiated 0X21 (int16u) 0 ÷ 0xFFFF R-
0x010D Neighbour Added 0X21 (int16u) 0 ÷ 0xFFFF R-
0x010E Neighbour Removed 0X21 (int16u) 0 ÷ 0xFFFF R-
0x010F Neighbour Stale 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0110 Join Indication 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0111 Child Moved 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0112 NWK Frame Control Failure 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0113 APS Frame Control Failure 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0114 APS Unauthorized Key 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0115 NWK Decrypt Failures 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0116 APS Decrypt Failures 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0117 Packet Buffer Allocate Failures 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0118 Relayed Unicast 0X21 (int16u) 0 ÷ 0xFFFF R-
0x0119 Phy to MAC queue limit reached 0X21 (int16u) 0 ÷ 0xFFFF R-
0x011A Packet Validate drop count 0X21 (int16u) 0 ÷ 0xFFFF R-

CL.9) CLIENT SIDE CLUSTER DESCRIPTION – OVER THE AIR BOOTLOADING (CLUSTER-ID=0x0019)
902010/32 implements the Zigbee Over-the-air Bootload Client Cluster. The device periodically searches an OTA server in the network, if it finds it, then it periodically queries the server for a new image to download, if it finds a coherent andnewer firmware image, it downloads the data and, eventually, uses the downloaded image to update itself. The OTA server is searched by a “Match Description Request” done through a broadcast message, this is issued some minutes after the device reset and each about 4 hours, until an OTA server is found. If an OTA server has been found, the device requires for an upgrading image each about 4 hours. During the OTA downloading, the delay between packets is fixed to 1 second. Downloading the whole firmware image takes about an hour. The device does not implement the Image Page Request Command.

Client-Side implemented Attributes:

Attribute-ID Name Attribute Type Range Access Attribute Default
0x0000 OTA Upgrade Server ID 0xF0 (IEEE_ADDRESS) 0÷ 264-1 R- 0xFFFFFFFFFFFFFFFF
0x0001 Offset into the file 0x23

(int32u)

0÷ 232-1 R- 0
0x0006 Upgrade Status 0x30

(enum8)

0x00÷0xFF R- 0

CC.1) PROPRIETARY EXTENSIONS
The device has some manufacturer specific extensions added to the standard ZigBee command set. These functions can be accessed using the manufacturer code 0x1071.

CC.2) PROPRIETARY EXTENSIONS – BASIC CLUSTER (CLUSTER-ID=0x0000)
Vendor Specific Commands Received (Client to Server):

Command-ID Name Payload Size Payload
0xFC PROPRIETARY COMMAND 2 1° int16u: Command value

List of PROPRIETARY COMMAND values and the respective functions

Vendor COMMAND value Command Issued
0x196E Reload Default Parameters
0x196F non-volatile memory total initialize
0x1970 Reset
0x1971 Disassociation
0x1972 Disassociation with reload default parameters
0x1973 Disassociation with non-volatile memory total initialize
0x1975 Rejoin
0x2100 -:- 0x21FF Change Transmission Power

(value in the low byte, from -30 to 8)

0x2501 Initialize OTA external eeprom
0x2502 Restart OTA Server searching

CC.3) PROPRIETARY EXTENSIONS – THERMOSTAT CLUSTER (CLUSTER-ID=0x0201)
List of PROPRIETARY ATTRIBUTES:

Attribute-ID Name Attribute Type Range Access Attribute Default Value
0x0101 Thermostat High Hysteresis 0x21

(int16u)

0 ÷ 0x03E8 RW 25 (0,25°C)
0x0102 Thermostat Low Hysteresis 0x21

(int16u)

0 ÷ 0x03E8 RW 25 (0,25°C)
0x0201 Setpoint Change Source Network-ID 0x21

(int16u)

0 ÷ 0xFFFF RW 0xFFFF
0x0201 Gateway Link Timer 0x21

(int16u)

0 ÷ 0xFFFF RW 0

Note aboute Hysteresis Attributes (Attribute-ID 0x0101, 0x0102):
The two custom attributes control the high value of hysteresis (hysteresis added to the set-point) and the low value of hysteresis (hysteresis subtracted to the set-point). The default value of both these attributes is 0,25°C.

Note about custom Attribute Setpoint Change Source NetworkId (Attribute-ID 0x0201)
This is the Network-ID of the source of the last radio SetPoint change.

Note about custom Attribute Gateway Link Timer (AttributeID 0x0202)
If this attribute is set to a value different by zero, then it is decremented by 902010/32 by one unit per second. If the value of this attribute is different by zero the “Gateway” icon on the 902010/32 is switched on.

Bitron

REFERENCE

DOWNLOAD MANUAL

Bitron 902010-32 Home Thermostat Technical Manual

Bitron-logo

Bitron 902010-32 Home Thermostat Technical Manual


Posted

in

by

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post’s permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post’s URL again. (Find out more about Webmentions.)