Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FEATURED

Aprilaire 8820 Touch Screen Wi-Fi Automation Thermostat Safety & Installation Instructions

Aprilaire-logo

Aprilaire 8820 Touch Screen Wi-Fi Automation Thermostat 

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-PRODUCT

WI-FI SETUP

To connect the 8820 thermostats to a Wi-Fi network follow the steps below.
Note: You will need a computer or mobile device with Wi-Fi and a web browser.

  1. STEP 1
    Verify the thermostat is in Wi-Fi Connection Mode.
    The thermostat by default will be in Wi-Fi Connection Mode. To confirm that the thermostat is in Wi-Fi Connection Mode, verify that the radio bars on the thermostat are strobing as shown below.Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.1
    Note: If the thermostat is not in Wi-Fi Connection Mode, refer to the Owner’s Manual for instructions on clearing the Wi-Fi settings.
  2. STEP 2
    Connect to the thermostat using a computer or mobile device.
    On your computer or mobile device, scan for available networks. The thermostat should appear as APRILAIRE8820 followed by a unique identifier, corresponding to the last 6 digits of the MAC address. Connect to the thermostat you want to configure. If you are installing multiple thermostats, the MAC address of each thermostat will be displayed in the message center on the display of the thermostat. The MAC address can also be found by removing the cover on the front of the thermostat.
  3. STEP 3
    Configure the thermostat to connect to the Wi-Fi network.
    Open a web browser on your computer or mobile device. In the browser enter: http://192.168.1.99/index.html
    In the web browser interface select the network you want to connect the thermostat to and enter the network’s security credentials.
  4. STEP 4
    Verify the thermostat is connected to the Wi-Fi network.
  5. Once all the required information is entered in the web browser interface, the thermostat will connect to the Wi-Fi network you selected. After the thermostat is connected to the Wi-Fi network, the thermostat will display the radio bars based on the Wi-Fi signal strength. If the radio bars are not displaying the signal strength, refer to Troubleshooting Wi-Fi Connection on page 22.
    Note: If you are not using the thermostat with a home automation system, but are instead using an Aprilaire account to communicate with the thermostat, Automation Enable must be set to Aprilaire Cloud in the installer setup menu, refer to pages 8 & 9. Go to my.aprilaire.com and refer to Wi-Fi Thermostat App User Guide and then StartUp for instructions on connecting to Wi-Fi and registering to an Aprilaire account.

INSTALLATION

INSTALLATION LOCATION RECOMMENDATIONS

Thermostat should be mounted:

  • On an interior wall, in a frequently occupied space.
  • Approximately 5‘ above floor.
  • At least 18” from outside wall.
  • Thermostat can be mounted to a vertical junction box.

Do not mount thermostat:

  • Behind doors, in corners or other dead air spaces.
  • In direct sunlight, near lighting fixtures, or other appliances that give off heat.
  • On an outside or unconditioned area wall.
  • In the flow of a supply register, in stairwells, or near outside doors.
  • On a wall with concealed pipes or ductwork.

OUTDOOR TEMPERATURE SENSOR (INCLUDED)

Outdoor temperature can be measured by attaching the included 8052 sensor to the S1 and S2 terminals. The outdoor sensor must be enabled in the installer setup menu.

Heat pump models can use the outdoor temperature to effectively utilize the heat pump:

  • When the outdoor temperature is less than the Low Balance Point, the heat pump will be locked out and only auxiliary heating will be used to provide heating.
  • When the outdoor temperature is higher than the High Balance Point, the auxiliary heating will be locked out and Nonly the heat pump will be used to provide heating.

Indoor Air Quality functions can use the outdoor temperature sensor to:

  • Control humidification setpoint based on outdoor temperature to prevent condensation.
  • Lock out humidification for temperatures over 60°F or below -30°F.
  • Lock out ventilation based on high and/or low outdoor temperatures.
  • Display outdoor temperature on thermostat.

Outdoor temperature sensor should be mounted:

  • On side of building out of direct sunlight (north side recommended).
  • Above snow line.
  • At least 3’ away from exhaust vents and condensing lines.
  • Using less than 300’ of wire.
  • Do not route wires along 120 VAC lines.

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.2

REMOTE TEMPERATURE SENSOR (OPTIONAL)

A remote temperature sensor can be used for control if the thermostat is to be mounted in a concealed location or a remote sensor can be averaged with the thermostat sensor to control a large space. An 8051 flush mount or 8053 surface mount remote temperature sensor can be attached to the T1 and T2 terminals and mounted in a recommended area. The remote sensor must be enabled in the installer setup menu, and once enabled will override or be averaged with the thermostat’s internal temperature sensor, based on the setting.

Remote temperature sensor should be mounted:

  • On an interior wall, in a frequently occupied space.
  • Approximately 5‘ above floor.
  • At least 18” from outside wall.
  • Using less than 300’ of wire.

Do not mount remote sensor:

  •  Behind doors, in corners or other dead air spaces.
  • In direct sunlight, near lighting fixtures, or other appliances that give off heat.
  • On an outside or unconditioned area wall.
  • In the flow of a supply register, in stairwells, or near outside doors.
  • On a wall with concealed pipes or ductwork.
  • Near 120 VAC lines.

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.3

THERMOSTAT MOUNTING

  1. Remove the rear mounting plate from the thermostat.
  2. Pull wires through the opening on the back of the rear mounting plate.
  3. Position and level the mounting plate of the thermostat on wall and mark the hole locations with a pencil.
  4. Drill 1/4” holes and insert supplied anchors (drywall only).
  5. Place mounting plate over anchors, insert and tighten screws.
  6. Seal wire entry holes to prevent drafts affecting temperature readings.

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.4

POWER & RESET OPTIONS

The thermostat is powered from 24VAC. In the case of power loss the thermostat will maintain the clock for 24 hours. The thermostat has a memory backup that saves the thermostat settings in case of power interruption. The reset button located under the cover on the front of the thermostat can be used to reset the thermostat to factory defaults. The Installer System Settings will also be set to the default settings.

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.5

WIRING TERMINAL

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.6

  • RSB & RSA – Model 8081 or 8082 Support Module communication
  • I1 & I2 – Indoor Air Quality control output
  • C – Common
  • O/B – Reversing valve
  • Y – First stage cooling (conventional) / First stage compressor (heat pump)
  • Y2 – Second stage cooling (conventional) / Second stage compressor (heat pump)
  • G – Fan
  • RC – 24VAC supply cooling1
  • R – 24VAC supply heating1
  • W2 – Second stage heat (conventional) / Second stage auxiliary (heat pump)
  • W – First stage heat (conventional) / First stage auxiliary (heat pump)
  • L – System fault indicator (optional) (heat pump only)
  • S1 & S2 – outdoor temperature sensor (included)
  • T1 & T2 – remote temperature sensor (optional)
  • 1 Jumper between RC & R is used in single transformer systems (see wiring diagrams).

Wire specifications: 18-24 gauge thermostat wire

Installation notes:

  • Ensure power at the HVAC equipment is off.
  • Loosen screw terminals, insert stripped wire and re-tighten.
  • Push the excess wire back into the opening and plug the wall opening to prevent drafts.

CONVENTIONAL HEAT/COOL WIRING DIAGRAMS

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.7

HEAT PUMP WIRING DIAGRAMS

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.8

INDOOR AIR QUALITY EQUIPMENT WIRING DIAGRAMS

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.10

Note: The I1/I2 output is a dry contact closure. The humidifier wiring diagram assumes the control is powering a solenoid valve. The dehumidifier wiring diagram is for a normally open dry contact input. The ventilation diagram assumes the control is for a normally closed damper. Refer to the individual humidifier, dehumidifier or ventilation installation instructions for product-specific wiring details.

SUPPORT MODULE WIRING DIAGRAM

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.11

Note: Up to four Support Modules can be wired to the thermostat. Support Modules should be wired with CAT-5 wire. The total length of wire for all support modules should not exceed 1000 feet

SETUP & TESTING

EQUIPMENT TYPE SELECTION SWITCH (SW1)

This thermostat has the option of being used in heat pump or heat/cool systems. Switch SW1 located on the back of the thermostat’s face is used to select this option. This setting is displayed in the Installer System Settings under Equipment Type.

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.12

INSTALLER SETUP MENU

HOW TO ENTER THE INSTALLER SETUP MENU AND SELECT EQUIPMENT TO SETUP:
In the Installer Setup menu, Thermostat or Indoor Air Quality (IAQ) setup can be selected. If IAQ setup is selected, the user can then select to set up Air Cleaning, Humidification, Dehumidification or Ventilation.

  • Press [MODE] to set system to OFF.
  • Press [MENU] to enter main menu.
  • Press and hold [SETUP] for seven seconds, [INSTALL
  • SETUP] appears.
  • Press [INSTALL SETUP] to enter installer setup menu.
  • Press Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.18 to adjust the option.
  • Press [MENU] to exit.
  • Press [NEXT] to select option.
  • Note: If IAQ is selected prior to performing thermostat setup, the Installer System Setting for Outdoor Sensor will be presented prior to entering IAQ setup.Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.13

CHANGE SYSTEM SETTINGS

Press [NEXT] or [BACK] to page through the settings.
Press Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.18 to adjust the setting.
Press [DONE] to save and exit, or [CANCEL] to exit without saving.
The thermostat will discard changes and exit if nothing is pressed within 60 seconds.
To reset the Installer System Settings to the default settings, reset the thermostat by pressing the [RESET] button for 5 seconds

THERMOSTAT INSTALLER SYSTEM SETTINGS TABLE

The following table contains the system settings and their details. Default settings are shown in bold. Some settings are only available dependent upon the value of other settings.

 

System setting

 

Description

Factory default setting (bold) and setting range
00 . Automation Enable Selects if the thermostat connects with an automation system or an Aprilaire account . 0: Aprilaire Cloud

1: Automation System

01 . Equipment Type Equipment type set by SW1 . Heat/Cool

Heat Pump

02 . Temperature Scale Set the thermostat to Fahrenheit or Celsius mode . Fahrenheit

Celsius

03 . Reversing Valve Selects O or B operation . O – On in cooling

B – On in heating

04 . Control Setup Used to lockout heating or cooling outputs . Note: Only available if Equipment Type is set to Heat/Cool . Heat and Cool

Heat Only Cool Only

05 . Heat/Cool: Cooling Stages Heat Pump: Compressor

Stages

Heat/Cool: Number of Cooling Stages . Heat Pump: Number of Compressor Stages . One

Two

06 . Heat/Cool: Heating Stages Heat Pump: Aux Heat

Stages

Heat/Cool: Number of Heat Stages .

Heat Pump: Number of Auxiliary Heat Stages .

One

Two

07 . Heat/Cool: Fan Control in Heating

Heat Pump: Auxiliary Equipment Type

Heat/Cool: Determines if the thermostat or equipment controls the fan in heating .

Heat Pump: Auxiliary Equipment type .

Gas/Oil Heat (equipment controls fan) Electric Heat (thermostat controls fan)
08 . Extended Fan – Heat Extends fan operation after heat call ends . Disable

Enable (90 second extension)

09 . Extended Fan – Cool Extends fan operation after cool call ends . Disable

Enable (90 second extension)

10 . Temperature Sensor Offset Field adjustment of controlling temperature sensor(s) . (no offset applied)

-4°F to +4°F (-2°C to +2°C)

11 . Humidity Offset Field adjustment of internal RH sensor . 0 (no offset applied)

-5% to +5%

12 . Auto Changeover Enable or disable Auto Changeover mode . Disable

Enable

13 . Deadband Auto Changeover mode deadband . 3°F (1.5°C)

2°F to 9°F (1°C to 4 .5°C)

14 . Remote Sensor Select if remote sensor is attached, and if it is attached, if it is the primary control or averaged with the built-in sensor . If the remote sensor is the primary control it can be configured to use the built-in sensor as a back-up sensor . Not installed

Control no backup

Control with built-in backup

Average with thermostat built-in sensor

15 . Outdoor Sensor Selects if an outdoor temperature sensor is not installed, a wired sensor is installed, or the outdoor temperature is provided by the automation system . Note: Automation is only available if Automation Enable is set to Automation System . Not installed Installed Automation
18 . Compressor Min Off Time Minimum off time for compressor protection . 5 minutes

1 to 5 minutes

19 . Heating Min Off Time Minimum off time for heating . 2 minutes

1 to 5 minutes

20 . Equipment Min On Time Minimum on time for heating and cooling . 2 minutes

1 to 5 minutes

21 . Auto Changeover Time Minimum time between heating and cooling calls . 4 minutes

1 to 5 minutes

 

System setting

 

Description

Factory default setting (bold) and setting range
22 . First Stage Differential First stage differential . 1°F (0.5°C)

1°F to 9°F (0 .5°C to 4 .5°C)

23 . Second Stage Differential Second stage differential . 1°F (0.5°C)

1°F to 9°F (0 .5°C to 4 .5°C)

24 . Third Stage Differential Third stage differential . 1°F (0.5°C)

1°F to 9°F (0 .5°C to 4 .5°C)

25 . Fourth Stage Differential Fourth stage differential . 1°F (0.5°C)

1°F to 9°F (0 .5°C to 4 .5°C)

26 . Away Enables the Away feature . The Away feature allows the automation system or Aprilaire mobile and web apps to use a single button press to set the thermostat to a predefined setpoint(s) . The thermostat will hold the setpoint(s) until Away is canceled with the automation system or app or at the thermostat . Disable

Enable

27 . Heat Blast Enables the Heat Blast feature . Disable

Enable

28 . Blast Offset Amount of heating when Heat Blast is initiated . 3°F (1.5°C)

3°F to 5°F (1 .5°C to 2 .5°C)

37 . Stage Rate Accumulation of equipment run time in equipment staging determination .

1 = more rapid staging of equipment (comfort) . 5 = slower staging of equipment (economy) .

2

1 to 5 or “OFF” to ignore accumulated run time .

38 . Progressive Recovery Enable or disable progressive recovery . Disable

Enable

39 . Low Balance Point Outdoor temperature low balance point .

Note: This option is only available if the thermostat is set to Heat Pump and Outdoor Sensor is set to Installed or Automation .

20°F or -8°C

0°F to 60°F (-18°C to 12°C) or OFF to

ignore LBP

40 . High Balance Point Outdoor temperature high balance point .

Note: This option is only available if the thermostat is set to Heat Pump and Outdoor Sensor is set to Installed or Automation .

65°F or 14.5°C

0°F to 80°F (-18°C to 22°C) or OFF to

ignore HBP

41 . Program Format Enables the 7-day program . 7-Day

Non-Prog

42 . Reset Service Reminders Clears the Air Filter, Dehumidifier, Fresh Air, and HVAC service reminders if they are active and resets the start date to the current date . Clears the Change Water Panel reminder if it is active . If the reminder is set to Timed, the clock will be reset . No

Yes

43 . HVAC Service Reminder The period for displaying the “HVAC Service Reminder” message . Off

1 to 12 months or “Off” to disable

44 . Constant Backlight Enable constant, low intensity backlight . Disable

Enable

45 . Backlight Intensity Set the active backlight intensity .

Note: The minimum setting is 40% when Constant Backlight is enabled .

100 Percent

0 to 100 Percent

51 . Support Module Controlling Temp Sensors Sets the number of controlling support module temperature sensors . NONE

1 to 8

52 . Support Module Controlling RH Sensors Sets the number of controlling support module humidity sensors . NONE

1 to 4

53 . Display Monitor Support Module Sensor Selects if the temperature or humidity values from support modules that are configured for monitoring are displayed in the message center of the thermostat . No

Yes

INDOOR AIR QUALITY SYSTEM SETTINGS TABLES

The following tables contain the Indoor Air Quality system settings and their details. Default settings are shown in bold. Some settings are only present dependent upon the value of other settings. The use of the included outdoor temperature sensor (recommended) enables additional Indoor Air Quality functionality. If the outdoor temperature sensor was not enabled in the thermostat system settings, thermostat system setting 15, outdoor sensor, will be presented prior to entering the Indoor Air Quality system settings. Please refer to the Model 8820 Owner’s Manual for further information about thermostat features.

Air Cleaning System Settings Table

 

System setting

 

Description

Factory default setting (bold) and setting range
Air Cleaner Installed Selects if an air cleaner is installed . (If set to no, no other air cleaning settings will be available .) No

Yes

Change Air Filter Reminder The period for displaying the “Change Air Filter” message . Off

1 to 12 months or “Off” to disable

Humidifier System Settings Table
Note: A humidifier can only be installed if ventilation is not installed and Dehumidifier Control is not set to Whole
Home or AC w/IAQ Output

 

System setting

 

Description

Factory default setting (bold) and setting range
Humidifier Installed Selects if a humidifier is installed . Yes/On HVAC is used for applications where the humidifier is installed on the HVAC duct . Yes/Standalone is used for application where the humidifier is independent of the HVAC system . (If set to no, no other humidifier settings will be available .) No

Yes/On HVAC Yes/Standalone

Humidifier Mode Selects auto or manual mode . Auto mode controls humidity based on the humidity setting and outdoor temperature .

Manual mode controls humidity based on the %RH setpoint . (Auto mode is only available if outdoor sensor is set to Installed or Automation .)

Auto

Manual

Humidity Setpoint Deadband Selects the minimum difference between the humidifier and dehumidifier setpoints . (Only available if a humidifier is installed and dehumidifier control is set to air conditioner . Available in both set-ups .) 10 Percent RH

10 to 20 Percent RH

Humidifier Operation Selects when humidification is allowed to occur relative to heating and fan operation . Without Fan allows humidification to occur without the HVAC fan . This option should only be used when the humidifier is independent of the HVAC system . Note: Without Fan is only available when Humidifier Installed is set to Yes/Standalone . Heat Only Heat or Fan Forces Fan Without Fan
CAUTION: When Humidifier Operation is set to Without Fan the thermostat will turn on humidification without energizing the HVAC fan . Do not select this option when the humidifier is installed on the HVAC duct . Without airflow moisture can accumulate in the duct resulting in significant damage .
Change Water Panel Reminder Selects the when the “Change Water Panel” message is displayed . Off

1 Per Season

2 Per Season

300 Hours

600 Hours

Reminder Month (Change Water Panel Reminder set to 1 per Season)

 

First Reminder Month (Change Water Panel Reminder set to 2 per Season)

Change Water Panel Reminder set to 1 per Season: Determines the month the “Change Water Panel” message is displayed .

 

Change Water Panel Reminder set to 2 per Season: Determines the first month the “Change Water Panel” message is displayed .

October November December January February March April

May June July August

September

Second Reminder Start Month Determines the second month the “Change Water Panel” message is displayed . (Only available when Change Water Panel Reminder set to 2 per Season .) October November December January February March April

May June July August

September

Dehumidifier System Settings Table
Note: Dehumidifier Control can only be set to Whole Home or AC w/IAQ Output if ventilation and humidification are not installed.

 

System setting

 

Description

Factory default setting (bold) and setting range
Dehumidifier Control Selects method of dehumidification . If set to None, no other dehumidifier settings will be available . If dehumidification is done with the air conditioner, using the option of AC w/IAQ Output will cause the IAQ output to be active when overcooling for dehumidification . This can be used if the HVAC equipment has a dedicated input to slow the fan during cooling to maximize dehumidification . None (no dehumidification installed) Whole Home

Air Conditioner AC w/IAQ Output

Humidity Setpoint Deadband Select the minimum difference between the humidifier and dehumidifier setpoints . (Only available if a humidifier is installed and Dehumidifier Control is set to Air Conditioner . Available in both set-ups .) 10 Percent RH

10 to 20 Percent RH

Lockout Dehumidifier During Cooling Selects if dehumidification is disabled during a cooling call . (Only available if Dehumidifier Control is set to Whole Home .) No

Yes

Dehumidifier Forces Fan Select if dehumidification can turn on the fan . (Only available if Dehumidifier Control is set to Whole Home .) No

Yes

Dehumidifier Service Reminder The period for displaying the “Dehum Service Reminder” message . (Only available if Dehumidifier Control is set to Whole Home .) Off

1 to 12 months or “Off” to disable

Dehumidifier Overcooling Limit Selects the amount of overcooling that can occur for dehumidification . (Only available if Dehumidifier

Control is set to Air Conditioner or AC w/IAQ Output .)

3°F (1.5°C)

1°F to 3°F (0 .5°C to 1 .5°C)

Dehumidify in Vacation Mode Selects if dehumidification with the air conditioner is done in Vacation Mode . (Only available if Dehumidifier Control is set to Air Conditioner or AC w/IAQ Output . No

Yes

Vacation Dehumidifier Low Temp Limit Sets the lowest temperature the air conditioner will cool to, to meet RH setpoint in Vacation Mode . (Only

available if Dehumidifier Control is set to Air Conditioner or AC w/IAQ Output .)

75°F (23.5°C)

70°F to 85°F (21°C to 28 .5°C)

Ventilation System Settings Table
Note: Ventilation can only be installed if humidification is not installed and Dehumidifier Control is not set to Whole Home or AC w/IAQ Output.

 

System setting

 

Description

Factory default setting (bold) and setting range
Fresh Air Vent Installed Selects if ventilation is installed . (If set to No, no other ventilation settings will be available .) No

Yes

Fresh Air Setup Type Selects if ventilation is configured through the Code setup or Comfort . Comfort setup has more lockout options . Code setting ensures missed lockout time is made up . Comfort

Code

Number of Bedrooms Selects the number of bedrooms to be used for the Calculated Minutes per Hour . 3 Bedrooms

1 to 10 Bedrooms

Home Size Selects the size of the home to be used for the Calculated Minutes per Hour . 2500 SQ FT

500 to 7500 SQ FT

Measured CFM Selects the ventilation CFM to be used for the Calculated Minutes per Hour . 110 CFM

30 to 250 CFM

Calculated Minutes per Hour Displays the Fresh Air Time calculated . None

Range 6 to 60 Minutes

Override Manual adjustment of Calculated Minutes per Hour . (Calculated Minutes per Hour)

Range 6 to 60 Minutes

Enable High Vent RH Limit Selects if ventilation is disabled if the indoor RH exceeds the indoor RH limit . (Only available if Fresh Air Setup is set to Comfort .) Yes

No

High Vent RH Limit Sets the ventilation indoor RH lockout limit . (Only available if Enable High Vent RH Limit is set to Yes .) 55%

45% to 70%

Enable Low Vent RH Limit Selects if ventilation is disabled if the indoor RH exceeds the indoor RH limit . (Only available if Fresh Air Setup is set to Comfort .) No

Yes

Low Vent RH Limit Sets the ventilation indoor RH lockout limit . (Only available if Enable Low Vent RH Limit is set to Yes .) 20%

10% to 30%

Enable High Vent Temperature Limit Enables high ventilation temperature lockout limit . (Only available if Outdoor Sensor is set to Installed or Automation .) No

Yes

High Vent Temperature Limit Sets high ventilation temperature lockout limit . (Only available if Enable High Vent Temperature Limit is set to Yes .) 100°F (38°C)

85°F to 105°F (29°C to 41°C)

Enable Low Vent Temperature Limit Enables low ventilation temperature lockout limit . (Only available if Outdoor Sensor is set to Installed or Automation .) No

Yes

 

System setting

 

Description

Factory default setting (bold) and setting range
Low Vent Temperature Limit Sets low ventilation temperature lockout limit . (Only available if Enable Low Vent Temperature Limit is set to Yes .) 10°F (-12°C)

-10°F to 40°F (-24°C to 6°C)

HVAC Fan with Vent Selects if ventilation forces the fan on . (Yes with high and low limits is only available if Outdoor Sensor is set to Installed or Automation .) Yes

Yes with high and low limits No

Enable High Mixing Temperature Enables high mixing temperature . (Only available is HVAC Fan with Vent is set to Yes with high and low limits .) No

Yes

High Mixing Temperature Sets the high mixing temperature . (Only available if Enable High Mixing Temperature is set to Yes .) 80°F or (26°C)

60°F to 105°F (14°C to 41°C)

Enable Low Mixing Temperature Enables low mixing temperature . (Only available is HVAC Fan with Vent is set to Yes with high and low limits .) No

Yes

Low Mixing Temperature Sets the Low mixing temperature . (Only available if Enable Low Mixing Temperature is set to Yes .) 40°F (6°C)

0°F to 50°F (-18°C to 12°C)

Fresh Air Service Reminder The period for displaying the “SERVICE FRESH AIR” message . OFF

1 to 12 months or “OFF” to disable

Note: Refer to manuals for humidifier, dehumidifier, air cleaner, and ventilation products for recommended installation and operation.

REMOVAL OF INDOOR AIR QUALITY CONTROL BUTTONS

If any of the Indoor Air Quality control features are not installed, the corresponding button can be removed using the following procedure:

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.15

  1. Step 1: Verify the specific Indoor Air Quality control feature is not installed in the Installer System Settings.
  2. Step 2: From the home screen , press and hold the
    Indoor Air Quality button you wish to remove for 7 seconds.
  3. Step 3: The message center will display the REMOVE BUTTON and the options of NO and YES (NO will be flashing).
  4. Step 4: Press or to select YES.
  5. Step 5: Press [DONE].
  6. Step 6: The button is now removed.
    Note: Once the button is removed it can be brought back by installing the corresponding Indoor Air Quality feature.

SYSTEM TEST MENU

The system test menu is used to test a system after installation. The outputs of the thermostat can be manually activated to test their function. The instructions below show how to enter the test mode and turn outputs on and off.

HOW TO ENTER THE SYSTEM TEST MENU:
Press [MODE] to set system to off.
Press and hold [FAN] and [MODE] for three seconds to enter system test mode.
The first screen of the installer test displays the equipment configuration.
Press [NEXT] to enter the first installation test or [CANCEL] to exit.

SYSTEM TEST STEPS
Heating equipment test
Cooling equipment test
Fan equipment test
Humidification equipment test
Dehumidification equipment test
Ventilation equipment test

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.16

Each equipment test will begin with the selection of turning on the output or stage as shown below.
Press or to change the selection.
Press [NEXT] to accept the selection and proceed to the next step.
If YES is selected, the thermostat will test the corresponding output. If NO is selected, the thermostat will proceed to the next step.

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.16

While the equipment test is active the corresponding test information will be shown.
Press [NEXT] to accept the selection and proceed to the next test selection.

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.17

SYSTEM TEST TABLES

Heat / Cool Heating Equipment Test
Heat Type W W2 Y Y2 G
Gas 1st Stage Test ON
Gas 2nd Stage Test ON ON
Electric 1st Stage Test ON ON
Electric 2nd Stage Test ON ON ON
Heat Pump Heating Equipment Test (Electric Heat)
Compressor Stages Aux Stages  

W

 

W2

 

Y

 

Y2

O/B set to  

G

O B
1 1 1st Stage Test ON ON ON
1 1 2nd Stage Test ON ON ON ON
2 1 1st Stage Test ON ON ON
2 1 2nd Stage Test ON ON ON ON
2 1 3rd Stage Test ON ON ON ON ON
1 2 1st Stage Test ON ON ON
1 2 2nd Stage Test ON ON ON ON
1 2 3rd Stage Test ON ON ON ON ON
2 2 1st Stage Test ON ON ON
2 2 2nd Stage Test ON ON ON ON
2 2 3rd Stage Test ON ON ON ON ON
2 2 4th Stage Test ON ON ON ON ON ON
Heat Pump Heating Equipment Test (Gas Heat)
Compressor Stages Aux Stages  

W

 

W2

 

Y

 

Y2

O/B set to  

G

O B
1 1 1st Stage Test ON ON ON
1 1 2nd Stage Test ON ON
2 1 1st Stage Test ON ON ON
2 1 2nd Stage Test ON ON ON ON
2 1 3rd Stage Test ON ON
1 2 1st Stage Test ON ON ON
1 2 2nd Stage Test ON ON
1 2 3rd Stage Test ON ON ON
2 2 1st Stage Test ON ON ON
2 2 2nd Stage Test ON ON ON ON
2 2 3rd Stage Test ON ON
2 2 4th Stage Test ON ON ON
Heat / Cool Cooling Equipment Test
W W2 Y Y2 G
1st Stage Test ON ON
2nd Stage Test ON ON ON
Heat Pump Cooling Equipment Test
 

W

 

W2

 

Y

 

Y2

O/B set to  

G

O B
1st Stage Test ON ON ON
2nd Stage Test ON ON ON ON
Fan Equipment Test
W W2 Y Y2 G
ON
Humidification Equipment Test
I1/ I2 G
ON ON
Dehumidification Equipment Test
I1/ I2 G
ON ON
Ventilation Equipment Test
I1/ I2 G
ON ON

QUICK REFERENCE TO CONTROLS & DISPLAY

HOME SCREEN

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.20

MAIN MENU

Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.21

TROUBLESHOOTING

DISPLAY IS BLANK

  • Check circuit breaker and reset if necessary.
  • Make sure power switch at heating & cooling system is on.
  • Make sure furnace door is closed securely.

HEATING SYSTEM DOES NOT RESPOND (“HEATING” APPEARS ON SCREEN)

  • Check for 24VAC at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the heating equipment to find the cause of the problem.
  • Check for 24VAC between the heat terminal (W) and the transformer common. If 24VAC is present, the thermostat is functional. Check the heating equipment to find the cause of the problem.
  • Check for loose or broken wires between the thermostat and the heating equipment.

TEMPERATURE SETTINGS DO NOT CHANGE
Make sure heating and cooling temperatures are set to acceptable ranges:

  • Heat: 40° to 90°F (4° to 32°C).
  • Cool: 50° to 99°F (10° to 37°C).

THE COOLING SYSTEM DOES NOT RESPOND (“COOLING” APPEARS ON SCREEN)

  • Check for 24VAC at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the cooling equipment to find the cause of the problem.
  • Check for 24VAC between the cooling terminal (Y) and the transformer common. If 24VAC is present, the thermostat is functional. Check the cooling system to find the cause of the problem.
  • Check for loose or broken wires between the thermostat and the cooling equipment.
  • FAN DOES NOT TURN ON IN A CALL FOR HEAT
  • Check System Setting 07 (Fan Control), to make sure the fan control is properly set to match the type of system (see page 9)

HEAT PUMP ISSUES COOL AIR IN HEAT MODE, OR WARM AIR IN COOL MODE

  • Check System Setting 03 (O/B Operation) to make sure the reversing valve operation matches the heat pump.

HEAT/COOL BOTH ON AT THE SAME TIME

  • Check SW1 (Equipment Type), to make sure it is set to match the installed heating/cooling equipment.
  • Check to make sure heating and cooling wires are not shorted together.

HEATING EQUIPMENT IS RUNNING IN COOL MODE

  • Check SW1 (Equipment Type), to make sure it is set to match the installed heating/cooling equipment (see page 8).

“HEATING” IS NOT DISPLAYED

  • Check Installer System Setting number 04 (Control Setup) is set correctly.
  • Change the System Mode to Heat, and set the temperature level above the current room temperature.

“COOLING” IS NOT DISPLAYED
HUMIDIFIER DOES NOT OPERATE IN AUTO MODE

  • Check Installer System Setting number 04 (Control Setup) is set correctly.
  • Change the System Mode to Cool, and set the temperature level below the current room temperature.
  • Check Installer System Setting number 15 (Outdoor Sensor) is set to Installed or Automation.
  • Verify that the outdoor sensor is functioning correctly or if it is set to Automation that it has not timed out. If the sensor is functioning correctly the outdoor temperature will display in the outdoor temperature location (see Home Screen on page 20 for the location).

TROUBLESHOOTING WI-FI CONNECTION

The Wi-Fi connection status is communicated through the use of the radio strength indicator and the message center.
The table below describes the various statuses and the corresponding message and radio bar display.Aprilaire-8820-Touch-Screen-Wi-Fi-Automation-Thermostat-FIG.22

ERROR CODES

If the thermostat enters an error mode, all outputs are turned off. The thermostat attempts to recover every 10 minutes.

Error code Message Error Description
01  

“SENSOR ERROR”

Open temperature sensor circuit
02 Shorted temperature sensor circuit
03 “EEPROM ERROR” Error in permanent memory
06  

“REMOTE SENSOR ERROR”

Open remote temperature sensor circuit
07 Shorted remote temperature sensor circuit
08 “SUPPORT MODULES LOST” All support modules with controlling temperature sensors are in error

THERMOSTAT FEATURES

  • Remote access and control over Wi-Fi.
  • Indoor air quality control.
    • Humidification automatic or manual control.
    • Dehumidification.
    • Event-Based™ air cleaning.
    • Ventilation with temperature and humidity limits.
  • Temperature control.
  • Heat Blast® raises the room temperature 3°F to 5°F.
  • Large touch screen with adjustable backlight – constant backlight option available.
  • Message center provides feedback and instructions.
  • 7 day programmability.
  • Displays room temperature, room humidity, temperature setting, and outdoor temperature.
  • Air filter, humidifier, dehumidifier, fresh air, and HVAC service reminders.
  • Programmable fan control with fan circulation mode.
  • Easy to use temperature control can override program schedule at any time.
  • Progressive recovery ensures proper temperature at the start of a program event.
  • Built in compressor protection prevents damage to your equipment.
  • ystem test mode.

SPECIFICATIONS

Environment
Temperature Operating: 32° to 120°F (0° to 48 .9°C) Shipping: -30° to 150°F (-34 .4° to 65 .5°C)
Relative humidity Operating: 5% to 90% R .H . (non-condensing)
Electrical
Operating voltage 24VAC (18 – 30VAC)
Current Maximum: 2 .5A (total), 1 .0A (single output) Maximum surge current: 5A
Thermal
Outdoor & Remote temperature sensor Maximum distance: 300 feet
Room temperature measurement Display range: 32° to 99°F (0° to 40°C)
Outdoor temperature measurement Display range: -40° to 130°F (-40° to 55°C)
Setpoint temperature range Heat: 40° to 90°F (4° to 32°C) Cool: 50° to 99°F (10° to 37°C)
Setpoint humidity range Humidification: 10% to 50% R .H .

Dehumidification: 40% to 90% R .H .

P.O. Box 1467
Madison, WI 53701-1467

Phone: 800/334-6011
Fax: 608/257-4357
www.aprilairepartners.com
61001112 2.17
B2206474D
U.S. Patent Numbers 8,146,376, 8,596,078, and other patents are pending.
© 2017 Aprilaire – A division of Research Products Corporation

REFERENCE:

Download Manual: Aprilaire 8820 Touch Screen Wi-Fi Automation Thermostat Safety & Installation Instructions

Aprilaire-logo

Aprilaire 8820 Touch Screen Wi-Fi Automation Thermostat Safety & Installation Instructions


Posted

in

by

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *