Aprilaire 8810 TouchScreen Wi-Fi Thermostat

Aprilaire-8810-TouchScreen-Wi-Fi-Thermostat-prduct

WI-FI SETUP

To connect the 8810 thermostats to a Wi-Fi network follow the steps below.

Note: You will need a computer or mobile device with Wi-Fi and a web browser.

  1. STEP 1
    Verify the thermostat is in Wi-Fi Connection Mode.Aprilaire-8810-TouchScreen-Wi-Fi-Thermostat-fig-1
    The thermostat by default will be in Wi-Fi Connection Mode. To confirm that the thermostat is in Wi-Fi Connection Mode, verify that the radio bars on the thermostat are strobing as shown below.
    Note: If the thermostat is not in Wi-Fi Connection Mode, refer to the Owner’s manual for instructions on clearing the Wi-Fi settings.
  2. STEP 2
    Connect to the thermostat using a computer or mobile device
    • On your computer or mobile device, scan for available networks. The thermostat should appear as APRILAIRE8810 followed by a unique identifier, corresponding to the last 6 digits of the MAC address.
    • Connect to the thermostat you want to configure.
    • If you are installing multiple thermostats, you can determine the MAC address of the specific thermostat you are trying to configure by removing the cover on the front of the thermostat to access the MAC address label.
  3. STEP 3
    • Configure the thermostat to connect to the Wi-Fi network.
    • Open a web browser on your computer or mobile device. In the browser enter: http://192.168.1.99/index.html
    • In the web browser interface select the network you want to connect the thermostat to, and enter the network’s security credentials.
  4. STEP 4
    Verify the thermostat is connected to the Wi-Fi network.
    • Once all the required information is entered in the web browser interface, the thermostat will connect to the Wi-Fi network you selected. After the thermostat is connected to the Wi-Fi network, the thermostat will display the radio bars based on the Wi-Fi signal strength. If the radio bars are not displaying the signal strength, refer to Wi-Fi Maintenance and Troubleshooting in the Owner’s manual.
      Note: If you are not using the thermostat with a home automation system, but are instead using an Aprilaire account to communicate with the thermostat, refer to Wi-Fi Thermostat App User Guide and then Start Up on my.aprilaire.com for instructions on connecting to Wi-Fi and registering to an Aprilaire account.

INSTALLATION

INSTALLATION LOCATION RECOMMENDATIONS

The thermostat should be mounted:

Do not mount the thermostat:

OUTDOOR TEMPERATURE SENSOR (OPTIONAL)

Heat pump applications can use the outdoor temperature to effectively utilize the heat pump:

THERMOSTAT MOUNTING

  1. Remove the rear mounting plate from the thermostat.
  2. Pull wires through the opening on the back of the rear mounting plate.
  3. Position and level the mounting plate of the thermostat on wall and mark the hole locations with a pencil.
  4. Drill 1/4” holes and insert supplied anchors (drywall only).
  5. Place a mounting plate over anchors, insert and tighten screws.
  6. Seal wire entry holes to prevent drafts affecting temperature readings.Aprilaire-8810-TouchScreen-Wi-Fi-Thermostat-fig-2

POWER & RESET OPTIONS

WIRING TERMINAL

SETUP & TESTING

SYSTEM SETUP INSTRUCTIONS

The following instructions show how to enter the system setup menu and change settings. The table on the following pages lists the settings and their details. Default settings are shown in bold. Some settings are only available based on other setting values.

How to enter the system setup menu to change system settings

 

System setting

 

Description

Factory default setting (bold) and setting range
00 . Automation Enable Selects if the thermostat connects with an automation system or an Aprilaire account . 0: Aprilaire Cloud

1: Automation System

01 . Equipment Type Equipment type set by SW1 . 0: Heat/Cool

1: Heat Pump

02 . Temperature Scale Set the thermostat to Fahrenheit or Celsius mode . 0: Fahrenheit

1: Celsius

03 . Reversing Valve Selects O or B operation . 0: O – On in cooling

1: B – On in heating

04 . Control Setup Used to lockout heating or cooling outputs .

Note: Only available if Equipment Type is set to Heat/Cool .

0: Heat and Cool

1: Heat Only

2: Cool Only

05 . Heat/Cool: Cooling Stages Heat Pump: Compressor

Stages

Heat/Cool: Number of Cooling Stages . Heat Pump: Number of Compressor Stages . 0: One

1: Two

06 . Heat/Cool: Heating Stages Heat Pump: Aux Heat

Stages

Heat/Cool: Number of Heat Stages .

Heat Pump: Number of Auxiliary Heat Stages .

0: One

1: Two

 

System setting

 

Description

Factory default setting (bold) and setting range
07 . Heat/Cool: Fan Control in Heating

Heat Pump: Auxiliary Equipment Type

Heat/Cool: Determines if the thermostat or equipment controls the fan in heating .

Heat Pump: Auxiliary Equipment type .

0: Gas/Oil Heat (equipment controls fan)

1: Electric Heat (thermostat controls fan)

10 . Temperature Sensor Offset Field adjustment of temperature sensor . (no offset applied)

-4°F to +4°F (-2°C to +2°C)

12 . Auto Changeover Enable or disable auto changeover mode . 0: Disable

1: Enable

13 . Deadband Auto Changeover mode deadband . 3°F (1.5°C)

2°F to 9°F (1°C to 4 .5°C)

15 . Outdoor Sensor Selects if an outdoor temperature sensor is not installed, a wired sensor is installed, or the outdoor temperature is provided by the automation system .

Note: Automation is only available if Automation Enable is set to Automation .

0: Not installed

1: Installed

2: Automation

18 . Compressor Min Off Time Minimum off time for compressor protection . 5 minutes

1 to 5 minutes

 

System setting

 

Description

Factory default setting (bold) and setting range
19 . Heating Min Off Time Minimum off time for heating . 2 minutes

1 to 5 minutes

20 . Equipment Min On Time Minimum on time for heating and cooling . 2 minutes

1 to 5 minutes

22 . First Stage Differential First stage differential . 1°F (0.5°C)

1°F to 9°F (0 .5°C to 4 .5°C)

23 . Second Stage Differential Second stage differential . 1°F (0.5°C)

1°F to 9°F (0 .5°C to 4 .5°C)

24 . Third Stage Differential Third stage differential . 1°F (0.5°C)

1°F to 9°F (0 .5°C to 4 .5°C)

25 . Fourth Stage Differential Fourth stage differential . 1°F (0.5°C)

1°F to 9°F (0 .5°C to 4 .5°C)

26 . Away Enables the Away feature . The Away feature allows the automation system or Aprilaire mobile and web apps to use a single button press to set the thermostat to a predefined setpoint(s) . The thermostat will hold the setpoint(s) until Away is canceled with the automation system or app or at the thermostat . 0: Disable

1: Enable

 

System setting

 

Description

Factory default setting (bold) and setting range
27 . Heat Blast Enables the Heat Blast® feature . The Heat Blast feature is only available with the automation system or Aprilaire mobile and web apps, and will raise the current room temperature 3°F to 5°F based on the Blast Offset and then resume normal operation . Heat Blast can be canceled with the automation system or the Aprilaire mobile and web apps, or at the thermostat . 0: Disable

1: Enable

28 . Blast Offset Amount of heating when Heat Blast is initiated . 3°F (1.5°C)

3°F to 5°F (1 .5°C to 2 .5°C)

37 . Stage Rate Accumulation of equipment run time in equipment staging determination .

1 = more rapid staging of equipment (comfort) . 5 = slower staging of equipment (economy) .

2

1 to 5 or “OFF” to ignore accumulated run time .

38 . Progressive Recovery Enable or disable progressive recovery . 0: Disable

1: Enable

39 . Low Balance Point Outdoor temperature low balance point .

Note: This option is only available if the outdoor sensor is set to Installed or Automation .

20°F or -8°C

0°F to 60°F (-18°C to 12°C) or OFF to

ignore LBP

 

System setting

 

Description

Factory default setting (bold) and setting range
40 . High Balance Point Outdoor temperature high balance point .

Note: This option is only available if the outdoor sensor is set to Installed or Automation .

65°F or 14.5°C

0°F to 80°F (-18°C to 22°C) or OFF to

ignore HBP

41 . Program Format Enables the 7 day program . 0: 7-Day

1: Non-Prog

54 . Change Air Filter Reminder The period displaying the Change Air Filter reminder . OFF

1 to 12 months

55 . Change Water Panel Reminder The time until the first Change Water Pnl message is displayed . OFF

1 to 12 months

56 . Humidifier Type Selects the type of humidifier . If humidifier type is set to Drain-less, then the first reminder is based on the system setting 55, the second reminder will activate 3 months later . If humidifier type is set to Flow through, then the first reminder is based on system setting 55, the second reminder will activate 12 months later . 0: Flow through type humidifier (1 reminder per season)

1: Drain-less type humidifier (2 reminders per season)

SYSTEM TEST MODE

Test Number Heat/Cool Heat Pump
50 Heating (W) (W2) Compressor Heating (Y) (Y2)
51 Aux Heating (W) (W2)
52 Cooling (Y) (Y2) Compressor Cooling (Y) (Y2)
53 Fan (G) Fan (G)

How to enter the system test menu

Test steps for Heat/Cool
 

Step

 

Key Input

System Setting Display (Output)
 

#07

01

HEATING ON (W)

02

HEATING ON (W2)

01

COOLING ON (Y)

02

COOLING ON (Y2)

01

FAN ON (G)

 

 

#50 Heat

1st [UP] 0 : Gas ON
1 : Elec ON ON
2nd [UP] 0 : Gas ON ON
1 : Elec ON ON ON
[DOWN]
 

#52 Cool

1st [UP] ON ON
2nd [UP] ON ON ON
[DOWN]
#53 Fan [UP] ON
[DOWN]
Test steps for Heat Pump
 

Step

 

Key Input

System Setting Display (Output)
 

#07

 

#03

01 AUX HEATING ON (W) 02 AUX HEATING ON (W2) 01

COOL/HEAT ON (Y)

02

COOL/HEAT ON (Y2)

01

FAN ON (G)

 

O/B

 

 

 

#50 Heat

1st [UP] 0 : O ON ON
1 : B ON ON ON
2nd [UP] 0 : O ON ON ON
1 : B ON ON ON ON
[DOWN] 0 : O
1 : B ON
 

 

#51 Aux

1st [UP] 0 : Gas ON
1 : Elec ON ON
2nd [UP] 0 : Gas ON ON
1 : Elec ON ON ON
[DOWN]
 

 

 

#52 Cool

1st [UP] 0 : O ON ON ON
1 : B ON ON
2nd [UP] 0 : O ON ON ON ON
1 : B ON ON ON
[DOWN] 0 : O ON
1 : B
#53 Fan [UP] ON
[DOWN]

QUICK REFERENCE TO CONTROLS & DISPLAYAprilaire-8810-TouchScreen-Wi-Fi-Thermostat-fig-13

THERMOSTAT FEATURES

TROUBLESHOOTING

DISPLAY IS BLANK

TEMPERATURE SETTINGS DO NOT CHANGE

HEATING SYSTEM DOES NOT RESPOND (“HEATING” APPEARS ON SCREEN)

COOLING SYSTEM DOES NOT RESPOND (“COOLING” APPEARS ON SCREEN)

FAN DOES NOT TURN ON IN A CALL FOR HEAT

HEAT PUMP ISSUES COOL AIR IN HEAT MODE, OR WARM AIR IN COOL MODE

HEAT/COOL BOTH ON AT SAME TIME

HEATING EQUIPMENT IS RUNNING IN COOL MODE

“HEATING” IS NOT DISPLAYED

“COOLING” IS NOT DISPLAYED

SPECIFICATION

Environment
 

Temperature

Operating: 32° to 120°F (0° to 48 .9°C)

Shipping: -30° to 140°F (-34 .4° to 60°C)

Relative humidity Operating: 5% to 90% R .H . (non-condensing)
Electrical
Operating voltage 24 VAC (18 – 30 VAC)
 

Current

Maximum: 2 .5A (total), 1 .0A (single output)

Maximum surge current: 5A

Thermal
Outdoor temperature sensor Maximum distance: 300 feet
Room temperature measurement Display range: 32° to 99°F (0° to 40°C)
Outdoor temperature measurement Display range: -40° to 130°F (-40° to 55°C)
Heat: 40° to 90°F
Temperature setting (4° to 32°C)
range Cool: 50° to 99°F
(10° to 37°C)

CONTACTS

U.S. Patent Numbers 8,146,376, 8,596,078 and other patents pending.

© 2015 Aprilaire – A division of Research Products Corporation

REFERENCE

Download Manual:

Aprilaire 8810 TouchScreen Wi-Fi Thermostat Installation Instruction

other manuals:

Aprilaire 8810 TouchScreen Wi-Fi Thermostat Owner Manual

Aprilaire-logo

Aprilaire 8810 TouchScreen Wi-Fi Thermostat Installation Instruction

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)