SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction-FEA

SIEMENS RDD310/EH Flush-mount Room Thermostat Operating Instruction

SIEMENS-LOGO

SIEMENS RDD310/EH Flush-mount Room Thermostat

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction-PRO

INTRODUCTION

RDD310/EH and RDE410/EH – the room thermostats for use with electrical floor heating systems. The products feature a built-in room sensor to control the room temperature, and the user can connect a cable temperature sensor to limit the maximum floor temperature. The thermostat provides Comfort, Economy and Frost Protection mode. The RDE410/EH also features an Auto Timer with 8 programmable time switches. You can either rely on the factory settings or make adjustments that suit your individual needs.

Display

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (1)

 

Operation and settings

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (2)

Are your rooms too warm or too cold?

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (3)

  • Press + or – to increase or decrease the current room temperature setpoint in increments of 0.5 C for Comfort mode. 5 seconds after the last push, the room temperature setpoint is automatically saved. The display stops flashing and shows the room temperature currently measured.
  • The maximum setpoint setting range is 5…40 °C, unless limited by parameters P09 and P10.

Do you require continuous Comfort mode?

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (4)

  • Press the operating mode buttonSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (5) to switch to Comfort mode SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (6). In that case, the room temperature setpoint is always maintained at the Comfort level.
  • The RDE410/EH has a dedicated buttonSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (7) for the selection of the operating mode.

Do you want to set your thermostat to Frost Protection mode?

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (8)

  • Press the operating mode buttonSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (5) several times until the display shows theSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (9) icon to indicate that Frost Protection mode is selected.
  • The RDE410/EH has a dedicatedSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (9) button to set the system either to Frost Protection mode or to switch it on.
  • SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (9)In Frost Protection mode SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (9), the room temperature setpoint is maintained at 8 °C (factory setting), unless your HVAC installer made some other setting.
  • Changes made by the installer.

Do you want to change to Economy mode?

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (10)

  • When Economy mode is enabled (parameter P02), press the operating mode button to select Economy mode SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (11). In that case, the room temperature setpoint is always maintained at the Economy level. The preset room temperature setpoint in Economy mode is 16 􀃛C (parameter P11).
  • The RDE410/EH has a dedicatedSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (7) button for selection of the desired operating mode.

Do you want to change to Auto Timer mode? (RDE410/EH only)

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (12)

  • Press theSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (7) button to select Auto Timer modeSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (13) . In this mode, the thermostat switches automatically between Comfort and Economy mode according to the 8 programmed time switches.

Setting the time of day and the weekday (RDE410/EH only)

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (14)

  1. Keep the SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (16)button depressed until the time digits start to flash, then press + or – to set the time of day. If the current time format is the 24-hour format and you wish to change to the 12-hour format, keep + depressed to pass 23:59, or keep – depressed to pass 00:00. Vice versa to go back to the 24-hour format.
  2. Confirm the time of day by pressingSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (15). The weekday indicator starts to flash.
  3. Press + or – to set the current weekday.
  4. Confirm the current weekday by pressing SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (15).

Do you want to set the time switches? (RDE410/EH only)
To set the time switches, keepSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (18) the button depressed for 3 seconds to go to Auto Timer mode. This mode is indicated by “Ax” appearing on the display (x = Auto Timer 1…8) and the time xx:xx flashing.
For each time switch, proceed as follows:

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (17)

  1. Icons SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (13)and SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (6)are displayed. Press + or – to set the Comfort mode start time and confirm by pressing SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (15).
  2. IconsSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (13) and SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (11)are displayed. Press + or – to set the Comfort mode end time (or Economy mode start time) and confirm by pressing SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (15).
  3. Icon flashes. Press + or – to select or deselect each day and advance to the next day. Confirm setting for the current time switch by pressingSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (15) and advance to the next time switch.

The thermostat exits the time switch setting mode automatically after 20 seconds if no button is pressed. All changes made after the last press SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (15)of will not be saved!

Do you want to view the time switch settings? (RDE410/EH only)

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (18)

  • Press the SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (18)button to sequentially review all 8 programmable time switches.

Do you want to reload the default time switch settings? (RDE410/EH only)

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (19)

  • Set the thermostat to Frost Protection mode SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (9).
  • Press + and – simultaneously for 3 seconds. Release the buttons and, within 2 seconds, press twice SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (18)the button.SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (20)

Commissioning (by qualified HVAC installer)

  • To adapt the thermostat to your system and to optimize the control performance, a number of control parameters can be set.
  • This can also be made during operation without opening the thermostat.

Recalibrating the temperature sensor

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (21)

  • If the room temperature displayed by the thermostat does not accord with the temperature effectively measured, the temperature sensor can be recalibrated. Using parameter P05, the temperature can be adjusted by pressing + or – in increments of 0.5 °C. The maximum recalibration range is +/- 3 °C.

Economy mode

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (22)If you want to change the factory-set temperature setpoint (16 °C for heating), readjust parameter P11.
Caution: The setpoint for Economy mode can be set to “Off”. This means that the thermostat will be deactivated! This means that there will be no protective heating function, therefore risk of frost!

Electrical floor heating/cable temperature sensor (floor sensor)

  • SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (22)The factory setting for this function is “Off” and must be set to “On” if electrical floor heating is used. This function is activated via parameter P38.
  • The installer must select the approximate capacity of the heating system (in kW) via parameter P45 during commissioning.
  • The cable temperature sensor is connected to input X1, M and acquires the floor temperature. If the floor temperature exceeds the parameterized limit xx ºC (P38 = 1, P51 = xx ºC), the heating system is turned off until the floor temperature returns to a level below the parameterized limit. A typical application are rooms (dry floor).
  • If the application does not require floor temperature limitation but instead uses the external sensor for room temperature display and control, the parameters have to be set as follows: P38 = 1, P51 = Off. A typical application are bathrooms (wet floor) where a constant floor temperature is required
  • SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (22)It is not recommended to have only a built-in room sensor for floor heating since in that case there is a risk of overheating.

Energy saving tips without loss of comfort:

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (23)

  • Never allow room temperatures to exceed 21 °C
  • When absent, set the thermostat to Economy mode (or Frost Protection), even for short periods of time
  • Air out the rooms briefly, but with windows wide open

Control parameters

If you want to change the control parameters, proceed as follows:

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (24)

  1. Set the thermostat to Frost Protection mode.
  2. Press + and – simultaneously for at least 3 seconds. Release the buttons and, within 2 seconds, press – again for 7 seconds. The display will show “P02”.
  3. Select the required parameter by repeatedly pressing + or –.
  4. Press + and – simultaneously. The current value of the selected parameter starts to flash. Adjust it by pressing + or –.
  5. Press + and – simultaneously again to display the next parameter.
  6. If you wish to display and change additional parameters, repeat steps 3 through 5.
  7. Service or expert level: 10 seconds after the last display or setting, all changes are stored and the thermostat will leave the parameter setting mode.
    Expert level: Press + or – until “End” is displayed. Then, press + and – simultaneously to save the change and exit the parameter setting mode.
No. Thermostat’s parameter Factory setting Setting range
P02 Selection of operating mode via the operating mode buttonSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (7) 1 = Frost Protection – Comfort mode RDD310/EH:

1 = Comfort – Frost Protection

2 = Comfort – Economy – Frost Protection

RDE410/EH:

1 = Auto-Comfort – Frost Protection

2 = Auto – Comfort – Economy – Frost

Protection

P05 Temperature sensor calibration 0.0 °C -3…3 °C
P06 Standard temperature display 0 = Room

temperature

0 = Room temperature 1 = setpoint
P08 Comfort basic setpoint 20 °C 5…40 °C
P09 Min. setpoint limitation in Comfort mode (WminComf) 5 °C 5…40 °C
P10 Max. setpoint limitation in Comfort mode (WmaxComf) 35 °C 5…40 °C
P11 Heating setpoint in Economy mode 16 °C Off, 5…18 °C
P14 Button lock (press the operating mode button SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Operating-Instruction- (7) for 3 seconds to lock or unlock) 0 = Disabled 0 = Disabled 1 = Auto-lock

2 = Manual lock

P30 Switching differential in heating mode 1 K 0.5…6 K
P38 External input 0 0 = No input

1 = External sensor input

P45 Heating system load in kW 2.8 kW 0…3.6 kW
P51 Floor heating temperature limit Off   Off, 10…60 °C
P65 Setpoint of heating in Frost Protection mode     (WheatStb) 8 °C Off, 5…18 °C
P69 Temporary setpoint in Comfort mode Off Off = Disabled On = Enabled
P71 Reloading factory settings Set value to “On” and confirm by pressing + and Off Off = Idle On = Reset
d02 Status X1 Diagnostics 0…xx °C = Measured temperature
d07 Software version information No adjustment

(All temperature settings can be made in increments of 0.5 °C with the exception of P51, which is at 1 °C)
Please write down all changes you make!

REFERENCE:

DOWNLOAD MANUALS:

SIEMENS RDD310EH Flush-mount room thermostat Operating Instruction

OTHER  MANUALS:

SIEMENS RDD310/EH Flush-mount room thermostat Product Specifications Guide

SIEMENS-LOGO

SIEMENS RDD310/EH Flush-mount Room Thermostat Operating Instruction

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post’s permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post’s URL again. (Find out more about Webmentions.)