Viconics VT7200 Room Temperature Control Thermostat
Smart energy management has never been easier than with the VT7200. Designed for new construction or retrofit projects, the controllers dramatically decrease total costs by reducing installation time, configuration, and commissioning time. The VT7200 provides the advanced features and monitoring functions required by modern building automation systems without the use of software and commissioning tools.
SPECIFICATIONS
Parameter | Specification |
---|---|
Thermostat Power Requirements | 19 to 30 Vac; 50 or 60 Hz; 2 VA Class 2 |
Operating Conditions | 0 to 50 °C (32 to 122 °F); 0 to 95% RH non-condensing |
Storage Conditions | -30 to 50 °C (-22 to 122 °F); 0 to 95% RH non-condensing |
Temperature Sensor | Local 10k NTC thermistor |
Resolution | ± 0.1 °C (± 0.2 °F) |
Control Accuracy Temp. | ±0.5 °C (±0.9 °F) @ 21 °C (70 °F) typical, calibrated |
Occupied and Unoccupied Setpoint Range Cooling | 12 to 38 °C (54 to 100 °F) |
Occupied and Unoccupied Setpoint Range Heating | 4.5 to 32 °C (40 to 90 °F) |
Room and Outdoor Air Temperature Display | -40 to 50 °C (-40 to 122 °F) |
Proportional Band for Room Temperature Range Control | Cooling & Heating: 1.8 °C (3.2 °F) |
Binary Inputs | Dry contact across terminal BI1, BI2 & UI3 to Scom |
Outputs Rating | Triac output: 30 Vac, 1 A max., 3 A in-rush; Analog: 0 to 10 Vdc into 2k Ω resistance min. |
Economizer Analog Output Rating | 0 to 10 Vdc into 2k Ω resistance min. |
Economizer Analog Output Accuracy | ±3% typical |
Advanced occupancy functions
Advanced occupancy functions through the network or smart local occupancy sensing
Minimize parameter tampering
Password-protected configuration utility
Auxiliary output
Can be used for lighting or reheating
Lockable keypad
Tamper-resistant, no need for thermostat guards
Pre-configured sequences
Pre-configured sequences of operation…one model meets more applications and reduces project delivery cost
Configurable inputs
Three configurable inputs for added functionality.
APPLICATIONS
- Variable Volume and Temperature (VVT)
- Perimeter radiation
- Duct reheat
- Induction unit
- Radiant floor control
Parameter | Specification |
---|---|
Thermostat Power Requirements | 19 to 30 Vac; 50 or 60 Hz; 2 VA Class 2 |
Operating Conditions | 0 to 50 °C (32 to 122 °F); 0 to 95% RH non-condensing |
Storage Conditions | -30 to 50 °C (-22 to 122 °F); 0 to 95% RH non-condensing |
Temperature Sensor | Local 10k NTC thermistor |
Resolution | ± 0.1 °C (± 0.2 °F) |
Control Accuracy (Temperature) | ± 0.5 °C (± 0.9 °F ) @ 21 °C (70 °F) typical, calibrated |
Occupied Setpoint Range (Cooling) | 12 to 38 °C (54 to 100 °F) |
Occupied Setpoint Range (Heating) | 4.5 to 32 °C (40 to 90 °F) |
Room and Outdoor Air Temperature Display | -40 to 50 °C (-40 to 122 °F) |
Proportional Band for Room Temperature | Cooling & Heating: 1.8 °C (3.2 °F ) |
Binary Inputs | Dry contact across terminal BI1, BI2 & UI3 to Scom |
Outputs Rating | Triac output: 30 Vac, 1 A max., 3 A in-rush; Analog: 0 to 10 Vdc into 2k Ω resistance min. |
Economizer Analog Output Rating | 0 to 10 Vdc into 2k Ω resistance min. |
Economizer Analog Output Accuracy | ±3% typical |
Wire Gauge | 18 gauge maximum, 22 gauge recommended |
Dimensions | 4.94” x 3.38” x 1.13” |
Approximate Shipping Weight | 0.75 lb (0.34 kg) |
WARRANTY | Limited Warranty: 2 years |
AGENCY APPROVALS
- UL: 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN, XAPX (US) and XAPX7 (Canada)
- FCC: Compliant to CFR 47, Part 15, Subpart B, Class A (US)
- Industry Canada: ICES-003 (Canada)
DIMENSIONAL DRAWING
ORDERING INFORMATION
PART NUMBER | DESCRIPTION | COMM. |
---|---|---|
VT7200C5031 | Zone Controller: Net Ready, Floating Outputs, VAV PD | Standalone |
VT7200C5031B | Zone Controller: BACnet, Floating Outputs, VAV PD | BACnet MS/TP |
VT7200C5531B | PIR Zone Controller: 2 On/Off or Floating Outputs | BACnet MS/TP |
VT7200C5531E | PIR Zone Controller: 2 On/Off or Floating Outputs | LonWorks |
VT7200C5531P | PIR Zone Controller: 2 On/Off or Floating Outputs | Zigbee Pro |
VT7200C5531W* | PIR Zone Controller: 2 On/Off or Floating Outputs | Zigbee |
VT7200F5031 | Zone Controller: Net Ready, 2 Analog 0-10V Outputs, VAV PD | Standalone |
VT7200F5031B | Zone Controller: BACnet, 2 Analog 0-10V Outputs, VAV PD | BACnet MS/TP |
VT7200F5531B | PIR Zone Controller: 2 Analog 0-10V Outputs | BACnet MS/TP |
VT7200F5531E | PIR Zone Controller: 2 Analog 0-10V Outputs | LonWorks |
VT7200F5531P | PIR Zone Controller: 2 Analog 0-10V Outputs | Zigbee Pro |
*Wireless ‘W’ Zigbee models for replacement or existing projects only. See PN: VCM7000V5000W.
Note: All models with PIR motion sensors and most models with communication modules must be purchased in two or three different parts. For example, VT7200F5531E should be ordered as VT7200F5031 + COV-PIR-ZN-5031 + VCM7300V5000E.
Reference Link
Download manual:
Viconics VT7200 Room Temperature Control Thermostat Data Sheet
Other manual
Viconics VT7200 Room Temperature Control Thermostat Installation Guide
Viconics VT7200 Room Temperature Control Thermostat Data Sheet
Leave a Reply