2GIG logo

2gig CT100 Programmable Thermostat 

2gig-CT100-Programmable-Thermostat-product

Installation

2gig-CT100-Programmable-Thermostat-fig.1

Caution

Caution To avoid electrical shock and to prevent damage to the furnace, air conditioner, and thermostat, disconnect the power supply before beginning work. This can be done at the circuit breaker.

TOOLS
You will need a small Phillips screwdriver and a drill with 3/16-in. (4.8mm) bit for wall mounts.

LOCATION

Replacement installations – mount the CT100 in place of the old thermostat.
A new location will require moving your wiring.
For new installations and relocating the CT100 – follow the guidelines listed below:2gig-CT100-Programmable-Thermostat-fig.2

REMOVE OLD UNIT

Switch OFF electricity to the HEATING and COOLING systems.
Then follow these steps:

Remove the cover from old thermostat. Most are snap-on types and simply pull off. Some have locking screws on the side or front. These must be loosened. DO NOT remove wires. Note the letters printed near the terminals. Attach labels (enclosed) to each wire for identification.

Caution
Read the instructions carefully before removing any wiring from the existing thermostat. Wires must be labeled before they are removed. THERE IS NO STANDARD COLOR CODE. When removing wires from their terminals, ignore the color of the wires and LABEL THEM by the lettered terminal where they were screwed.2gig-CT100-Programmable-Thermostat-fig.3

What wires do you have?

Make sure your wires are labeled. This may require you to find the ‘other end’ connection for each wire on your heating or air conditioning equipment and read the label there. Refer to the Wire Reference page at end of the install section for better understanding of wire labels from different HVAC system makers.
IMPORTANT: The CT100 runs on 4 AA alkaline batteries and/or the C wire if available. If you do not have a C wire you can run a new wire from the HVAC or use a standard 12-24V [AC or DC] wall transformer.
IMPORTANT: If you have both RH and RC you need to remove the jumper wire between these 2 terminals.2gig-CT100-Programmable-Thermostat-fig.4
Prepare Wires
Please follow these guidelines for safe and secure wire connections:2gig-CT100-Programmable-Thermostat-fig.5

Find the step-by-step diagram for your system

2gig-CT100-Programmable-Thermostat-fig.6

connect Your Wires

Mount the CT100 to Wall

2gig-CT100-Programmable-Thermostat-fig.8 2gig-CT100-Programmable-Thermostat-fig.9

  1. Hold the CT100 against the wall, with the wires coming over the top; above the terminal block. The CT100 will cover the hole in the wall.
  2. Position CT100 for best appearance.
  3. Attach the CT100 to the wall with the screws provided.
  4. If you are mounting the CT100 to sheetrock or if you are using the old mounting holes, use the plastic anchors provided.
  5. Mark irst and drill a 3/16-in.(4.8mm) hole for the insert at each screw location then mounts the unit.

HVAC Selection

2gig-CT100-Programmable-Thermostat-fig.10

Install 4 AA Batteries

2gig-CT100-Programmable-Thermostat-fig.11

HVAC Setup on Screen

2gig-CT100-Programmable-Thermostat-fig.12

IMPORTANT: Make sure the CT100 is powered up and the mode is set to OFF. Remember that the two HVAC selection switches must be set irst [pg 8].

If you have a Normal HVAC system…

If you have a HEAT PUMP HVAC system…

Caution Do not change
the HVAC setup or HVAC selection switches if the thermostat is included to Z-Wave network. The HVAC system must be changed, irst EXCLUDE the thermostat from the network, change the HVAC setup, and INCLUDE the thermostat to the network.

Test Installation

2gig-CT100-Programmable-Thermostat-fig.13

Follow these procedures to verify you have correctly installed the CT100.
TO CHECK FAN (If you connected the G wire):

TO CHECK HEAT

Congratulations, you have successfully installed your unit. Please proceed to the OPERATING Guide to initialize the CT100.
IMPORTANT: If you have labeled and connected your wires and followed the correct HVAC setup, and your system still does not operate, contact technical support.2gig-CT100-Programmable-Thermostat-fig.14
STATEMENT OF USE: This thermostat can be used with 4AA batteries, 24VAC (C wire), 24VAC adapter, heating and cooling systems and also millivolt heating. It cannot be used with line voltage systems. This thermostat is digital and your desired heat or cool temperatures can easily be set on the large touchscreen with the +/- buttons. A minimum of 4 minute off time protects the compressor from damage.
This thermostat runs on 4AA batteries. The CT100 can be externally powered with a power source rated from 12V to 24V, AC or DC, at 100ma or greater. If used, connect to the C and RH terminals (no polarity). The 24VAC “C” wire is the other side of the 24VAC heating transformer and can be found where the other thermostat wires connect at the wall or at the furnace. Do not use the common or ground side of the line voltage.

Step-by-step wiring diagrams

2 Wire Heat GAS MILLIVOLT or 24VAC system2gig-CT100-Programmable-Thermostat-fig.15

3 Wire Heat2gig-CT100-Programmable-Thermostat-fig.16

4 Wire Heat/Cool2gig-CT100-Programmable-Thermostat-fig.17

5 Wire HEAT/Cool2gig-CT100-Programmable-Thermostat-fig.18

Multi-stage Heat and Multi-stage Cool2gig-CT100-Programmable-Thermostat-fig.19
The CT100 can handle up to 2 stages of HEAT and 2 stages of COOL.

Heat Pump (heat/cool) without Auxiliary Heat2gig-CT100-Programmable-Thermostat-fig.20

Multi-stage Heat Pump with Multi-stage Aux Heat2gig-CT100-Programmable-Thermostat-fig.21
The CT100 can handle up to 2 stages of Pump compression and 2 stages of AUX heat.

Accessory Wiring

3 Wire Zoned Hot Water Heat 2gig-CT100-Programmable-Thermostat-fig.22
For a 3-wire solenoid or motor, valves connect the wires shown to the correct terminals on the CT100. If you have different letters than shown, go to page 18 Wire Reference Table.

Trane Products [American Standard]

Zoned Hot Water

2 wire
Your Wires: Thermostat Terminal

3 Wire
Motor-Driven Valves

3 Wire
Solenoid Valves

APPENDIX 1 Multi-staged HVAC theory of operation for the CT100

Staging for 2-stage normal or heat pump Cool

Staging for 2-stage normal Heat

Staging for a 2 stage Heat Pump with no auxiliary heat

Reference

Download Manual:

2gig CT100 Programmable Thermostat Installational Guide

2GIG logo

2gig CT100 Programmable Thermostat Installational Guide

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)