SIEMENS-RDB160BN-Room-Thermostat-featured

SIEMENS RDB160BN Room Thermostat Product Specifications Guide

SIEMENS-LOGO

SIEMENS RDB160BN Room Thermostat 

SIEMENS-RDB160BN-Room-Thermostat

For fan coil and universal applications

  • For 2-pipe, 2-pipe with electric heater, and 4-pipe applications
  • BACnet MS/TP bus communication
  • Built-in temperature sensor
  • Outputs for On/Off, PWM, 3-position or DC 0…10 V control
  • Outputs for 3-speed, 2-speed, 1-speed or DC 0…10 V fan
  • Three multifunctional inputs for keycard contact, external sensor, etc.
  • Operating modes: Comfort, Standby (Economy) and Off
  • Automatic or manual fan speed control
  • Automatic heating/cooling changeover
  • On/Off button
  • Control based on room or return air temperature
  • Minimum and maximum limitation of room temperature setpoint
  • Operating voltage: AC 230 V

Use

The RDB160BN BACnet MS/TP room thermostats are used for the following types of system:

  • Fan coils with On/Off, modulating or DC control outputs (electric heater only with On/Off output):
    2-pipe system
    2-pipe system with electric heater
    4-pipe system
  • Chilled/heated ceilings (or radiators) with On/Off, modulating or DC control outputs (electric heater only with On/Off output):
    Chilled/heated ceiling
    Chilled/heated ceiling with electric heater
    Chilled ceiling with radiator

The RDB160BN controls:

  • One 1-speed, 2-speed, 3-speed or DC fan
  • Up to two On/Off, PWM, DC 0…10 V or one 3-position valve actuators

The RDB160BN is used in systems with:

  • Heating or cooling mode
  • Automatic heating/cooling changeover
  • Heating and cooling mode (e.g. 4-pipe system)

The RDB160BN BACnet MS/TP room thermostats are delivered with a fixed set of applications. The relevant application is selected and activated during commissioning using the local HMI.

Functions

Control applications

  • Fan coil units, e.g. 2-pipe fan coils
  • Universal applications, e.g. chilled ceiling

General functions

  • Room temperature control with built-in temperature sensor, external room tempera-ture or return air temperature sensor
  • Changeover between heating and cooling mode (automatic with local sensor or BAC-net object)
  • Backlight LCD
  • Supply air limitation
  • Automatic valve exercise
  • Mold protection

Setpoints and display

  • Minimum and maximum limitation of room temperature setpoint
  • Display of temperature or setpoint
  • Button lock

Fan

  • 1-speed, 2-speed, 3-speed or DC 0…10 V fan control (automatically or manually)

Inputs

  • One analog input for:
    External room temperature or return air temperature sensor
    Supply air temperature limitation sensor
  • One universal input for:
    Changeover digital
    Changeover analog
    Window contact
  • One digital input
    Presence input
    Window contact

BACnet MS/TP communication

Device address
The BACnet MS/TP MAC address can be set from 0 to 127.
Factory setting is from 0 to 99.

Baud rate
The baud rate is selectable. Four options are available for the RDB160BN: 9600, 19200, 38400 and 76800 (default setting) bps.

Applications

The RDB160BN BACnet MS/TP room thermostats support the following applications. The applications can be configured using the local parameter setting or via the system.

SIEMENS-RDB160BN-Room-Thermostat-fig-1

YHC Heating/cooling valve actuator M1 1-speed, 2-speed or 3-speed fan
YH Heating valve actuator B1 Return air temperature sensor or external room temperature sensor (optional)
YC Cooling valve actuator B2 Changeover sensor (optional)
YE Electric heater

Possible output combinations

2-pipe 2-pipe with electric heater 4-pipe
Fan 1/2/3-speed DC 0…10 V 1/2/3-speed DC 0…10 V 1/2/3-speed DC 0…10 V
Output #1 On/Off, PWM, 3-position, DC 0…10 V On/Off, PWM, DC 0…10 V On/Off, PWM,

DC 0…10 V

On/Off

, PWM

DC 0…10 V
Output #2 n.a. On/Off On/Off, PWM

Mechanical design

The RDB160BN BACnet MS/TP room thermostats consist of two parts:

  • Mounting plate with screw terminals
  • Plastic housing with electronics, operating elements and room temperature sensor

Operation
The display is operated using the buttons on the controller.SIEMENS-RDB160BN-Room-Thermostat-fig-2

  1. On/Off button
  2. Up/Down buttons to adjust setpoints and parameters
  3. Fan mode

Display
The display has the following indications:SIEMENS-RDB160BN-Room-Thermostat-fig-3

  1. AUTO/MANˈ: Automatic or manual mode indication for the fan
  2. Current fan speed (Low, Medium, High)
  3. Up/Down buttons to adjust setpoints and parameters
  4. Occupancy indication
  5. Current room temperature or setpoint in °C to one decimal point
  6. Open window
  7. COOL/HEATˈ: Shows the current control mode of the thermostat.
  8. STANDBYˈ: Economy mode indication.
    SERVICEˈ: Setting parameters
  9. OFFˈ: OFF mode (only the temperature is shown)
  10. Indoor / outdoor temperature
  11. Setpoint
  12. Fan status

Type summary

Type Order number Designation
RDB160BN S55770-T426 RDB160BN BACnet Room Temp Controller

Equipment combinations

SIEMENS-RDB160BN-Room-Thermostat-fig-4

On/Off actuators

SIEMENS-RDB160BN-Room-Thermostat-fig-5

On/Off and PWM actuators1)

SIEMENS-RDB160BN-Room-Thermostat-fig-6

3-position actuatorsSIEMENS-RDB160BN-Room-Thermostat-fig-7

DC 0…10 V actuatorsSIEMENS-RDB160BN-Room-Thermostat-fig-8SIEMENS-RDB160BN-Room-Thermostat-fig-9

The documents can be downloaded at http://siemens.com/bt/download
With PWM control, it is not possible to ensure exact parallel running of two or more thermal actuators. If several fan coil systems are controlled by the same room thermostat, use motorized actuators with On/Off or 3-position control.

Product documentation

The following product documentation is available

Topic Document ID:
Mounting instructions A6V11904646
Basic documentation A6V11917618
CE declaration A5W00090598A
Environmental declaration A5W00088543A

The mounting instructions are included with the product.

Languages
The mounting instructions are available in English.
Related documents such as environmental declarations, CE declarations, etc., can be downloaded at the following Internet address: http://siemens.com/bt/download

Notes

Mounting and installation

CAUTION Noncompliance with the following safety regulations. Risk of injury to persons and damage to property. Compliance with the following regulations is required.

MountingSIEMENS-RDB160BN-Room-Thermostat-fig-10

  • The devices are suitable for wall mounting.
  • Recommended height: 1.5 m above the floor.
  • Do not mount the devices in recesses, shelves, behind curtains or doors, or above or near heat sources.
  • Avoid direct solar radiation and drafts.
  • Seal the conduit box or the installation tube if any, as air currents can affect sensor readings.
  • Adhere to allowed ambient conditions.

Wiring

Comply with local regulations to wire, protect and earth the thermostat.

WARNING
Supply lines to external consumers (DO1, DO2, DO3, Yx or Yxx) have no internal line protection! Short-circuits, risk of fire and injury.

  • Adapt the line diameters as per local regulations to the rated value of the installed over current protection device.
  • The AC 230 V mains supply line must have an external circuit breaker with a rated current of no more than 10 A.
  • Properly size the cables to the thermostat, fan and valve actuators for AC 230 V mains voltage.
  • Use only valve actuators rated for AC 230 V.
  • Disconnect the thermostat from the power supply before removing it from the mounting plate.

Commissioning

Applications and settings
The BACnet MS/TP room thermostats are delivered with a fixed set of applications and related parameters. The factory settings can be changed by using the display and buttons on the controller. The INCREASE and DECREASE buttons change the parameter values: the changes are confirmed with the On/Off button.

Wizard setting
The first time the RDB160BN is powered on, a wizard is available to easily set the device.

Parameter Name Range Factory setting
P01 Application 2 = 2-pipe system 3 = 4-pipe system

4 = 2-pipe system with electric heater

3 = 4-pipe system
P77 Fan output type 0 = 1-, 2- or 3-speed fan 1 = DC fan 0 = 1-, 2- or 3-speed fan
P78 Valve 1 output type 0 = DC valve

1 = PWM (Thermal valve) 2 = On/Off (Thermostat function)

3 = 3-position valve

0 = DC valve
P79 Valve 2 type *) 0 = DC valve

1 = PWM (Thermal valve) 2 = On/Off (Thermostat function)

3 = 3-position valve

0 = DC valve
P58 BACnet MS/TP MAC

address

Must be unique within an MS/TP network 0-99, as per device label
P59 BACnet MS/TP, device id, the

4 lowest digits.

Lowest 4 digits of device ID, as per device label
P60 BACnet MS/TP, device id, the

3 highest digits

Highest 3 digits of device ID, as per device label
P62 Baud rate 0 = 9600 bps

1 = 19200 bps

2 = 38400 bps

3 = 76800 bps

3 = 76800 bps

Locked to On/Off when thermostat is set to 2-pipe with electric heater application.

Disposal

The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage.

  • Dispose of the device through channels provided for this purpose.
  • Comply with all local and currently applicable laws and regulations.

Warranty

Technical data on specific applications are valid only together with Siemens products listed under “Equipment combinations”. Siemens rejects any and all warranties in the event that third-party products are used.

Technical data

General
Operating voltage AC 230 V ±10 %
Frequency 50/60 Hz
Power consumption 3 W, class II construction
Built-in temperature sensor NTC type, measuring range 0…50 °C
Terminal blocks Lift type for max. cable area 2.1 mm2
No internal fuse!

External preliminary protection with max. C 10 circuit breaker required in all cases.

Ambient conditions, environmental conditions
Ambient temperature 0…50 °C
Storage temperature -20…+70 °C
Ambient humidity Max. 90% r.h.
Safety class and degree of protection
Protection class IP20
Pollution degree 2
Overvoltage category 3
Communication
Communication BACnet MS/TP
Communication speed 9600, 19200, 38400 or 76800 bps
Inputs
External sensor, AI PT1000-sensor
Universal input, UI Change-over, potential-free contact or PT1000-sensor
Presence/window contact, D1 Potential free contact
Outputs
Fan control, DO1, DO2, DO3 3 outputs for speed I, II and III, AC 230 V
DOx rating min., max. inductive 5 mA…2 A
No internal fuse!

Always use external preliminary protection with max. C 10 A circuit breaker in the supply line.

Outputs
Do NOT connect fans in parallel!

Connect one fan directly, for additional fans, one relay for each speed.

DC 0…10 V; AO1, AO2 SELV DC 0…10 V, max. ±5 mA
Control outputs Solid state (triacs)
DO4-N, DO5-N AC 230 V
DOx power limitation 8…300 mA

3 A fast microfuse, cannot be exchanged

Operational data
Switching differential, adjustable
Heating/cooling mode (P10) 1 K (0.5…50 K)
Setpoint setting and setpoint range
Comfort mode (P64) 22 °C (5…50 °C)
Economy mode (P6-7) 15 °C/30 C (OFF, 5…40 °C)
Input AI default value (P13) 0 (no function)
Input U1 default value (P14) 0 (no function)
Input D1 default setting (P36) 0, Normally Open
Built-in room temperature sensor NTC 10 KOhm
Measuring range 0…50 °C
Accuracy ±1.5 °C at 15…30 °C
Temperature calibration range (P33) ±10 K
Standards and directives
EU conformity (CE) A5W00090598A *)
Electronic control type 2.B (micro-disconnection on operation)
RCM conformity A5W00090592A *)
Safety class II as per EN 60730
Pollution class Normal
Degree of protection of housing IP20 as per EN 60529
Environmental compatibility The product environmental declaration A5W00088543A*) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal)
General
Connection terminals Solid wires or stranded wires with wire end sleeves 1x 0.4…2.5 mm2 or 2x

0.4…1.5 mm2

Minimal wiring cross section on terminals Min. 1.5 mm2
Housing front color White RAL 9010
Weight without packaging 0.18 kg

Note: The documents can be downloaded at http://siemens.com/bt/download

Connection terminals

SIEMENS-RDB160BN-Room-Thermostat-fig-11

10, 12, 13 L, N Operating voltage AC 230 V 40 DI Digital input
41 M Ground
20 DO1 Control output fan speed I AC 230 V 42 AI Analog input
21 DO2 Control output fan speed II AC 230 V 43 UI Universal input
22 DO3 Control output fan speed III AC 230 V 44 M Ground for SELV
31 DO4 Control outputs ‘Valve’ AC 230 V 51 AO1 Control outputs DC 0…10 V
32 C Common 50 M Ground
33 DO5 Control outputs Valve’ AC 230 V 52 AO2 Control outputs DC 0…10 V
53 P1 A BACnet MS/TP
54 P1 B BACnet MS/TP

Connection diagrams

SIEMENS-RDB160BN-Room-Thermostat-fig-12 SIEMENS-RDB160BN-Room-Thermostat-fig-13

N1 Room thermostat RDB160BN S1, S3 Switch (keycard, window contact, presence detector)
M1 Fan (1-/ 2-/ 3- speed or DC 0…10 V) B1, B2 Temperature sensor (return air temperature, external room temperature, changeover sensor, etc.)
V1, V2 Valve actuator, 2-position, 3-postion or DC 0…10 V P1 A BACnet MS/TP –
E1 Electric heater P1 B BACnet MS/TP +

SIEMENS-RDB160BN-Room-Thermostat-fig-14 SIEMENS-RDB160BN-Room-Thermostat-fig-15

N1 Room thermostat RDB160BN S1, S3 Switch (keycard, window contact, presence detector)
M1 Fan (1-/ 2-/ 3- speed or DC 0…10 V) B1, B2 Temperature sensor (return air temperature, external room temperature, changeover sensor, etc.)
V1, V2 Valve actuator, 2-position, 3-postion or DC 0…10 V P1 A BACnet MS/TP –
E1 Electric heater P1 B BACnet MS/TP +

DimensionsSIEMENS-RDB160BN-Room-Thermostat-fig-16

Issued by
Siemens Switzerland Ltd
Smart Infrastructure Global Headquarters Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies
Document ID A6V11913047_en–_c
Edition 2021-02-26

© Siemens Switzerland Ltd, 2020
Technical specifications and availability are subject to change without notice.

REFERENCE:

DOWNLOAD MANUALS:

SIEMENS RDB160BN Room Thermostat Product Specifications Guide

SIEMENS-LOGO

SIEMENS RDB160BN Room Thermostat Product Specifications Guide

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post’s permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post’s URL again. (Find out more about Webmentions.)