Frico TD10 Electronic Thermostat
Installation
Display
- Operating mode menu
- Heater indication
- Cooler indication
- If lit-up (5) displays the measured temperature
- Measured temperature or set temperature
- Temperature unit
- Title for installation
- Parameters (J0,CLr…
MODES DESCRIPTION
- Electronic thermostat with LCD display for electrical heating systems.
- Savings reduction by external clock (Pilot wire).
- Three Functioning modes: Comfort, reduction or Clock mode.
- Possibility to regulate either the floor or room temperature, or combined (in this case, the floor sensor is used as temperature limiter)
- 10A relay.
- Use OK key to change the mode in the Operating mode menu
COMFORT operating mode:
Force comfort temperature operation indefinitely. By pressing +/- keys the comfort temperature starts to blink and can be adjusted. The measured temperature reappears after a few seconds.
OFF mode:
Use this mode if your Heating installation needs to be turned OFF. The display is blank. (Careful in this mode your installation can freeze) Parameters are saved.
SAVINGS REDUCTION mode
Activates Setback operation.. By pressing +/- keys the temperature starts to blink and can be adjusted. The measured temperature reappears after a few seconds.
SAVINGS REDUCTION mode with external clock:
The Thermostat will follow the external PILOT WIRE signal.
Blinking indicates a comfort signal.
Blinking indicates a setback signal
Press the OK key during 5 seconds, Then use + or – keys to select the installation parameter to be adjusted. Press OK to toggle the parameter setting or edit the value. If the value starts to blink you can use + / – keys to adjust this value. Press + & – keys at the same time to reset this value to the factory default value. Once you have adjusted the value press OK to validate this parameter value. When you have finished, use + / – keys to go to ‘End’ display and then press OK key to exit installation parameter menu
- J0: °C / °F temperature display selection
- J1 “Hot” / “Cold” regulation mode. Select Hot for a Heater system, select cold for a Cooling system
- Cy Proportional Integral regulation time cycle value in minutes (default: 15 minutes cycle)
- bp Proportional Integral regulation band amplitude value in degrees °C/°F (default: 2.0 °C/3.6 °F)
- J4 “NC” or “NO” Normally closed or normally open actuators selection.
- J5 Select “PNP” to perform an 1 minute exercise everyday (if installation inactive during a day)
- J6 Air or Floor temperature regulation selection. (if no Floor sensor, regulation will use Air sensor)
- J7 “rEG” (Proportional Integral) or “HYs” (0.3K Hysteresis) regulation type selection
- Cp compensation value in °C/°F (default: 2.0 °C/3.6 °F) this parameter must be adjusted by a professional.
- Ao Air sensor offset adjustment (default: no offset). Display measured Air sensor value
- Fo Floor sensor offset adjustment (default: no offset).
- Display measured Floor sensor value
- FL Floor temperature LOW limitation (default: 5 °C/41 °F), effective only if floor sensor present
- FH Floor temperature HIGH limitation (default: 28 °C/82 °F), effective only if floor sensor present
- CLr Press OK key during 5s to reset all the WFHT LCD parameters to factory defaults
- End Press OK key to exit installation parameter menu and return to normal operation