Braeburn-1100-Non-Programmable-Thermostats-User-Manual-FEATURED

Braeburn 1100 Non-Programmable Thermostats User Manual

Braeburn-logo

Braeburn 1100 Non-Programmable Thermostats

Braeburn-1100-Non-Programmable-Thermostats-User-Manual-PRODUCT

READ ALL INSTRUCTIONS BEFORE PROCEEDING

WARNING!
Important Safety Information

  • Always turn off power to the air conditioning or heating system prior to installing, removing, cleaning or servicing the thermostat.
  • Read this manual thoroughly prior to installing, programming or operating this thermostat.
  • This thermostat is designed for use with a 24 Volt-AC low voltage multi-stage heat / cool system.
  • Do not use this thermostat on systems with voltages higher than 30 Volt-AC.
  • This thermostat requires 24 Volt AC power for normal operation and control of the heating or cooling system.
  • In the event of an AC power outage, the first and second stage temperature differentials and the setpoint will return to their default system values. The user can change the default settings once power is restored.
  • Wiring must conform to all building codes and ordinances as required by local and national code authorities having jurisdiction.
  • Do not short (or jumper) across terminals on the gas valve or at the heating or cooling system control board to test the thermostat installation. This could damage the thermostat and void the warranty.
  • do not select the COOL mode of operation if the outside temperature is below 50˚ F (10˚ C). This could possibly damage the controlled cooling system and may cause personal injury.
  • This thermostat should only be used as described in this manual. Any other use is not recommended and will void the warranty.

SPECIFICATIONS

  • Electrical Rating: 24 Volt AC (18-30 Volt AC)
    1 amp maximum load per terminal
    3 amp total maximum load (all terminals)
  • Control Range: 45° – 90° F (7° – 32° C)
  • Accuracy: +/- 1° F (+/- .5° C)
  • AC Power: 18-30 Volt AC
  • Compatibility: Multi-stage heat/cooling systems with up to two stages of heating and one stage of cooling.
  •  Terminations: R, O, B, C, Y, W1, G, W2

INSTALLATION

Replacing Existing Thermostat

  1. Always turn off power to the air conditioning or heating system prior to removing the existing thermostat.
  2. Remove the cover of your old thermostat and locate the wire terminals. Do not remove wires from terminals yet.
  3. Using small pieces of masking tape label wires prior to removal from terminals. Use the chart below to determine the new terminal designations for your new thermostat.

Old Terminal from New Terminal for Existing Thermostat New Thermostat Terminal Description

R, V-VR or VR-R R 24 VAC
O O Reversing Valve (Cooling)
B B Reversing Valve (Heating)
C C 24 VAC common
Y, Y1 or M Y Cooling
W, E or W1 W1 1st Stage Heating
G or F G Fan Control
W1, W2 or W-U W2 2nd Stage Heating

After labeling and removing all wires from terminals, unscrew the existing thermostat sub-base from the wall. Make sure to secure wires to prevent them from slipping back into the hole in the wall.

NOTE: This thermostat is for use on low voltage 24 Volt AC multi-stage systems with up to two stages of heating and one stage of cooling and requires a transformer common wire for proper installation. This thermostat is not for use on single-stage heating or cooling systems

Installing Your New Thermostat

Installing Your New Thermostat cont.
NOTE: If you are installing this thermostat in a new installation be sure to locate the thermostat 4 to 5 feet above the floor in accordance with applicable building codes. Make sure to install the thermostat in a location that provides good airflow characteristics and avoid areas behind doors, near corners, air vents, direct sunlight, or near any heat-generating device. Installation in any of these areas could impact thermostat performance.

  1. Always turn off power to the air conditioning or heating system prior to installing your new thermostat.
  2. Place the system switch on the front of the thermostat to the OFF position.
  3.  Place the fan control switch on the front of the thermostat to the AUTO position.
  4. Remove the front of the thermostat body from the sub-base by pressing the release latch on the bottom of the front body.
  5. Place the thermostat sub-base against the wall in the desired thermostat location.
  6. Guide thermostat wires through the center hole in the sub-base. Continue to hold the sub-base against the wall.
  7. Mark placement of mounting holes as appropriate and drill using a 3/16″ drill bit.
  8. Gently tap supplied plastic anchors into the holes in the wall.
  9. Place the thermostat sub-base against the wall in the desired location making sure the mounting holes are aligned as appropriate and the thermostat wires are properly inserted through an opening in the middle of sub-base
  10. Fasten the sub-base to the wall using supplied screws.
  11. Connect wires to quick wiring terminal block as appropriate using the new terminal designations. Refer to the Wiring Diagram section of this manual if required for assistance.
  12.  Make sure all of the wire connections are secure and are not touching any other terminal to prevent electrical shorts and potential damage to the thermostat.
  13. Turn the front thermostat body over exposing the rear view of the circuit board.
  14. Locate the internal °F / °C switch on the circuit board.
  15. Using your fingers, gently flip the switch toward the preferred temperature °F / °C scale.
  16.  Locate the internal fan option switch, HG (Gas) / HE (Elec) on the circuit board. This switch controls the heating system fan delay. Select gas for gas or oil-fired systems. This will allow the furnace to run for a few seconds before initiating the fan. Select electric for systems with electric furnace elements that require the fan to come on immediately.
  17. Using your fingers, gently flip the switch towards the HG (gas) or HE (Elec) selection which indicates the low voltage heating system the thermostat will control.
  18. Attach the front body of the thermostat to the sub-base of the thermostat being careful to align the terminal pins on the front body with the terminal block on the sub-base.
  19.  Restore system power so you can test installation.

TESTING YOUR NEW THERMOSTAT

  • Do not short (or jumper) across terminals on the gas valve or at the heating or cooling system control board to test the thermostat installation. This could damage the thermostat and void the warranty.
  •  Do not select the COOL mode of operation if the outside temperature is below 50° F (10° C). This could possibly damage the controlled cooling system & may cause personal injury.
  •  This thermostat includes an automatic compressor protection feature to avoid potential damage to the system from short cycling. This thermostat automatically provides a 5-minute delay after turning off the cooling output to protect the compressor.

NOTE: Test your thermostat prior to programming any user settings. Pressing the RESET button will erase any user entries previously programmed. This will erase all user settings and return them to their default values.

  1. Place the system switch in the HEAT position.
  2. Press the button on the keypad until the setpoint temperature setting is a minimum of 3 degrees higher than the current room temperature. The heating system should start within several seconds. The fan may not turn on immediately due to the heating system’s built-in fan delay.
  3. Place the system switch in the OFF position. The heating system should stop within several seconds.
  4. Place the system switch in the COOL position.
  5. Press the button on the keypad until the setpoint temperature is a minimum of 3 degrees lower than the current room temperature.
  6. The cooling system should start within several seconds. Place the system switch in the OFF position. The cooling system should stop within a few seconds.
  7. Place the fan switch in the ON position. The system blower should start.
  8. Place the fan switch in the AUTO position. The system blower should stop.

USREORG RSAETMTMININGGS
Default Thermostat Settings

Operation Mode Normal Operating Mode
Room Temperature 70˚ F (21.0˚ C), to be renewed within

5 seconds

Setpoint Temperature According to system switch: 62˚ F (17.0˚ C) for Heat and Off

85˚ F (29.0˚ C) for Cool

Temperature Scale ˚F or ˚C dependent on switch setting
First Stage Differential 0.5˚ F (0.25˚ C)
Second Stage Differential 2˚ F (1.0˚ C)
Short Cycle Protection Timer Reset
Output Relays Off

Setting Temperature Differential
The default settings for the first and second stage differentials are compatible with most systems and applications. This is normally set at the time of installation and usually does not require any modification under normal operating conditions. If you feel that the first or second stage of your system is turning on too often, simply follow the instructions below.
NOTE: The first and second stage differential settings are the same for both the heating and cooling systems

Setting First Stage Differential

The default setting is 0.5° F (0.25° C). The room temperature must change by 0.5° F (0.25° C) from the setpoint temperature before the thermostat will initiate the system in heating or cooling.

  1. In normal operating mode, press and hold the buttons at the same time for 4 seconds. The LCD display will show “SET D1 x°”, where “x” equals the °F / °C differential setting. This is the current first stage differential setting.Braeburn-1100-Non-Programmable-Thermostats-User-Manual-FIG-1
  2. Press the or buttons to set the first stage differential to your desired setting of .5°, 1°, or 2° F (.25°––displayed as .2°, .5°, or 1° C).
  3. The default setting is 2° F (1.0° C). This means that the room temperature must change 2° F (1.0° C) in addition to the first stage of differential setting before the thermostat will initiate the second stage of the system in heating.  Press the buttons at the same time again and the LCD display will show “SET D2 x°”, where “x” equals the °F / °C differential setting. This is the current second-stage differential setting.
  4. Press the or buttons to set the second stage differential to your desired setting of 2°, 3°, 4°, 5°, or 6° F (1.0°, 1.5°, 2.0°, 2.5°, or 3.0° C).Braeburn-1100-Non-Programmable-Thermostats-User-Manual-FIG-2

NOTE: If you do not desire to change the second stage differential “SET D2” setting, you can wait 5 seconds and the thermostat will automatically return to the normal operating mode. Otherwise, you can press the and buttons at the same time twice to skip the second stage differential setting

USREORG RSAETMTMININGGS cont

NOTE: Once you have finished setting the differentials, you can wait 5 seconds and the thermostat will return to the normal operating mode, or you can press both and buttons at the same time to return to the normal mode.
NOTE: To erase all user program settings, gently press the RESET button using a paper clip or a small pencil tip. This will return all thermostat settings to their default values. Remember, this will erase all user program settings entered by the user.

ADDITIONAL

OPERATION FEATURES
Review Set Temperature

  1. Press and hold the or buttons. The current setpoint temperature will be displayed in place of the current room temperature, and the indicator SET will be displayed.
  2. The display will return to the normal operating mode when the or button is released. Continuing to hold the or button for 3 seconds or longer will allow the user to change the current setpoint temperature (See Changing Set Temperature).Braeburn-1100-Non-Programmable-Thermostats-User-Manual-FIG-3

Changing Set Temperature

Braeburn-1100-Non-Programmable-Thermostats-User-Manual-FIG-4

  1. Press and hold or button for 3 seconds. The entire display will flash once and the SET indicator will be flashing. Release the or button and press the or button again as desired to adjust the set temperature.
  2. The display will return to normal operating mode after 5 seconds, or you can press the and buttons at the same time to return to the normal operation mode.
  3. The SET indicator will turn off indicating that the current temperature shown in the display is the room temperature.

Compressor Protection
This thermostat includes an automatic compressor protection feature to avoid potential damage to the system from short cycling. This thermostat automatically provides a 5-minute delay after turning off the cooling output to protect the compressor.
NOTE: The installer can reset the thermostat and bypass the compressor protection features by pressing the RESET button. This will erase all user program settings and should only be used during installation for testing purposes or to reset a thermostat to regain normal operation. This will return all thermostat settings to their default values. The user will have to re-program all of the erased settings.

ADDITIONAL OPERATION FEATURES

Resetting Thermostat
Non-Volatile Memory
The Reset feature allows the user to completely reset the thermostat and to register new manual °F / °C temperature scale switch settings.

  1. To erase all entered program settings, gently press the RESET button using a paper clip or a small pencil tip.
  2. This will return all thermostat settings to their default values and register all new manual °F / °C temperature scale switch settings.
  3. In the event of a power failure, the Non-Volatile Memory feature of this unit allows all settings to be recovered, eliminating the need to reset the temperature and differential settings. When AC power is restored after an outage, all settings are retrieved from memory and reinstated

TROUBLESHOOTING

SYMPTOM POTENTIAL SOLUTION
Thermostat does not turn on heating or cooling system. Check to see if OFF is shown in display. This indicates that the system is turned off at the thermostat. Move the system selector switch to the HEAT or COOL position. After the compressor short cycle protection 5-minute period expires the system should start within a minutes time.

Compressor protection features may be in effect due to compressor short cycle conditions. See Compressor Protection section for full explanation of this feature.

Thermostat turns on heating instead of cooling, or cooling instead of heating. Check thermostat wiring to make sure that the heating and cooling stages are connected to the correct terminals on the wiring terminal block. See Installation and Wiring Diagram sections of this manual.
Thermostat turns heating or cooling system on too often or not often enough. Increase or decrease first stage temperature differential setting as appropriate to provide the desired performance level. See Setting Temperature Differential section of this manual.
Thermostat turns on second (auxiliary) stage of heating or cooling too quickly or not quickly enough. Increase or decrease second (auxiliary) stage temperature differential setting as appropriate to provide the desired performance level. See Setting Temperature Differential section of this manual.
SYMPTOM POTENTIAL SOLUTION
ThermBraeburn-1005-Non-Programmable-Thermostats-Installation-Guide-fig-7ostat display is blank. It is possible that AC power is not present at the thermostat. Check fuse, circuit breaker and thermostat wiring as appropriate to verify AC power is available.

If AC Power is present, call a professional service technician immediately to verify thermostat and system performance.

HI is shown in the thermostat display where the room temperature is normally displayed.Braeburn-1005-Non-Programmable-Thermostats-Installation-Guide-fig-8 The temperature sensed by the thermostat is higher than the 90˚ F (32˚ C) upper limit of the thermostats display range. The display will return to normal after the sensed temperature lowers within the 45˚ to 90˚ F (7˚ to 32˚ C) display range. Turn on the cooling system or use other methods to lower the temperature accordingly.

This condition could occur from the system being turned off during an exceptionally warm period or upon installation when the thermostat has been stored for a long period of time in a warm vehicle or location prior to being installed. The thermostat is equipped with a mechanical high-temperature safety switch that will turn off the thermostat should the temperature exceed 99˚ F (37˚ C) in the heat mode.

LO is shown in the thermostat display where the room temperature is normally displayed. The temperature sensed by the thermostat is lower than the 45˚ F (7˚ C) lower limit of the thermostats display range.

The display will return to normal after the sensed temperature rises within the 45˚ to 90˚ F (7˚ to 32˚ C) display range. If the temperature in the controlled space seems to be normal, wait for the thermostat to acclimate to the correct room temperature.

If the room seems to be colder than usual, turn on the heating system to raise the temperature as needed for comfort within the room.

This condition could occur from the system being turned off during a cold weather period or upon installation when the thermostat has been stored for a long period of time in a cold vehicle or location prior to being installed. The thermostat should be allowed to warm up prior to installation to allow proper heating control once installed.

Thermostat will not allow me to program a setpoint temperature higher than 90˚ F (32˚ C). This is above the normal thermostat temperature setting range of 45˚ to 90˚ F (7˚ to 32˚ C).
Thermostat will not allow me to program a setpoint temperature lower than 45˚ F (7˚ C). This is below the normal thermostat temperature setting range of 45˚ to 90˚ F (7˚ to 32˚ C).
Fan continues to run all the time whether the system is on

or off.Braeburn-1005-Non-Programmable-Thermostats-Installation-Guide-fig-6

Check that the fan control switch is in the AUTO position. This will allow the fan to run only when the heating or cooling system is turned on and running.

Check thermostat wiring to make sure that the fan control wiring is connected to the correct terminals on the wiring terminal block. See Installation and Wiring Diagram sections of this manual.

SYMPTOM POTENTIAL SOLUTION
OFF is shown in thermostat display and heating or cooling system will not start. This indicates that the system is turned off at the thermostat. Move the system selector switch to the HEAT or COOL position. After the compressor short cycle protection 5-minute period expires the system should start within several seconds.
The room is too warm or too cold. See Review Set Temperature section of this manual to verify the current setpoint and make any modifications that are necessary.

WIRING DIAGRAM

Wiring Diagram for 2 Stage Heat, 1 Stage Cool

Braeburn-1100-Non-Programmable-Thermostats-User-Manual-FIG-5

Store this booklet for future reference

Braeburn-1100-Non-Programmable-Thermostats-User-Manual-FIG-6

Braeburn Systems LLC warrants each new Braeburn thermostat against any defects that are due to faulty material or workmanship for a period of five years after the original date of purchase by a professional service technician. This warranty and our liability do not apply to batteries, nor does it include damage to merchandise or the thermostat resulting from accident, alteration, neglect, misuse, improper installation or any other failure to follow Braeburn installation and operating instructions.

Braeburn Systems LLC agrees to repair or replace at its option any Braeburn thermostat under warranty provided it is returned postage prepaid to our warranty facility in a padded carton within the warranty period, with proof of the original date of purchase and a brief description of the malfunction. This limited warranty does not include the cost of removal or re-installation. This warranty gives you specific legal rights and you may also have other rights that vary from state to state or province to province. Answers to any questions regarding our limited warranty may be obtained by writing our corporate offices.

WARRANTY FACILITY: Braeburn Systems LLC Attn: Warranty Department 2215 Cornell Avenue Montgomery, IL 60538 Braeburn Systems LLC
2215 Cornell Avenue • Montgomery, IL 60538
Technical Assistance: www.braeburnonline.com
Call us toll-free: 866-268-5599 (U.S. Only)
630-844-1968 (Outside the U.S.)
© 2004 Braeburn Systems LLC • Patents Pending • All Rights Reserved. Pub. No. 1100-100-004

REFERENCE

Download Manual

Braeburn 1100 Non-Programmable Thermostats User Manual

Braeburn-logo

Braeburn 1100 Non-Programmable Thermostats User Manual

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post’s permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post’s URL again. (Find out more about Webmentions.)