AMANA-logo

AMANA PHWT-A100C Non-Programmable Electronic Thermostat

AMANA-PHWT-A100C-Non-Programmable-Electronic-Thermostat-product

DESCRIPTION AND COMPATIBILITY

The Amana PHWT-A100C is a non-programmable electronic thermostat, which can be used with the following heating/cooling applications:

SPECIFICATIONS

SAFETY INFORMATION

TO REMOVE EXISTING THERMOSTAT

  1. Write down the letters printed near each wire terminal that is used, and the color of each wire it is connected to; self-adhesive wire labels are also enclosed.
  2. Carefully remove wires from existing thermostat and bend so they cannot fall back into wall or touch each other.
  3. Remove existing thermostat base from the wall.

TO INSTALL NEW THERMOSTAT

  1. Mount the thermostat on an inside wall about five feet above the floor in an area that has good circulation, but is not directly affected by a vent or duct.
  2. If painting or construction is still ongoing, cover the thermostat completely or wait until work is complete before mounting thermostat.
  3. If new mounting holes are needed, mark the placement of the new mounting holes throughthe thermostat base. Using a 3/16” drill bit, drill the holes you have marked and insert the supplied wall anchors.
  4. Feed the wires through the wire opening in thebase and use supplied screws to mount base to the wall.
  5. Using Section 7) WIRING DIAGRAMS, wire each terminal on the new thermostat base. Ensure that the bare end is fully seated into the connector, then tighten securely. Pull gently on wires to ensure they are secure.
  6. Place thermostat front back onto the base.
  7. Restore power back to heating and cooling components and thermostat.
  8. See Section 8) INSTALLER SETTINGS MENU, to adjust the required settings needed for each system type.

FRONT PANEL CONTROLS

THERMOSTAT SYSTEM MODE SWITCH POSITIONS:

AMANA-PHWT-A100C-Non-Programmable-Electronic-Thermostat-fig-1

THERMOSTAT FAN SWITCH POSITIONS

AMANA-PHWT-A100C-Non-Programmable-Electronic-Thermostat-fig-2

THERMOSTAT BUTTONS

AMANA-PHWT-A100C-Non-Programmable-Electronic-Thermostat-fig-3

Note: to adjust the target set temperature, first ensure that the thermostat is in either Heat or Cool mode, and press either the up or down buttons until the desired target temperature is reached. Presses to the Up or Down buttons will have no effect when the thermostat is in Off mode.

SETTING A KEYPAD / FRONT PANEL LOCKOUT

WIRING DIAGRAMS

UP TO 1H/1C CONVENTIONAL APPLICATIONS:

(AMANA PTC PTAC MODELS)

AMANA-PHWT-A100C-Non-Programmable-Electronic-Thermostat-fig-4

WIRING DIAGRAM NOTES

AMANA-PHWT-A100C-Non-Programmable-Electronic-Thermostat-fig-5

UP TO 1H/1C HEAT PUMP APPLICATIONS

(AMANA PTH & HEH PTAC MODELS)

AMANA-PHWT-A100C-Non-Programmable-Electronic-Thermostat-fig-6

WIRING DIAGRAM NOTES

INSTALLER SETTINGS

MENU# SETTING OPTIONS
01 Scale F, C
02 Temp. Calibration Zero, -5F to +5F (-3C to +3C)
04 Max. Heat 60F to 90F (80F)

(16C to 32C)

05 Min. Cool 60F to 80F (65F)

(7C to 24C)

09 Swing /

Temp. Differential

±0.25F (±0.14C)

±0.50F (±0.28C)

±1.00F (±0.56C)

±2.25F (±1.25C)

17 Backlight Always On Off=Turn off 10 sec

On=Always On

18 Use default set temp. after mode change ON: Uses default temps

OFF: Use last temp per mode

19 Default heat mode set temp. 70F (21C)

60F to max heat set temp

20 Default cool mode set temp 74F (23C)

60F to max set temp

98 Compressor Protection Bypass No=Delays Remain

Yes=Suspend Delay

99 RESET No=Save and Exit

Yes=Full Reset

SETTING DESCRIPTIONS

TO ENTER SETTINGS MENU

AMANA-PHWT-A100C-Non-Programmable-Electronic-Thermostat-fig-8

TO CHANGE AN ENTRY

AMANA-PHWT-A100C-Non-Programmable-Electronic-Thermostat-fig-9

TO ADVANCE TO THE NEXT MENU ITEM

AMANA-PHWT-A100C-Non-Programmable-Electronic-Thermostat-fig-10

TO RETURN TO THE MAIN THERMOSTAT SCREEN

AMANA-PHWT-A100C-Non-Programmable-Electronic-Thermostat-fig-11

Waiting for 1-Minute with no button presses will exit the settings menu with all items saved as they were last shown on the display screen.

CONTACT

PTAC DIRECT SALES, INC.

53608

Reference

Download Manual:

AMANA PHWT-A100C Non-Programmable Electronic Thermostat INSTALLATION INSTRUCTION

AMANA-logo

AMANA PHWT-A100C Non-Programmable Electronic Thermostat INSTALLATION INSTRUCTION

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)