Source1-LOGO

Source1 S1-THPU433-S High-Resolution Digital Thermostat

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-PRODUCT

Get To Know Your Thermostat

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (3)

Dropdown Dashboard

The Dropdown Dashboard displays temperature, humidity, and other readings. It will also show the high and low readings of the day.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (4)

Dropdown Dashboard
(The contents of your Dashboard may vary)

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (7). Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (8)

Care and Use of Your Thermostat

Pencils, pens and other sharp objects should never be used on your thermostat; these may damage your touchscreen. Only use your finger tip to press the touchscreen buttons.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (9)

DO NOT USE ABRASIVE CLEANERS OR CLEANERS THAT CONTAIN SOLVENTS. DO NOT SPRAY ANYTHING DIRECTLY ONTO THE THERMOSTAT.

Quick Start

Temperature, Modes & Fan

Selecting Your Desired Temperature and Mode Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (10)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (11)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (12) Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (13)

AUTO-CHANGEOVER MODE – Pressing the WARMER or COOLER buttons in Auto mode will adjust both the heat and cool setpoints simultaneously. To adjust heat and cool setpoints individually, choose HEAT mode to adjust the heat setpoint and COOL mode to adjust the cool setpoint, then return to AUTO mode.
HEAT OR COOL MODE – Pressing the WARMER or COOLER buttons in Heat or Cool mode will adjust only the heat or cool setpoints.

Using the Fan Button

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (15)

Set Time & Date

NOTE: When the thermostat is connected to a Skyport account, the Time & Date are automatically synchronized to the Skyport Cloud, including automatic Daylight Savings adjustments. Your time zone is selected in the Skyport web application.

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (16).

Setting the Time
Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (17)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (18)

Setting the DateSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (19)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (20)

Connect to Wi-Fi

Connect to Wi-Fi (from initial start-up)
When power is connected to the thermostat and it has not been configured to connect to a Wi-Fi Access point, the following message appears:Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (21)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (22)

Although there is more than one way to create a Skyport account, the steps below illustrate creation from a browser.
If the thermostat is connected to the local Wi-Fi Access Point, but not yet joined to a Skyport account, you may join the thermostat to an account by doing the following:

  1. Open your browser to: https://Source1.skyportcloud.com
  2. Select “Create account now”
  3. Create Account NowSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (25)
  4. Follow the on-screen instructions to create an account and add a thermostat to the Skyport account.

Main Menu Buttons

ScheduleSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (26)

This thermostat features up to four programmable time periods per 24 hour day: Morning, Day, Evening, and Night. The start time for each time period is adjustable. The stop time for each time period is
the start time for the next period.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (27)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (28)

Press a day of the week to view its settings. This may be repeated for each day.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (29)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (30)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (31)

Press and select a Time Period (Morning, Day, Evening, or Night) to editSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (32)

Adjust Mode, Start Time, and Heat and Cool Setpoints to desired settings. The Time Period may also be Enabled or Disabled. Un-check the Enabled box for Time Periods you don’t want to use. Press DONE when finished.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (33)

When you are finished editing the four time periods pressSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (34)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (35)

Smart Fan

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (36)

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (37)The fan may be programmed to turn on automatically for a specific period during the day.

Press to turn fan schedule on or off

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (38)

Set the minimum number of minutes the fan will run from the top of each hour. Set runtime to 60 minutes to be on continuously from Start Time to Stop time. (5 – 60 mins.)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (39)

Set when the Smart Fan schedule will start and stop. For example, you may not want Smart Fan to run during sleeping hours.

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (40)

Choose which days of the week Smart Fan will run

Screensaver

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (41)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (42)

Alerts

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (43)

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (44)The alerts let you know when your system needs serviceSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (45)

View your service company’s contact information

Display

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (46)

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (47)The display brightness options may be adjusted in this menu.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (48)

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (49)Maintenance allows you to clean and calibrate the touchscreenSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (50)

When calibration is complete, the thermostat will automatically restart and return to the Home Screen.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (51)

Preferences

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (52)You may set the type of background that appears on the thermostat Home Screen.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (53)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (54)

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (55)The Humidity feature allows the thermostat to control a humidifier or use your air conditioner to dehumidify the space
IMPORTANT: Aux Output Usage must be set for Hum or Dehum for these settings to take effect.
See AUX Output Settings.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (56) Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (57)

Vacation/Away

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (58)Vacation or pressing the AWAY button, will use temporary, energy saving settings without changing the regular schedule. Pressing the HOME button will return the thermostat to normal comfort settings.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (59) Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (60)

Security

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (61)

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (62)Security settings may be set to limit or prevent changes to your thermostat.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (63)

Information

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (64)

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (65)This button contains valuable service and system runtime information.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (66)

Settings

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (67) Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (68) Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (69) Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (70)

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (71)Thermostat heating and cooling options are found in this menuSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (72)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (73)

Smart Recovery turns on the heat or cool before the Morning start time to bring the room temperature to the Morning setpoint at the start of the Morning time period. Please allow 4-8 days for Smart Recovery time to adjust. When used with a heat pump, electric strip heat will be disabled while Smart Recovery is active.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (74)

Turn on Simple Thermostat for the most basic user interface
When Simple Thermostat is on, alerts will appear in the top bar of the main screen. Press on the top yellow alert bar to view alerts

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (75)

Note: When using the Simple Thermostat Home Screen; the program schedule along with the HOME and AWAY features are unavailable.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (76)

TouchScreen thermostats support the handling of specific signals from the utility provider. The utility-generated signals carry pricing information and/or setback actions that alter the comfort settings of the thermostat in order to reduce energy usage on demand. This is known as Automated Demand Response or ADR for short. You must register to participate in a utility-sponsored program, if offered by your local utility, to take advantage of this feature.

SKYPORT CLOUD SERVICES
From the web application, the user will select Thermostat Settings from the left column. Then the Demand Response button is selected.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (77)

Selecting the Overview tab of the ADR page will cause a summary of ADR events to be displayed.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (80)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (81)

Utility and Program setup must be done at the Skyport Cloud Services account. From the thermostat Home Screen, press the ‘Menu’ button, then select ‘Settings”.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (82)

From the above screen the ‘Automated Demand Response’ button is pressed.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (83)

By selecting ADR – On, the user can participate in ADR events triggered by their utility, or price-dependent events.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (84)

Selecting the ‘Price Dependent Action’ button allows the user to determine what action is taken when the price rises above the set threshold.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (85)

In the above example; if the price threshold is exceeded, the thermostat will invoke the ‘Offset Setpoints’ configured for an ADR event until the event is over.
Please note that the Threshold price may only be set in the Skyport Cloud Services account.
Selecting ‘Skip Event’ will take no action when the set price threshold is exceeded.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (86)

The user may limit the maximum Cooling Setpoint.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (87)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (88)

The user may limit the minimum Heating Setpoint.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (89)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (90)

The user may adjust the ADR Cooling ‘static’ Setpoint. Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (92)

The user may adjust the ADR Heating ‘static’ Setpoint.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (93) Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (94)

The user may adjust the ADR Cool offset. During an ADR event the cooling setpoint will be adjusted by the amount of degrees configured in this step.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (95) Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (96)

The user may adjust the ADR Heat offset. During an ADR event the heating setpoint will be adjusted by the amount of degrees configured in this step.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (97)

When an ADR event is pending, and hasn’t started yet, there will be a yellow leaf on the top bar. This will be accompanied by associated text as shown below.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (98)

During an ADR event there will be a green leaf on the top bar. This will be accompanied by associated text as shown below.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (99)

If a Warmer or Cooler button is pressed during an active ADR event, then the user is presented with this opt-out screen.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (100)

If a pricing triggered ADR event is enabled, there will be a green leaf on the top bar along with the actual cost of energy. This will be accompanied by associated text as shown belowSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (101)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (102)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (103)

The Deadband is the number of degrees or minutes that the thermostat waits before it initiates the stages of heating or cooling.
1st Stage Deadband Specifies the minimum temperature difference between the room temperature and the desired setpoint before the first stage of heating or cooling is allowed to turn on. For example, if the heat setpoint is 68˚ and the 1st Stage deadband is set to 2 degrees, the room temperature will need to drop to 66 degrees before the heat turns on.

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (104)

Free Cooling requires additional dampers and duct work to be installed. Additionally, the thermostat is wired in a different manner for this feature to function properly. Before enabling this feature, please make sure these steps are completedSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (106)

If you don’t have a compressor, set Mechanical Cooling to “NO”, Y1 will then be used to control the Free Cooling Damper(s) and Y2 will be disabled. If set to “YES”, mechanical (compressor) cooling will be controlled by the Y2 terminal. (See page for wiring diagram)83
Mechanical air conditioning is turned on with a 2nd stage demand for cooling and the Free Cooling, outdoor air damper is closed.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (107)

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (108)

This feature is for heat pump applications only

NOTE: Once the change to fossil fuel is made, the heat demand must finish with fossil fuel. Additional heat demands within 10 minutes will also use fossil fuel, regardless of outdoor temperature or stage demand.

Allows the W3/AUX output to be used for Heating, Humidification, or Dehumidification

IMPORTANT: Aux Output Usage must be set for Hum or Dehum before any settings will take effect in the Humidity Main Menu.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (110)

The AUX Output polarity may be set for Normally Open or Normally Closed to accommodate different types of humidification and dehumidification equipment.

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (111)

Runs the fan for a short time after Cooling or electric strip heat turns off to increase system efficiency. (0 – 120 Secs.)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (112)

When a remote sensor is connected to the thermostat, the user may choose which sensor source is used to measure room temperature.

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (114)

The wireless sensor may be used as follows:

 

The wired sensor may be used as follows:

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (115)

The thermostat and wired sensor may be calibrated -7 to +7 degrees F. The integral humidity sensor may be calibrated -20% to +20% RH

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (115)

The installer or service technician can use this feature to test the functions without any time delays from the thermostat.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (117)

A Dealer may enter their company contact information for the customer to use when they need service. This will appear when the “Who To Call For Service” button is pressed in the Information Menu.
Use the keyboard to enter your information.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (118)

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (119)

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (120)

Wi-Fi

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (121) Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (122)

Wi-Fi Status
It is here that you will find helpful information regarding the connectivity status of your thermostat, including the thermostat’s ID.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (124)

Choose your network from the list and enter the network password.
If your network does not appear in the list, hit the refresh button.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (125)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (126)

Local API Option

Turning on the local API allows 3rd party software to interface with your thermostat, such as a home automation system.
This is the default with the local API OFF.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (127)

To turn on the HTTP Local API select Local API
If a Secure API is preferred, then select API ProtocolSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (128)

Upon pressing API Protocol, the following screen will appear

Then select HTTPS and press BACK

Upon pressing BACK, the screen will look like this.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (129)

Select Basic Auth User, and enter the appropriate information on the screen below and press DONE to save.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (130)

Select Basic Auth Password as the next step.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (131)

Basic Auth Password

Select Basic Auth Password and enter the appropriate information on the screen below and press DONE to save.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (133)

The last step is to turn the Local API as shown below.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (134)

SkyportSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (135)

Pressing this button will let you know if you are paired with a Skyport account. If not, then you may follow prompt and instructions to create an account and add the thermostat to the account.

Emergency Heat

The Emergency Heat function is only available if your thermostat is set to control a Heat Pump.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (136)

To initiate the Emergency Heat feature, Press the Emergency Heat button. During Emergency Heat operation the thermostat will turn on the fan and auxiliary stages of heat when there is a demand for heat. The 1st stage of heating and all stages of cooling will be unavailable. To exit Emergency Heat, press the Emergency Heat button.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (137)

CTS Series Desktop App

CTS Series Desktop App may be downloaded at no charge at: http://source1thermostats.com/CTSSeries.html#desktopAppSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (138)

Every time the user runs the CTS Desktop App software,
it automatically connects to the Source 1 Color Display website in the background and updates the software and firmware (the operating system for touch screen) at no cost.

The CTS Series Desktop App allows you to use your computer to:Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (139)

CTS Series Assistant

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (140)

Uploading Photos and Settings to your thermostat
When you are finished adding and editing photos and settings, click on Save to SD. When prompted, remove the SD card from the SD card reader on your computer.

At the thermostat:

Your thermostat will automatically save your new photos and settings in its internal memory. When finished, you may remove the SD card. It is not needed for normal thermostat operation.

Installation Instructions

Remove and Replace the old thermostat

To install the thermostat properly, please follow these step-by-step instructions. If you are unsure about any of these steps, call a qualified technician for assistance.

Wire Connections

If the terminal designations on your old thermostat do not match those on the new thermostat, refer to the chart below or the wiring diagrams that follow.

Wire from the old thermostat terminal marked  

Function

Install on the new thermostat connector marked
G or F Fan G
Y1, Y Cooling Y1
W1, W Heating W1/0/B
Rh, R, M, Vr, A Power R
C Common C
O/B Rev. Valve W1/O/B*
W2 2nd Stage Heat W2
Y2 2nd Stage Cooling Y2
W3 3rd Stage Heat W3
OUT – Outdoor Sensor SENSOR
OUT + Outdoor Sensor SENSOR

O/B is used if your system is a Heat Pump.

Before you go any further, determine what your existing wiring and equipment situation is.

Making 4 Wires Work When 5 Wires Are Required

If you would like to install the Source 1 thermostat using only 4 wires when 5 are required, follow the directions below. You will need a screwdriver along with a 3″ long piece of thermostat wire to use as a jumper:

  1. Make sure the power is off.
  2. Label and disconnect wires at the thermostat. Please note the color and corresponding wire designator with each color. For example: The R wire is red and the W wire is white and so on. You will need this information handy for the next step at the HVAC equipment.
  3. At the HVAC equipment end of the thermostat wires (usually at the furnace), locate the terminals that the wires are attached to.
  4. Remove the “G wire” from the terminal marked G.
  5. Place the “G wire” on terminal C.
  6. Place one end of the 3″ long jumper on terminal G.
  7. Place the other end of the 3″ long jumper on terminal Y. Please note that there will be more than 1 wire on terminal Y.
  8. When connecting the wires to the Source 1 thermostat, note that the wire that was previously connected to the G terminal of the old thermostat will now be required to be connected to the C terminal on the Source 1 thermostat. All other wires will be connected such that the connections on each end of the individual wires match terminal designations. For example: Connect the yellow wire on the thermostat end to the Y terminal on the thermostat. The yellow wire will be connected to the Y terminal on the HVAC equipment end also.

Making 5 Wires Work When 6 Wires Are Required

If you have a system that requires 6 wires, and you would like to install the Source 1 thermostat using only 5 wires, follow the directions below. You will need a screwdriver along with a 3″ long piece of thermostat wire to use as a jumper:

  1. Make sure the power is off.
  2. Label and disconnect wires at the thermostat. Please note the color and corresponding wire designator with each color. For example: The R wire is red and the W wire is white and so on. You will need this information handy for the next step at the HVAC equipment.
  3. At the HVAC equipment end of the thermostat wires (usually at the furnace), locate the terminals that the wires are attached to.
  4. Remove the “G wire” from the terminal marked G.
  5. Place the “G wire” on terminal C.
  6. Place one end of the 3″ long jumper on terminal G.
  7. Place the other end of the 3″ long jumper on terminal Y. Please note that there will be more than 1 wire on terminal Y.
  8. When connecting the wires to the Source 1 thermostat, note that the wire that was previously connected to the G terminal of the old thermostat will now be required to be connected to the C terminal on the Source 1 thermostat. All other wires will be connected such that the connections on each end of the individual wires match terminal designations. For example: Connect the yellow wire on the thermostat end to the Y terminal on the thermostat. The yellow wire will be connected to the Y terminal on the HVAC equipment end also.

The Source 1 Thermostat BackplateSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (142)

NOTE:
The backplate does not fully cover a full-size vertical junction box. The S1-CTSPLATE Source 1 Wallplate or a single-gang, horizontally mounted junction box would be needed for that type of installation
To remove the thermostat backplate: Using the Finger Pull Areas, pull the front housing away from the backplate.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (143)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (144)Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- 156

IMPORTANT: This thermostat requires both R (24 VAC Return) and C (24 VAC Common) to be connected to the backplate terminals.

Explanation of Thermostat Dip Switches

Dip switches are located on the back of the thermostat

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (145)

Sample Wiring Diagrams with Dip Switch Positions Conventional Heating and Cooling Systems

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (149) Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (150)

Sample Wiring Diagrams with Dip Switch Positions Heat Pump Systems

Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (151)

Sample Wiring Diagrams with Dip Switch Positions Heat Pump Systems with Dual FuelSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (152)

Sample Wiring Diagrams

Outdoor Sensor: S1-CTSDTS Temperature Sensor 10K ohm sensor at 77F/25C. Negative Temperature Coefficient.Source1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (153)

Sample Wiring Diagrams

Humidification

AUX Output Usage must be set for HumSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (154)

Dehumidification

AUX Output Usage must be set for DehumSource1-S1-THPU433-S-High-Resolution-Digital-Thermostat-FIG- (155)

Troubleshooting

Warranty

THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR:

This warranty gives you specific legal rights and you may also have other rights which may vary from state to state.
Patents Issued & Pending P/N 88-1406 Rev. 2 02/20

CAUTION

Follow the Installation Instructions before proceeding. Set the thermostat mode to “OFF” prior to changing settings in setup or restoring Factory Defaults.

FCC Compliance Statement

This equipment has been tested and found to comply with the limits for an intentional radiator, pursuant to Part 15, subpart C of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference in radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

Notice: Only peripherals complying with FCC limits may be attached to this equipment. Operation with noncompliant peripherals or peripherals not recommended by Source 1, is likely to result in interference to radio and TV reception. Changes or modifications to the product, not expressly approved by Source 1 could void the user’s authority to operate the equipment.

FCC – INDOOR Mobile Radio Information:

We, Source 1, declare under our sole responsibility that the device to which this declaration relates: Complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation

Glossary of Terms

REFERENCE:

DOWNLOAD MANUALS:

Source1 S1-THPU433-S High-Resolution Digital Thermostat Owners Manual

Source1-LOGO

Source1 S1-THPU433-S High-Resolution Digital Thermostat Owners Manual

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)