Siemens RDF870KN Touch Screen Room Controller Thermostat
Introduction
Reference pages | Terminals | Description | |
RDF870KN | RDF870MB | ||
![]() Application |
L, N
Q1, Q2, Q3, Q4 |
L, N
Q1, Q2, Q3, Q4 |
AC 230 V operating voltage
Fan relay with max four speeds outputs |
![]() |
X1, X2
M |
X1, X2
M |
Multifunctional inputs 1 & 2
Input reference ground |
Installation | Y50 | Y50 | DC 0…10 V output |
![]() Parameters |
CE+, CE-
– – |
–
A+, B- REF |
KNX bus + and – terminals Modbus + and – terminals
Modbus reference ground |
Symbols
Status symbols
Selection symbols
Operational icons
Commissioning
Download via ETS
Note: This operation applies to RDF870KN only.
- Screen idle
- Touch digits/screen
- Normal display
- Touch & hold the icon > 5 s to enter Programming mode
- Ready for downloading address & application
Commissioning: Local via DIP switches
- Set application via DIP switches
- Refer to
- Refer to
- Configure basic control parameters
DIP switch positions |
Application |
|
1 | 2 | |
ON |
OFF |
Room unit |
OFF |
OFF |
Room controller |
DIP switch setting applies to RDF870MB only.
Current factory setting for PM2.5 control with 3 speed on/off fan application:
- APP= 1: PM2.5 control only
- DISP: Room temp= 1; PM2.5= 1
- SEN1= 3: PM2.5 (AI) μg/m3 (0…10 V)
- SEN2= 0: no function
- FAN= 3: 3 speed fan
OPERATIONS INSTRUCTIONS
Idle screen shows default PM2.5
- Screen idle
- Touch digits / screen
- Normal display / mode
Normal display for ventilation
- Screen idle
- Touch digits / screen
- Normal display / mode
If unit is OFF
- Screen idle
- Touch digits / screen
- Unit being turned ON
- Normal display / mode
Adjust setpoint
- Touch icon
- Press + or – to adjust:
Single fan: On/Off only
- Touch icon
- Press + or – to adjust:
- Change fan mode:
- ON > AUTO
- See
for fan type selection.
Fan speed selection
Adjust 3- or 4-speed fan:
- Touch icon
- Press + or – to adjust:
- Auto
- Speed 1
- Speed 2
- Speed 3
- Speed 4
- Depends on fan type selection
- Auto
Adjust ECM fan:
- Touch icon
- Press + or – to adjust:
Fan speed is adjusted by percentage
- Touch + or – once to adjust speed by 5 %.
- Press and hold + or –to quickly adjust speed.
(See Min./Max. settings in Engineering mode parameters)
Dual fan operations
(RDF870MB RU only)
- Touch icon
- Use
or
and press + or – to adjust:
Change operating modes
- Touch icon
- Press + or – to select:
- ON: Comfort mode
- ECO: Economy mode, a
symbol will be shown
- OFF: OFF
Adjust timer
(Fan filter alarm)
Change timer setpoint (TCSP) default value:
- Touch timer area once to enter time counter setting
- Press + or – to adjust:
Reset timer:
- Press and hold timer area more than 10 s to reset timer to 0.
View alarms
(RDF870KN)
- When alarm bell is displayed
- Touch icon once and press
or
to view all alarms
View alarms
(RDF870MB)
- When alarm bell is displayed
- Touch icon once and press
or
to view all alarms
View alarms
(RDF870MB room unit)
- When alarm bell is displayed
- Alarm AL originates in the controller when RDF870MB works as a room unit.
Priority | Alarm/Service Display | Error code * | Type | Product | |
1 | Bus power supply | BUS | 5000 | Fault | RDF870KN |
2 | Device address error | Adr | 6001 |
– |
RDF870KN |
4 | External fault input 1 | AL1 | 9001 | RDF870.. | |
5 | External fault input 2 | AL2 | 9002 | RDF870.. | |
6 | Clean filter reminder | FIL | 3911 | RDF870.. | |
7 | Internal sensor error | Er1 | – | RDF870.. | |
8 | EEPROM error | Er2 | – | RDF870.. | |
9 | External error | Er3 | – | RDF870.. |
- Error codes are for RDF870KN only.
Parameter mode user access
- Touch & hold icon > 5 s
- Enter first password via
or
- Enter the second password via
or
- After 6 seconds
Note: Press the Setting icon to exit or re-enter the password if not correct - Edit parameters.
- Exit parameter mode
Engineering parameters
Item | Description | Range Factory settings | |
MODA | Modbus address
setting |
1…247 | 1 |
MODB | Modbus baud rate setting | 1: 9600 bps 2: 19200 bps 3: 38400 bps |
2: 19200 bps |
MODF | Modbus data frame format | 0: 1/8/E/1 1: 1/8/O/1 2: 1/8/N/1 3: 1/8/N/2 |
0: 1/8/E/1 |
APP | Application selection | 1: PM2.5 control only 2: PM2.5 + CO2 control 3: CO2 control only 4: Ventilation |
1: PM2.5 control only |
DISP | Symbol display enable/disable | 0: Disable display 1: Enable display | 1) Room Temp= 1;
2) Outside Temp= 0; 3) PM2.5= 1; 4) VOC= 0; 5) CO2= 0; 6) RH= 0; |
SEN11) | External sensor1 type selection | 0: No function 1: Temperature (AI) (NTC 10k) 2: Temperature (AI) (0…10 V) 3: PM2.5 (AI) μg/m3 (0…10 V) 4: CO2 (AI) ppm (0…10 V) 5: VOC (AI) % (0…10 V) |
3: PM2.5 (AI)
μg/m3 (0…10 V) |
6: VOC (AI) mg/m³ (0…10 V) 7: R.h. (AI) % (0…10 V) 8: Alarm input (DI) 9: Dummy AI (0…10 V) (RU only) 10: Dummy DI (RU only) |
|||
DIL1 | Operating action if
digital input |
0: Normally open / Open 1: Normally closed / Closed |
0: Normally open /
Open |
SEN21) | External sensor2 type selection | 0: No function 1: Temperature (AI) (NTC 10k) 2: Temperature (AI) (0…10 V) 3: PM2.5 (AI) μg/m3 (0…10 V) 4: CO2 (AI) ppm (0…10 V) 5: VOC (AI) % (0…10 V) 6: VOC (AI) mg/m³ (0…10 V) 7: R.h. (AI) % (0…10 V) 8: Alarm input (DI) 9: Dummy AI (0…10 V) (RU only) 10: Dummy DI (RU only) |
0: No function |
DIL2 | Operating action if
digital input |
0: Normally open / Open
1: Normally closed / Closed |
0: Normally open /
Open |
PMH | PM2.5 sensor high range | Max. of low range…1000 | 500 |
PML | PM2.5 sensor low
range |
0…Min. of high range | 0 |
CO2H | CO2 sensor high
range |
Max. of low range…2000 | 2000 |
CO2L | CO2 sensor low range | 0…Min. of high range | 0 |
UOCH | VOC sensor high
range |
Max. of low range…100 | 5 |
UOCL | VOC sensor low
range |
0…Min. of high range | 0 |
HUMH | Humidity sensor high range | Max. of low range…100 | 100 |
HUML | Humidity sensor low range | 0…Min. of high range | 0 |
TEMH | Temperature sensor high range | Max. of low range…100 | 50 |
TEML | Temperature sensor low range | -50…Min. of high range | 0 |
SPMH | PM2.5 setpoint high range | Max. of low range…500 | 100 |
SPML | PM2.5 setpoint low range | 0…Min. of high range | 12 |
SPCH | CO2 setpoint high
range |
Max. of low range…2000 | 1500 |
SPCL | CO2 setpoint low
range |
0…Min. of high range | 500 |
FAN | Fan type selection | 1: 1-speed fan (ON/OFF) 3: 3-speed fan 4: 4-speed fan 5: ECM fan |
3: 3-speed fan |
ECMH | ECM fan output limit high | Max. of ECML…100 % | 80 % |
ECML | ECM fan output limit Low | 0…Min. of ECMH | 30 % |
TC | Filter time display | 0: Disable | 0: Disable |
setting | 1: Enable | ||
PMES2) | PM2.5 ECO mode
setpoint |
0…100 | 60 |
COES2) | CO2 ECO mode
setpoint |
500…1500 | 1000 |
BUZZ | Buzzer function | 0: Disable 1: Enable |
1: Enable |
UNIT | Temperature unit | 0: °C (degrees Celsius) 1: °F (degrees Fahrenheit) |
0: °C (degrees Celsius) |
LOCK | Keylock function | 0: Unlock 1: Locked 2: Setpoint only 3: Operating mode only 4: Setpoint and fan speed only |
0: Unlock |
OPSL | Operating mode
selection |
0: ON/OFF 1: ON/ECO/OFF 2: ON/ECO/Protection/OFF (RU only) 3: ON/ECO/Protection (room unit only) |
1: ON/ECO/OFF |
CALT | Internal temperature sensor calibration | -5…5 K | 0 |
RDF870KN available parameters and their order of appearance:
- Room controller:
- APP > DISP > SEN > FAN > OPSL > TC > UNIT > LOCK > BUZZ > CALT > APP
RDF870MB available parameters and their order of appearance:
- Room controller:
- MODA > MODB > MODF >APP > DISP > SEN > FAN > OPSL > TC > UNIT > LOCK > BUZZ > CALT > MODA
- Room unit:
- MODA > MODB > MODF > LOCK > BUZZ > CALT > MODA
- Room controller: 0…8; Room unit: 0…10
- The setpoint cannot be changed in ECO mode.
Restriction for sensor selection:
- If SEN1 and SEN2 are configured with the same selection type 1…8, they cannot be the same sensor types:
- For type 1…8, sensor1 cannot be the same as sensor2.
- For sensor types with the same function such as 1&2 or 5&6, if one sensor type is 1 or 5, the other one cannot be 2 or 6.
Firmware Setpoint Settings
Item | Description | Range Factory
settings |
|
TCSP | Filter time setting | 0…9999 | 8760 |
PM2.5 SP | PM2.5 setpoint | SPML…SPMH | 60 |
CO2 SP | CO2 setpoint | SPCL…SPCH | 1000 |
T SP | Temperature setpoint | T SP L…T SP H | 24 |
T SP H | Temperature setpoint range high | Max. of low range…200 (°C) | 50 |
T SP L | Temperature setpoint range low | -50…Min. of high range (°C) | 5 |
VOC SP | VOC setpoint | %: 0…100
mg/m3: 0…5 |
0.6 mg/m3 or
6 % |
HUM SP | Humidity setpoint | 0…100 % | 50 % |
P81 1) | Device address (KNX only) | 1…255 | 255 |
1) P81 is only for ETS and local HMI does not support P81:
- During power up, there is a startup delay (TwaitDevice = tWaitMin + DeviceAdr * 200ms) before the processing signal is processed.
- When P81=255(default), the device does not process the signal according to the heartbeat and COV mechanism. But it can respond when another device is polling.
- The local HMI does not support P81.
- When the individual address is changed via ETS, P81 is updated automatically after the device downloads it from ETS.
Expert Mode Parameters
Item | Description | Range Factory
settings |
|
PMP | PM2.5 Control factor Xp | 0…1000 | 50 |
PMI | PM2.5 Control factor Tn | 0…120 min | 45 min |
CO2P | CO2 control factor Xp | 0…2000 | 100 |
CO2I | CO2 control factor Tn | 0…120 min | 45 min |
PMDB | PM2.5 control loop
deadband |
0…20 | 10 |
CODB | CO2 control loop deadband | 0…100 | 50 |
OPAF | Operating mode settings after power failure/reset | 0: Return to the previous operating mode/user setting
1: Off |
0: Return to previous operating mode/user
setting |
FANT | Fan minimum on time (dwell time) | 1…6 min | 2 min |
FSET | Reload factory settings | 0: OFF = Disable
1: ON = Reload start “–””—””—– ” is displayed while reloading |
0: OFF = Disable |
SW | Software version | ||
EPAS | Engineer mode password | 0000…4999 | 0000 |
XPAS | Expert mode password | 5000…9999 | 9999 |
Room controller workflow:
- EPAS > XPAS > PMP > PMI > PMDB > CO2P > CO2I > CODB > OPAF > FANT > FSET > SW > EPAS
- RDF870MB Room unit workflow: EPAS > XPAS > SW > EPAS
Other Parameters (RDF870MB room unit only)
Item | Description | Range Factory settings | |
Output 1 (Q1) | Output for external Modbus
controller (master) |
0: Off
1: On |
0: Off |
Output 2 (Q2) | Output for external Modbus
controller (master) |
0: Off
1: On |
0: Off |
Output 3 (Q3) | Output for external Modbus
controller (master) |
0: Off
1: On |
0: Off |
Output 4 (Q4) | Output for external Modbus
controller (master) |
0: Off
1: On |
0: Off |
For complete parameter list, please refer to the document listed in the following table.
Ref. | Document title | Document number |
[1] | Datasheet | A6V11439454 |
Download above document from http://siemens.com/bt/download by searching for the document number.
WIRING
RDF870…
- 3/4 Speed Fan and ECM Fan
INFO
INSTALLATION INSTRUCTIONS
DIMENSION
Issued by
- Siemens Switzerland Ltd
- Smart Infrastructure
- Global Headquarters
- Theilerstrasse 1a CH-6300 Zug
- Tel: +41 58 724 2424
- www.siemens.com/buildingtechnologies
Open Source Software (OSS)
© Siemens Switzerland Ltd, 2019
Technical specifications and availability are subject to change without notice.
REFERENCE:
DOWNLOAD MANUALS:
Siemens RDF870KN Touch Screen Room Controller Thermostat Operating Instruction
Siemens RDF870KN Touch Screen Room Controller Thermostat Operating Instruction
Leave a Reply