PECO T8532-002 Programmable Thermostat Quick Start Guide

peco-logo

PECO T8532-002 Programmable Thermostat

PECO-T8532-002-Programmable-Thermostat-product

SET CLOCK, YEAR, MONTH, DAY

PECO-T8532-002-Programmable-Thermostat-fig-1

  1. Press ▲/ ▼ to select 12 or 24 HR mode, then press Next.
  2. Press ▲/ ▼to select the hour, then press Next.
  3. Press ▲/▼to select minutes, then press Next.
  4. Press ▲/ ▼ to select the current year, then press Next.
  5. Press ▲/ ▼ to select the current month, and press Next.
  6. Press ▲/ ▼ to select the calendar day number.
  7. Press Done to complete the operation.
    Note: Select More > Clock, to access after setup.

ACCESS SERVICE MENUS

PECO-T8532-002-Programmable-Thermostat-fig-2

  1. Hold the lower right and lower left keys for five seconds.
  2. Press the Next or the Go Back button to select a Service Menu.
  3. Press ▲/ ▼ to select the option.
  4. Press Done when complete.

CONFIGURE SERVICE MENUS
The following Service Menus (SM) commonly require configuration. Please verify that these are set for your specific application. Additional configuration may be required. Refer to Table 2 for all available Service Menus.

  • SM 100 = Programmable or Nonprogrammable
  • SM 110 = System Type
  • SM 121 = Number of Fan Speeds
  • SM 130 = Reversing Valve
  • SM 135 = W1 heat output NO or NC
  • SM 170 = Remote Sensors
  • SM 265 = Single or Dual Setpoint Operation

WIRING: TERMINAL DESIGNATIONS
Connect wires for the appropriate system type (Table 1).
WARNING: DISCONNECT POWER BEFORE BEGINNING INSTALLATION.

  • CAUTION: Use copper wire only. Insulate or wire-nut all unused leads.
  • Use care to avoid electrostatic discharge to the thermostat
  • CAUTION: Do not connect unused wires together
  • ALL ELECTRICAL LOADS MUST BE CONNECTED TO TERMINAL C (24 VAC).

TABLE 1. TERMINAL BLOCK DESIGNATIONS

C 24 VAC, Unswitched side C 24 VAC, Unswitched side
W1 Stage 1 Heat B/O Reversing Valve
W2 Stage 2 Heat AUX Auxiliary Heat (Stage 2 or 3)
G FAN High G FAN High
A FAN Medium A FAN Medium
E FAN Low E FAN Low
Y1 Stage 1 Cool Y1 Compressor Stage 1
Y2 Stage 2 Cool Y2 Compressor Stage 2
RH 24 VAC Power for heating, switched side RH 24 VAC Power for heating, switched side
RC 24 VAC Power for cooling, switched side RC 24 VAC Power for cooling, switched side
SC Sensor Common SC Sensor Common
S1 Indoor Remote Sensor S1 Indoor Remote Sensor
S2 Occupancy Sensor S2 Occupancy Sensor
 

S3

Seasonal Changeover Switch OPEN=Cooling in Summer CLOSED=Heating in Winter  

S3

 

NA

TYPICAL FAN COIL WIRING DIAGRAM

PECO-T8532-002-Programmable-Thermostat-fig-3

FAN SPEED SELECTION

PECO-T8532-002-Programmable-Thermostat-fig-4

  1. Press the Fan button to select speed/operation.
    Note: Fan Speed is noted as follows:PECO-T8532-002-Programmable-Thermostat-fig-5
  2.  Press Done when complete.
    ON = Continuous Fan Operation
    AUTO = Fan Cycles with Heating and Cooling

TABLE 2. ADVANCED CONFIGURATION: SERVICE MENUS
Some Service Menus may not be available, depending on the system type (SM 110).

MENU FEATURE OPTIONS STD. DEFAULT DESCRIPTION / COMMENTS
100 Schedule Format 0-3 1 Select the schedule format on the T8000 Series. (Menu not available on non-programmable thermostats.)

0 =  nonprogrammable

1 =  programmable

2 =  5-1-1 schedule

3 =  5-2 schedule

101 Daylight-Saving Time 0,1 0 Select daylight-saving time as it follows standard format in U.S.: It begins second Sunday of

March at 2:00 AM and ends on the first Sunday of November at 2:00 AM.

0 =  Disabled

1 =  Enabled (2007 U.S. Format)

110 System Type 1-13 1 Select the appropriate system configuration (determines available Service Menus).

1 = 1 Heat/1 Cool conventional 2 = 1 Heat/1 Cool heat pump

3 = Heat only without fan (2-wire systems) 4 = Heat only with fan

5 =  Cool only

6 = 2 Heat/1 Cool heat pump (with auxiliary heat) 7 = 2 Heat/2 Cool multistage conventional

8 =  2 Heat/ 1 Cool multistage conventional

9 =  1 Heat/ 2 Cool multistage conventional

10 = 2 Heat/ 2 Cool heat pump (no auxiliary heat) 11= 3 Heat/ 2 Cool heat pump (with auxiliary heat) 12 = NA

13= NA

120 Fan Control (heating) 0,1 1 0 = Fossil Fuel; Gas/Oil/Propane heat (equipment controls heating fan) 1 = Electric Furnace (thermostat controls heating fan)
MENU FEATURE OPTIONS STD. DEFAULT DESCRIPTION / COMMENTS
121 Fan Speeds 1, 2, 3, 4 3 Allows selection of multiple fan speeds. 1 = Single speed Fan (G terminal)

2 = 2-speed Fan (G and E Terminals)

3 = 3-speed Fan (G,A and E Terminals) 4 = 3-speed Staged Fan

130 O/B Reversing valve 0,1 0 When 0, output is active for cooling. When 1, output is active for heating. 0 = (O) Active with cooling

1 =  (B) Active with heating

135 W1 Output

Configuration

0,1 0 Changes operation of W1 for Active to Open (NC Normally Closed) to Active to Close (NO Normally Open). Must be 0 for heat pump operation.

0 = NC Operation 1 =  NO Operation

150 Backlight 0,1 0 0 =  Backlight temporarily on

1 =  Backlight always on (low intensity, 24V only)

170 Remote Sensor 0-8 0 Select sensor if used. Contact PECO for information on the T8000 Series Indoor Remote Zone Sensor. 0 = No Remote Sensors

1 = Remote Indoor Sensor Only 2 = Not Used

3 = Not Used 4 = Not Used 5 =  Not Used

6 =  S3 Input with Aquastat Only

7 = S3 Input with Aquastat and S1 with Remote Indoor Sensor 8 = Not Used

240 Number of Program Periods 2; 4 events 4 2 =  2 events per day (Selections OCC1 and UnOcc1)

4 =  4 events per day (Selections Occ1-UnOcc1-Occ2- UnOcc2)

250 Clock format 12 or 24 Hours 12 12 = 12-hour clock mode 24 = 24-hour clock mode
260 Temperature Format (°F or °C) 0,1 1 0 =  Celsius

1 =  Fahrenheit

265 Single/Dual Setpoint 0,1 1 Determines if single user override setpoint is used, or if user sets heat and cool setpoints independently. 0 = Dual Setpoint (Heat and Cool)

1 =  Single Override Setpoint (Single Setpoint with auto changeover algorithm)

290 Range Low 50-90 °F or

10-32°C

50°F (10°C) Choose the lowest selectable temperature setpoint value.
300 Range High 50-90 °F or

10-32°C

90°F (32°C) Choose the highest selectable temperature setpoint value.
310 Setback Low Off; 50-82°F or 11-27°C 55°F (13°C) Temperature setpoint thermostat will Heat to when in Setback mode (Off sets Heating to ~45F Setback). 0 = Off

50-82°F (11-27°C)

320 Setback High Off; 58-90°F or 11-32°C 90°F (32°C) Temperature setpoint thermostat will Cool to when in Setback mode. (Off sets Cooling to ~150F in Setback).

0 = Off (disabled) 58-90°F (11-32°C)

330 Zone Temp Offset +/-9°F or +/- 4.5°C 0°F (18 °C) Adjusts the sensed Zone Temperature displayed, allowing calibration in the field.
340 Keypad Lockout 0-3 0 Restricts access to certain features of device; Service Menu still available if keypad lockout is enabled. 0 = No key pad lockout (Default)

1 =  Disables Schedule and System keys

2 = Disables Schedule, System, and Fan keys 3 = Disables all keys

341 Enable Pin Access 0,1 0 Applies a 3 digit access code to enter Service Menu 342 0 = Disable

1 =  Enable

342 Set PIN 000-999 000 Choose a 3-digit PIN access code.
350 Fan Mode 1-3 3 1 =  ON: Fan is always on, regardless of demand

2 = Auto: Fan is only on with heating or cooling demand 3 = ON or Auto: Occupant can choose either selection

360 System Mode 0-3 1 Allows ability to determine which system modes the occupant can select. 0 = OFF, Auto

1 = OFF, Heat, Cool, Auto 2 = OFF, Heat, Cool

3 =  Heat, Cool, Auto

 

MENU FEATURE OPTIONS STD. DEFAULT DESCRIPTION / COMMENTS
375 Purge Enable 0-3 0 0 =  No Purge      ▲!   WARNING: Service Menu 375 may disable fan operation during valve

1 =  W1 purge. This feature should be set to 0 (zero) unless outputs are connected

2 = Y1 Purge to hydronic heating or cooling valves. Failure to follow this instruction can 3 = W1 & Y1 purge result in damage to equipment and/or property.

376 Purge Duration 1-3 1 Defines how long to open the valve to perform the purge function.

1 to 3 minutes

377 Purge Frequency 0-2 0 Defines how long to open the valve to perform the purge function.

0 =  Every 24 Hours

1 =  Every 12 Hours

2 =  Every 6 Hours

380 Minimum Deadband Adjustment 1-10°F, 0.5-5°C 3°F A changeover deadband value prevents short cycling between heating and cooling modes. The value is adjustable to meet various HVAC system requirements.
395 Temporary Occupied Duration Limit 0-4 hours 0 The temporary User Override is limited by the time defined in this service menu.

0 = Remainder of time until the next scheduled event. 1 = 1 Hour

2 =  2 Hours

3 =  3 Hours

4 =  4 Hours

480 Minimum Off Time Range:

0-10 Minutes

4 Sets the minimum off time for both the heat and cool output.
500 Programmable/ Intermittent Fan 0-2 0 In programmable mode, fan will operate continuously during occupied periods or with demand during unoccupied periods. In intermittent mode, fan will operate based on the on and off times set in menus 501 and 502 whenever there is no call for fan.

0 =  Disable

1 = Programmable Fan: Fan operates continuously in occupied periods or with demand in unoccupied periods.

2 =  Intermittent Fan: Fan operates based on the on and off times set in menus 501 and 502.

501 Intermittent Fan On Time 1-60 minutes 5 minutes Defines the duration in which fan low will be on. Fan On will be activated after Fan Off time has passed.
502 Intermittent Fan Off Time 0-60 minutes 25 minutes Defines the duration in which fan low will be off. Fan Off will be activated after Fan On time has passed.

A selection of 0 will result in continuous Fan.

520 Default Display Icons 0-4 0 Select icons that will be displayed in the Default Display screen. 0 = Time, Temp, SP

1 = Time, Temp 2 = Time only

3 = Temp only 4 =     No Display

530 Revision Upon menu selection the firmware revision, firmware checksum and configuration checksum is

displayed.

540 Factory Default Reset 0,1 0 When Enable is selected the device will return to factory default settings. 0 = Disable

1 =  Enable

Note: Press “Done” key to complete process.

600 System Test Main Output (Cool) 0-2 0 If either stage is enabled it will activate the associated output for 10 minutes. The Fan output will automatically turn on. If a different service menu is selected the output will be disabled.

0 =  Disable

1=     Cool Stage 1

2 =  Cool Stage 2

610 System Test Main Output (Heat) 0-3 0 If either stage is enabled it will activate the associated output for 10 minutes. The Fan output will automatically turn on if configured to do so. If a different service menu is selected the output will be disabled. (Note: Aux heat could be stage 2 or stage 3 based on configuration)

0 = Disable (Default) 1 = Heat Stage 1

2 =  Heat Stage 2

3 =  Heat Stage 3

620 System Fan Test Output 0-3 0 0 =  Disabled

1 =  Low Speed

2 = Medium Speed 3 = High Speed

900 Factory Use Only Factory Use Only
901 Factory Use Only Factory Use Only
902 Factory Use Only Factory Use Only

COPYRIGHT 2016 PECO, INC. ALL RIGHTS RESERVED.P/N 70864 3220-2318 REV 04

REFERENCE

DOWNLOAD MANUALS:

PECO T8532-002 Programmable Thermostat Quick Start Guide

OTHER MANUALS:

PECO T8532-002 Programmable Thermostat Product Specifications Guide

peco-logo

PECO T8532-002 Programmable Thermostat Quick Start Guide


Posted

in

by

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post’s permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post’s URL again. (Find out more about Webmentions.)