Peco T8000 Programmable Thermostat
Set Clock, Year, Month, Day
- Press ▲/ ▼ to select 12 or 24 Hr mode, then press Next.
- Press ▲/ ▼to select hour, then press Next.
- Press ▲/ ▼to select minutes, then press Next.
- Press ▲/ ▼ to select current year, then press Next.
- Press ▲/ ▼ to select current month, press Next.
- Press ▲/ ▼ to select the calendar day number.
- Press Done to complete operation. note: Select More > Clock, to access after setup.
- Hold lower right and lower left keys for fi ve seconds.
- Press Next or Go Back button to select a Service Menu.
- Press ▲/ ▼ to select Menu option.
- Press Done when complete
The following Service Menus (SM) commonly require confi guration. Please verify that these are set for your specifi c application. additional confi guration may be required. refer to Table 2 for all available Service Menus.
- SM 100 = Programmable or nonprogrammable
- SM 110 = System Type
- SM 120 = fan control
- SM 130 = reversing valve
- SM 240 = number of Program Periods
- SM 260 = Temperature format (°f or °c)
- SM 340 = Keypad lockout
Wiring: TerMinal deSignaTionS
Connect wires for the appropriate system type (Table 1).
WARNING:
- DISCONNECT POWER BEFORE BEGINNING INSTALLATION.
- Use copper wire only. Insulate or wire-nut all unused leads.
- Use care to avoid electrostatic discharge to thermostat
- Do not connect unused wires together
- ALL ELECTRICAL LOADS MUST BE CONNECTED TO TERMINAL C (24 VAC).
Table 1. Terminal blocK deSignaTionS
C | 24 VAC, Unswitched side | C | 24 VAC, Unswitched side |
W1 | Stage 1 Heat | B/O | Reversing Valve |
W2 | Stage 2 Heat | AUX | Auxiliary Heat (Stage 3) |
G | FAN | G | FAN |
A | Economizer/Damper/Humidity | A | Economizer/Damper/Humidity |
E | Stage 3 Heat | E | Emergency Heat |
Y1 | Stage 1 Cool | Y1 | Compressor Stage 1/Heat/Cool 1 |
Y2 | Stage 2 Cool (or Dehumidify) | Y2 | Compressor Stage 2/Heat/Cool 2
(or Dehumidify) |
RH | 24 VAC Power for heating, switched side | RH | 24 VAC Power for heating, switched side |
RC | 24 VAC Power for cooling, switched side | RC | 24 VAC Power for cooling, switched side |
SC | Sensor Common | SC | Sensor Common |
S1 | Indoor Remote Sensor | S1 | Indoor Remote Sensor |
S2 | Occupancy Setback Input* | S2 | Occupancy Setback Input |
S3 | Outdoor Remote Sensor | S3 | Outdoor Remote Sensor |
Table 2. Advanced configuration: SERVICE MENUS
MENU | FEATURE | OPTIONS | STD. DEFAULT | DESCRIPTION / COMMENTS |
100* | Schedule Format | 0-3 | 1 | Select the schedule format on the T8000 Series. (Menu not available on non-programmable thermostats.)
0 = nonprogrammable 1 = programmable 2 = 5-1-1 schedule 3 = 5-2 schedule |
101 | Daylight-Saving Time | 0,1 | 0 | Select daylight-saving time as it follows standard format in U.S.: It begins second Sunday of March at 2:00 AM and ends on the first Sunday of November at 2:00 AM.
0 = Disabled 1 = Enabled (2007 U.S. Format) |
110 | System Type | 1-13 | 1 | Select the appropriate system configuration (determines available Service Menus). 1 = 1 Heat/1 Cool conventional
2 = 1 Heat/1 Cool heat pump 3 = Heat only without fan (2-wire systems) 4 = Heat only with fan 5 = Cool only 6 = 2 Heat/1 Cool heat pump (with auxiliary heat) and Emergency (Em) heat 7 = 2 Heat/2 Cool multistage conventional 8 = 2 Heat/ 1 Cool multistage conventional 9 = 1 Heat/ 2 Cool multistage conventional 10 = 2 Heat/ 2 Cool heat pump (no auxiliary heat) 11= 3 Heat/ 2 Cool heat pump (with auxiliary heat) and Emergency (Em) heat 12 = 3 Heat/ 1 Cool conventional 13= 3 Heat/ 2 Cool conventional |
120 | Fan Control (heating) | 0,1 | 0 | 0 = Fossil Fuel: Gas/Oil/Propane heat (equipment controls heating fan) 1 = Electric Furnace (thermostat controls heating fan) |
130 | Changeover valve (B/O terminal) | 0,1 | 0 | 0 = B/O terminal controls valve in cooling 1 = B/O terminal controls valve in heating |
140 | Auxiliary Heat | 0,1 | 0 | 0 = Electric backup heat
1 = Fossil fuel backup heat |
150 | Backlight | 0,1 | 0 | 0 = Backlight temporarily on
1 = Backlight always on (low intensity, 24V only) |
170 | Remote Sensor | 0-5 | 0 | Select sensor if used. Contact PECO for information on the T8000 Series Indoor Remote Zone Sensor.
0 = No Sensor 1 = Indoor Sensor 2 = Outdoor Sensor display only 3 = Outdoor Sensor display and lockout control 4 = Indoor, Outdoor Sensor display only 5 = Indoor, Outdoor Sensor display and lockout control |
180 | Heat Pump | 0-45°F | 0 | If an outside sensor is used, the compressor will be locked out when the outside air temp is below |
Compressor Lockout | (-18°C – 7°C) | the value selected. | ||
0 = None | ||||
15°F( -9°C); 20°F (-7°C); 25°F ( -4°C); 30°F ( -1°C); 35°F (2°C); 40°F (4°C); 45°F (7°C) | ||||
190 | Heat Pump Auxiliary | 0- 60°F | 0 | If an outside sensor is used, the auxiliary heat will be locked out when the outside air temperature |
Lockout | (-18°C – 15°C) | is above the value selected. | ||
0 = None | ||||
40°F (4°C); 45°F (7°C); 50°F (10°C); 55°F (13°C); 60°F (16°C) | ||||
230 | Furnace Filter | 0; 30; 60; 90; | 0 | Set a filter reminder timer; appears on digital display when timer expires (if programmed). |
Change Reminder | 120; 365 | 0 = Off | ||
10 days; 30 days; 60 days; 90 days; 120 days; 365 days | ||||
240 | Number of Program Periods | 2; 4 events | 4 | 2 = 2 events per day
4 = 4 events per day |
250 | Clock format | 12 or 24 Hours | 12 | 12 = 12-hour clock mode 24 = 24-hour clock mode |
260 | Temperature Format (°F or °C) | 0,1 | 1 | 0 = Celsius
1 = Fahrenheit |
270 | Fan Off Delay Heat | 0-99 Seconds | 0 | Select the amount of time (in seconds) that the fan will run after the thermostat heat outputs are turned off. |
280 | Fan Off Delay Cool | 0-99 Seconds | 0 | Select the amount of time (in seconds) that the fan will run after the thermostat cool outputs are turned off. |
MENU | FEATURE | OPTIONS | STD. DEFAULT | DESCRIPTION / COMMENTS |
290 | Range Low | 50-90 °F or
10-32°C |
50°F (10°C) | Choose the lowest selectable temperature setpoint value. |
300 | Range High | 50-90 °F or
10-32°C |
90°F (32°C) | Choose the highest selectable temperature setpoint value. |
310 | Setback Low | Off; 50-82°F or 11-27°C | 55°F (13°C) | Select the heat setpoint for setback mode. 0 = Off
50-82°F (11-27°C) |
320 | Setback High | Off; 58-90°F or 11-32°C | 90°F (32°C) | Select the cool setpoint for setback mode. 0 = Off
58-90°F (11-32°C) |
330 | Zone Temp Offset | +/-9°F or +/- 4.5°C | 0°F (18 °C) | Adjusts the displayed value; may differ from actual zone temperature. |
340 | Keypad Lockout | 0-3 | 0 | Restricts access to certain features of device; Service Menu still available if enabled. 0 = No key pad lockout (Default)
1 = Disables Schedule and System keys 2 = Disables Schedule, System, and Fan keys 3 = Disables all keys |
341 | Enable Pin Access | 0,1 | 0 | Applies a 3 digit access code to enter Service Menu 342 0 = Disable
1 = Enable |
342 | Set PIN Access Code | 000-999 | 000 | Choose a 3-digit code. |
350 | Fan Mode Enable | 1-3 | 3 | 1 = ON: Fan is turned on regardless of demand.
2 = Auto: Fan is turned on according to heating or cooling demand. 3 = ON or Auto: Allows occupant to select either 1 or 2 above. |
360 | System Mode Enable | 0-3 | 1 | Allows ability to determine which system modes the occupant can select.
0 = OFF, Auto (0 is NOT valid for following configurations: Heat Only; Cool Only.) 1 = OFF, Heat, Cool, Auto 2 = OFF, Heat, Cool 3 = Heat, Cool, Auto |
370 | Economizer/Outside Air Damper | 0-4 | 0 | 0 = Off
1 = Time Based Output 2 = Economizer 3 = Continuous Outside Air Damper 4 = Cycled Outside Air Damper |
380 | Minimum Deadband Adjustment | 3-10°F, 1.5-5°C | 3°F | Select a changeover deadband value to prevent short cycling between heating and cooling modes. The value is adjustable to meet various HVAC system requirements. |
390 | Pre-Occupancy Purge | 0-3 hours | 0 hours | Select to energize fan for selected number of hours (0-3) prior to all occupied events. |
395 | Maximum Override Time Limit | 0=Time until next event; or
1-4 hours |
3 | Restricts the duration that a temporary hold can be set. The temporary hold is limited by the maximum amount of time as defined in this Service Menu.
0 = Remainder of time until the next scheduled event. 1 = 1 Hour 2 = 2 Hours 3 = 3 Hours 4 = 4 Hours |
400 | Cycles Per Hour (CPH) Cooling Stage 1 | 0-6 CPH | 0 CPH | Defines the number of cycles per hour for cooling (Stage 1). Select 0 to enable ON-OFF control for Stage 1 cooling. |
410 | Cycles Per Hour (CPH) Cooling Stage 2 | 0-6 CPH | 0 CPH | Defines the number of cycles per hour for cooling (Stage 2). Select 0 to enable ON-OFF control for Stage 2 cooling. |
420 | Cycles Per Hour (CPH) Heating Stage 1 | 0-12 CPH | 0 CPH | Defines the number of cycles per hour for heating (Stage 1). Select 0 to enable ON-OFF control for Stage 1 heating. |
430 | Cycles Per Hour (CPH) Heating Stage 2 | 0-12 CPH | 0 CPH | Defines the number of cycles per hour for heating (Stage 2). Select 0 to enable ON-OFF control for Stage 2 heating. |
450 | Cycles Per Hour (CPH) Emergency Heating &
Stage 3 Heat |
0-12 CPH | 0 CPH | Defines the number of cycles per hour for heating. Select 0 to enable ON-OFF control for Emergency Heating & Stage 3 Heat. |
MENU | FEATURE | OPTIONS | STD.MODEL DEFAULT | DESCRIPTION / COMMENTS |
460 | Heat Recovery Rate | 0-18°F/Hr
0-10°C/Hr |
0°F/Hr | Defines the rate at which the device achieves the heat comfort setpoint. Select 0 to disable ramp recovery. |
470 | Cool Recovery Rate | 0-18°F/Hr
0-10°C/Hr |
0°F/Hr | Defines the rate at which the device achieves the cool comfort setpoint. Select 0 to disable ramp recovery. |
480 | Minimum Off Time | 1-10 minutes | 4 minutes | Sets the minimum off time for both the heat and cool output. |
490 | Humidity Control Enable
(Select models only) |
0-3 | 0 | Selects how humidity will be controlled. When dehumidify control is enabled, the Y2 terminal becomes dehumidify. Note: If option 3 is selected, Service Menu 491 becomes available.
0 = Disabled 1 = Dehumidify Control 2 = Humidify Control 3 = Dehumidify and Humidify Control |
491 | Humidity Deadband | 10-50 | 30% relative humidity (RH) | Selects the deadband in %RH between the humidify and dehumidify setpoints. Note: If option 3 is selected in Service Menu 490, Service Menu 491 becomes available.
10; 20; 30; 40; 50 |
500 | Programmable/ Intermittent Fan | 0-2 | 0 | 0 = Disable
1 = Programmable Fan: Fan operates continuously in occupied periods or with demand in unoccupied periods. 2 = Intermittent Fan: Fan operates based on the on and off times set in menus 501 and 502. |
501 | Intermittent Fan On Time | 1-60 minutes | 5 minutes | Defines the on time for the Intermittent Fan. |
502 | Intermittent Fan Off Time | 0-60 minutes | 25 minutes | Defines the off time for the Intermittent Fan. Select 0 for continuous fan. |
510 | Power Harvesting Enable
(For use on systems in which a Common “C” power wire is unavailable) |
0-3 | 0 | Options 1-3 draw a small amount of current from load wire indicated to supplement battery supply.
0 = No power harvesting is available. Warning: Power Harvesting is intended to be used only as a 1 = Use Y1 as the battery supplement. battery supplement. If enabled, the feature preserves battery 2 = Use W1 as the battery supplement. life. If Power Harvesting is not compatible with your system, 3 = Use both Y1 and W1 as the battery supplement select “0” (default) to disable. If thermostat is powered from AC, select only “0” or off. Consult a technician if you have questions. |
520 | Default Display Icons | 0-4 | 0 | Select icons that will be displayed in the Default Display screen. 0 = Time, Temp, SP
1 = Time, Temp 2 = Time 3 = Temp 4 = None |
530 | Revision | — | — | Displays firmware revision information (for technician); not adjustable. |
540 | Factory Default Reset | 0,1 | 0 | Select 1 (enable) to restore factory default settings for thermostat. Select 0 to disable. 0 = Disable
1 = Enable Note: Press “Done” key to complete process. |
600 | System Test Main Output (Cool) | 0-2 | 0 | Select an option to activate the fan output for 10 minutes; select 0, Done or a different Service Menu to disable.
0 = Disable 1= Cool Stage 1 2 = Cool Stage 2 |
610 | System Test Main Output (Heat) | 0-3 | 0 | Select an option to activate the fan output for 10 minutes; select 0, Done or a different Service Menu to disable. Note: Outputs will be activated based upon the system configuration.
0 = Disable (Default) 1 = Heat Stage 1 2 = Heat Stage 2 3 = Heat Stage 3 |
620 | System Test Fan Output | 0,1 | 0 | Select 0 or 1 to activate the fan output for 10 minutes; select 0, Done or a different Service Menu to disable.
0 = Disable Fan Output 1 = Enable Fan Output |
630 | System Test Emergency Output | 0,1 | 0 | Select 0 or 1 to activate the Emergency output for 10 minutes; select 0, Done or a different Service Menu to disable.
0 = Disable Emergency Output 1 = Enable Emergency Output |
640 | System Test Economizer | 0,1 | 0 | Select 1 to activate the Economizer output for 10 minutes; select 0, Done or a different Service Menu to disable.
0 = Disable Economizer Output 1 = Enable Economizer Output |