Aube-logo

Aube Technologies TH144 Electronic Thermostat

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-PRODUCT

Installation

TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK.
Installation should be carried out by an electrician or a qualified technician.

Find a Location for the Thermostat

Prepare and Connect the Thermostat

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-1

TABLE 1: Wiring Terminals

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-31

For 2H1C & 3H2C models, the AC144-02 is required to use the balance point option (compressor cut-off).

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-2

Connecting the REM input (optional)

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-3
To remotely activate the Unoccupied mode, the REM input allows connection to an optional CT240/CT241 telephone controller, a central timer or an alarm system. A closed contact remotely activates the Unoccupied mode (see 4.1).

Connecting the AC144-02 RTI (optional)
The AC144-02 Remote Temperature Interface (RTI) connects to a TH144 thermostat for remote indoor or outdoor temperature readings.
NOTE: If you wish to use the balance point cut-off function to cut the heat pump compressor when the outdoor temperature drops below the defined cut-off setpoint (see section 4.4 to define this setpoint), you must connect a remote temperature interface.
NOTE: Refer to the AC144-02 installation instructions for details on how to connect the RTI to the thermostat.

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-5

Remote Indoor Sensing
The REM icon indicates that the temperature is controlled from a remote location using the RTI’s housing sensor or the connected probe(s). Temperature averaging can be obtained using up to 4 probes. To return to local control, disconnect the RTI wires at the thermostat terminals and turn off for at least 5 seconds.

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-6

Remote Outdoor Sensing
The OUT icon indicates the outdoor temperature read from the outdoor probe connected to the RTI. On some models (2H1C & 3H2C), the outdoor temperature is used for the compressor
cut-off point.

First Power On
When you power TH144 for the first time, it runs a sequence of tests and resets itself, which lasts approximately 10 seconds. The default setpoint is 20°C (68°F).
NOTE: The displayed ambient temperature might be higher than the real ambient temperature if you are holding the thermostat. For the programmable models, open the thermostat’s door, and set the time (Hour and Minute) and day (Day).

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-7
NOTE: To protect the compressor, TH144 has an On/Off delay of 2 or 4 minutes (default is 2 minutes) before starting or stopping the system (see the following section).

Configure the TH144

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-8
The TH144 offers many configuration options using the DIP switches located on the back of the thermostat. Default settings are inside the shaded cells.
NOTE: After first power-up, wait at least 5 minutes while the internal battery is being charged before configuring TH144.

Name DESCRIPTION UP DOWN
 

Display

Select the display format. When you change the display format, the set- points revert to their default values.  

°C/24h

 

°F/12h

 

 

 

 

 

Cycle

20 minutes = heavy commercial applications

15 minutes = residential & light commercial applications

NOTE: On models not equipped with the Protect switch, the On/Off delay is set based on the cycle. That is, the On/Off delay is 4 minutes for the 20 minute-cycle and is 2 minutes for the 15 minute-cycle.

 

 

 

 

20 min.

 

 

 

 

15 min.

 

Aux

W = the compressor turns Off during auxiliary heating.

W + Y = the compressor remains On during auxiliary heating.

 

W

 

W+Y

 

 

 

Keys

Lock the keypad. The      icon is dis- played when any button is pressed to indicate that the setpoint or operating mode cannot be modified. On the pro- grammable models, the schedule can- not be modified as well.  

 

Lock

 

 

Unlock

 

Protect

To protect the compressor against too frequent On/Off, TH144 provides an On/Off delay selectable via this switch.  

4 min.

 

2 min.

Stages Select between 2H2C and 1H1C. 1H1C 2H2C
 

Valve

Select the polarity of the reversing valve. B= the valve is energized during heating. O= the valve is energized dur- ing cooling.  

B

 

O

Basic Configuration

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-9Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-10

Select the Control Mode
The mode indicates which system is used for temperature control. Use the Heat / Cool button to select one of the following modes:

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-11

Predefined Setpoints
Predefined setpoints represent the temperature that you wish to have during the day, at night or while you are away. The Comfort and Economy setpoints are used with the Automatic mode (schedule, for programmable models) while the Unoccupied setpoint can be used with the Unoccupied mode (activated manually or remotely). This table displays the default setpoints:

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-12

To Modify the Predefined Setpoints
NOTE: If your thermostat controls both HEATING and COOLING, the predefined setpoints must be configured for both applications.
NOTE: The Cool setpoints cannot be lower than the Comfort Heat setpoint. If this should happen, the TH144 will automatically set your Cool setpoint 1°C (1°F) higher than your Comfort Heat setpoint.

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-13

View the Current Setpoint
To view the current setpoint, briefly press one of these buttonsAube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-15 once. The arrow indicates the setpoint.

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-14

Programming

Program Your Schedule
The TH144 allows four setting changes for each day of the week. There are no pre-set programs. For each day, enter the time at which you wake up (P1), the time you leave for work (P2), the time you return home (P3) and the time you go to bed (P4):

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-16

NOTE: For temperature increases (P1 and P3), allow at least 15
minutes per 1°C (2°F). For example, if you have lowered the temperature
by 3°C (6°F) during the night and you wake up at 7 a.m., program
the change for 6:15 a.m.
To reduce energy costs, you must lower the temperature for a period
of 2 to 3 times the delay required to bring the temperature back to
your comfort level.

Set or Modify the Programs

Programming Example
Comfort (programs 1 and 3):

Economy (programs 2 and 4)

To program this schedule

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-18

To erase programs 2 and 3 for Saturday and Sunday

  1. Press Program to access programming mode.
  2. Press Program until P2 is selected.
  3. Press Day to select Saturday (SA) and press Clear.
  4. Press Day to select Sunday (SU) and press Clear.
  5. Repeat steps 2 to 4 for P3.
  6. Press Mode/Return to exit.

Select the Operating Mode

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-20
The TH144 offers 2 operating modes:

Automatic

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-21
This mode executes the programmed schedule.
To activate:
Press Mode/Return until is displayed. The associated program setpoint icon is also displayed.
NOTE: This mode can be bypassed for up to two hours (see 4.2).

Manual

Maintains a constant temperature. To activate:

if you are using the automatic changeover mode, see 2.1 and 4.5.

Other Information

Remote Unoccupied

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-26
When the REM input is connected to a central system or a telephone controller and a signal is received through this input, the TH144 will switch to the unoccupied setpoint.

2-hour Temporary Bypass

When the TH144 is in Automatic Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-15or Remote Unoccupied mode, you can temporarily bypass the current setpoint for a 2-hour period after which it will return to the previous mode.
Automatic (schedule programs)

Fan Modes (Fan button)
The TH144 thermostat is equipped with a fan button offering two fan settings: On and Automatic.

Balance Point Cut-Off
The 2H1C et 3H2C models require the AC144-02 Remote Temperature Interface and the outdoor sensor to use this function. This option allows the user to define the temperature setpoint at which the heat pump compressor will be cut-off and only the auxiliary heat will be used when heating is required. The auxiliary heat is automatically activated on a call for heat when
the outdoor temperature falls below the balance point. The heat pump compressor will be re-activated only when the outdoor temperature is at least 1°C (1°F) higher than the cut-off setpoint. The default balance point cut-off is -8°C (17°F).

  1. Press Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-15and hold Heat/Cool until the setpoint is displayed.
  2. Use theAube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-15 buttons to set the new balance point.
  3. Press Heat/Cool to exit.

Automatic Changeover

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-28

When the AUTO mode (automatic changeover) is selected, the thermostat analyzes the system’s requirements and automatically alternates between HEAT and COOL mode to provide occupant comfort. There are two ways to use the automatic changeover mode

Fixed Setpoint
When you set the temperature using the arrow buttons, the TH144 uses this unique temperature setpoint for temperature control. The thermostat automatically switches to HEAT mode when the ambient temperature drops under the temperature setpoint whereas the COOL mode is activated when the temperature rises above the temperature setpoint. In order to switch modes, the ambient temperature must be maintained over or under the control band for more than 12 minutes. Predefined Setpoint ( , or ) When a predefined setpoint button is selected, the TH144 uses the corresponding COOL and HEAT setpoint temperatures for temperature control. The thermostat automatically switches to COOL mode when the ambient temperature rises above the COOL setpoint whereas the HEAT mode is activated when the ambient temperature drops below  the HEAT setpoint. In order to switch modes, the ambient temperature must be maintained over or under the setpoint control band for more than 12 minutes

Aube-Technologies-TH144-Electronic-Thermostat-User-Guide-FIG-30

Technical Specifications

Accessories

Warranty

AUBE warrants this product, excluding battery (if applicable), to be free from defects in the workmanship or materials, under normal use and service, for a period of three (3) years from the date of purchase by the consumer. If at any time during the warranty period the product is determined to be defective or malfunctions, AUBE shall repair or replace it (at AUBE’s option).
If the product is defective,

  1. return it, with a bill of sale or other dated proof of purchase, to the place from which you purchased it, or
  2. contact AUBE. AUBE will make the determination whether the product should be returned, or whether a replacement product can be sent to you.

This warranty does not cover removal or reinstallation costs. This warranty shall not apply if it is shown by AUBE that the defect or malfunction was caused by damage which occurred while the product was in the possession of a consumer. AUBE’s sole responsibility shall be to repair or replace the product within the terms stated above. AUBE SHALL NOT BE LIABLE FOR
ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT. Some provinces, states or regions do not allow the exclusion or limitation of incidental or consequential damages, so this limitation may not apply to you. THIS WARRANTY IS THE ONLY EXPRESS WARRANTY AUBE MAKES ON THIS PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IS HEREBY LIMITED TO THE THREE-YEAR DURATION OF THIS

WARRANTY. Some provinces, states or regions do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. This warranty gives you specific legal rights, and you may have rights which vary from one province, state or region to another

Technical Assistance

For more information on our products, go to www.aubetech.com

REFERENCE

Download Manual

Aube Technologies TH144 Electronic Thermostat user Guide

Aube-logo

Aube Technologies TH144 Electronic Thermostat user Guide

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)